”mbtO”

- this parameter defines maximal time (sec) between following frames received by
the device. If the delay will be greater than the value of  

”mbtO”  

parameter, the

relays  and analogue outputs which are controlled via RS-485 interface, will set to
alert state (see 

"OUtP" menu, 

 and 

“rEL1” menu

 

description). Parameter “

mbtO

can be set to values from 0 to 99 seconds. The value 0 means that the time will be

not controlled.

”rESP”

-  this parameter defines minimal (additional) delay between the Modbus message

and   the   answer   of   the   device   (received   and   sent   via   RS-485   interface).   This

additional delay allows the device to work with poor RS-converters which do not

works properly on baud rates higher than 19200. This parameter can be set to one

of values:

”Std”

- answer as quick as possible, no additional delay

” 10c”
” 20c”
” 50c”
”100c”
”200c”

- answer delayed of 10, 20,   50, 100 of 200 chars respectively, where

one character time depends on selected baud rate

In the most cases parameter  

”rESP”

  should be set to  

”Std”  

(no additional delay).

Unfortunately   for   some   third   party   RS-converters  

”rESP”

  should   be   adjusted

experimentally. Table 7.2 contains most frequently used values.

”bAud” parameter

“38.4”

“57.6”

“115.2”

”rESP” parameter

“ 10c”

“ 20c”

“ 50c”

Tab.7.2. 

 

Settings of 

”rESP” 

parameter

7.3.12. 

 

 ”Edit”

 

  paramet

 

 er

This parameter allows to change the edition mode of numerical parameters:

”dig”

- the change to “by digit” mode,

”Slid”

- slide change mode.

7.3.13. 

 

 ”dEFS”

 

  parameter

 This setting allows to restore the factory settings of the device. To get the access  to this 

option special password is required: „5465”, next the device displays acknowledge question 

„SEt?”

. Press

 

 

[ENTER] 

to acknowledge the restoring of factory settings or 

[ESC]

 to cancel.

7.3.14. 

 

 ”SErv” menu

This   menu   contains   the   parameters   for   authorized   service   only.   To   enter   this   menu

proper service password must be entered. Improper settings can causes of damage of the

device.

40

i

Содержание SUR-457

Страница 1: ...UR 457 Firmware v 1 00 or higher Input type universal Wall mounting case IP 67 Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement cha...

Страница 2: ...rEL1 menu 29 7 3 2 bEEP menu 31 7 3 3 inPt menu common parameters 31 7 3 4 inPt menu parameters of temperature inputs 32 7 3 5 inPt menu parameters of current and voltage inputs 32 7 3 6 OutP menu 34...

Страница 3: ...g to this manual local safety and EMC regulations If the device is equipped with PE connector it should be connected to PE wire Otherwise PE wire should be connected to GND connector The unit must be...

Страница 4: ...mpensated automatically RTD and TC inputs are fully linearised It is allowed to use only one input at the same time Input ranges are described in the next chapter Result is showed on 4 digit LED displ...

Страница 5: ...nt input resistance 65 W typical 30 W Accepted prolonged input overload 20 Voltage input 10V range 0 5 V 1 5 V 0 10 V 2 10 V Voltage measurement accuracy 0 1 25 C one digit for 0 10 V range Voltage in...

Страница 6: ...y output 24V 5 10 max 100 mA stabilized Relay output 2 or 4 NO 5A 250V AC resistance 3A 250V AC reactance OC type output 2 or 4 30mA 30VDC 100mW Active current output range max 0 24 mA Load resistance...

Страница 7: ...o 50 C Storage temperature depending on version 10 C to 70 C or 20 C to 70 C Humidity Altitude 5 to 90 no condensation up to 2000 meters above sea level Screws tightening max torque 0 5 Nm Max connect...

Страница 8: ...t be conducted with a disconnected power supply Protecting the power supply connections against unauthorized persons must be taken into consideration 4 1 UNPACKING After removing the unit from the pro...

Страница 9: ...User manual METER SUR 457 Figure 4 1 Device and assembly dimensions of the case 9 230 mm 140 mm 96 5 mm 212 mm 122 mm 8 4 4 4...

Страница 10: ...ver tightening can lead to damaging the connections inside the units and breaking the thread In the case of the unit being fitted with separable clamps they should be inserted into appropriate connect...

Страница 11: ...tion between the filter and the unit should be as short as possible and the metal housing of the filter must be connected to the earth with the largest possible surface The cables connected to the fil...

Страница 12: ...6 7 8 9 10 11 12 18 19 20 21 22 18 21 20 21 RTD RTD mV V mA TC Uo DATA DATA GND 24V 5 10 Imax 100mA 13 14 15 16 17 OC1 OC4 Umax 30V DC Imax 30mA Pmax 100mW OC4 optional OC3 optional OC2 optional OC1...

Страница 13: ...0mA Pmax 100mW OC3 optional Passive isolated Current output 4 20mA optional R1 optional R2 optional n c 3 PE 1 2 Power supply depending on version 4 5 6 7 8 9 10 11 12 18 19 20 21 22 18 21 20 21 RTD R...

Страница 14: ...rrent converters Figure 4 12 Connection of 3 wire current converters 14 18 19 20 21 22 13 14 15 16 17 internally connected External power supply 18 19 20 21 22 24V DC 18 19 20 21 22 13 14 15 16 17 int...

Страница 15: ...DIFFERENT When 3 wires connection is used the resistance of particular wires Ra Rd MUST BE IDENTICAL to enable proper compensation of it s resistance The resistance of particular wire should not be g...

Страница 16: ...switching of inductive loads coils contactors power relays electromagnets motors etc it is required to use additional suppression circuit typically capacitor 47nF min 250VAC in series with 100R 5W re...

Страница 17: ...ction Figure 4 18 Example of active current outputs connection for device with active current output only 17 11 12 ACTIVE current output optional current input 0 20 mA Logic controller 9 10 Uo 16 17 O...

Страница 18: ...ice with passive current output only Figure 4 20 Example of active voltage outputs connection for device with active voltage output only 18 11 12 ACTIVE current output optional current input 0 20 mA L...

Страница 19: ...ct marked with this symbol should not be placed in municipal waste Please check local regulations for disposal of electronic products 5 FRONT PANEL DESCRIPTION Symbols and functions of push buttons Sy...

Страница 20: ...Figure 6 3 Figure 6 1 Definitions of measurement ranges in mode 4 20mA If the result of measurement exceeds the permissible measurement range warning Hi or Lo is displayed rather than input signal de...

Страница 21: ...oller is equipped with peaks detection function It can detect a peaks of the input signal and display their values Presets connected with this function are placed in HOLd menu see description of HOLd...

Страница 22: ...parameters SEtP SEt2 HYSt modE t on toFF unit and AL Depend on modE parameter relays can be not used or controlled over one or two thresholds values If one threshold is used Figure 6 5 the relay can...

Страница 23: ...ys state changes moments for t on 0 toFF 0 tA tB tC tD time periods while input signal is in zone A or zone B Figure 6 7 Principle of LED relay output operation for one threshold mode 23 zone B zone A...

Страница 24: ...least t on see points BON DON Figure 6 7 a d e Similarly the relay will be turned off if time toFF elapse since the input signal value exceeds any of the border values see points BOFF DOFF Figure 6 7...

Страница 25: ...g process the relay output changes his state depends of both SEtP and SEt2 thresholds in similar way as it was described in one threshold mode If two threshold mode is used modE parameter defines stat...

Страница 26: ...cription of SECu menu user can change the value of particular threshold pressing button ENTER see PARAMETERS EDITION If particular parameter has been changed and confirmed in quick view mode its new v...

Страница 27: ...e of current position flashing digit or the sign Short pressing of the ENTER button causes change of the position digit Press ENTER at least 2 seconds to accept the changes after that question SEt is...

Страница 28: ...change of value acceleration deceleration direction change While editing switch parameter selection of switch parameter If numerical parameter is being edited a short press of ENTER button change edit...

Страница 29: ...out value Threshold is the medium value of relay hysteresis HYSt hysteresis of relay range 0 999 Full hysteresis of the relay is equal to 2 times HYSt parameter The relay state can change when an inp...

Страница 30: ...meter is set by unit parameter toFF turn off delay time the relay is turned off with delay equal toFF if the input value exceeds appropriate border value defined with threshold and hysteresis at least...

Страница 31: ...c signal r3 if this parameter is set to on activation of LED R3 causes by acoustic signal r4 if this parameter is set to on activation of LED R4 causes by acoustic signal Acoustic signal turned on by...

Страница 32: ...Sqr square Sqrt square root When one of those characteristics is chosen display range is defined by Lo C and Hi C USEr user defined characteristic Maximal length 20 points Every point is defined by u...

Страница 33: ...prox 1 5 sec After that device waits for selection of point being deleted by v buttons The short pressing of ENTER button causes by switching between X and Y value of the displayed point The long pres...

Страница 34: ...raph the procedure of the permissible input range determining is presented in details If the measurement value do not exceeds permissible measurement range but displayed value exceeds range 999 9999 t...

Страница 35: ...e B higher range limit 20mA 5V 10V A lower range limit 0mA 4mA 0V 1V 2v OutL parameter can be greater than OutH In this case the conversion characteristic is reversed it means that if input value rais...

Страница 36: ...t to 3 4 mA 0 0 current will be set to 0 mA For passive current output noCH current will not change 22 1 current will be set to 22 1 mA 3 4 current will be set to 3 4 mA For active voltage output noCH...

Страница 37: ...coL9 the display will change colour to the one which corresponds to selected value coL1 red coL9 green when relay changes its state to active C AL control the display colour according to alarm situat...

Страница 38: ...hysteresis to threshold hysteresis zone Presented parameters should be set ensuring that values SEtP HYSt and SEtP HYSt do not exceed the measured range CrES permission to use any local key to confirm...

Страница 39: ...le to use it again The one use password can be restored by Service Division only A r1 A r4 this option permits user on or prohibits oFF to modify the thresholds of the relays LEDs R1 R4 without knowle...

Страница 40: ...delayed of 10 20 50 100 of 200 chars respectively where one character time depends on selected baud rate In the most cases parameter rESP should be set to Std no additional delay Unfortunately for som...

Страница 41: ...U ESC MENU ESC bEEP MENU ESC inPt MENU ESC AL r1 r2 r3 r4 Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC tYPE Parameter edition ENTER MENU ESC ENTER ENTER MENU ESC SEtP SEt2 HYSt modE t on toFF...

Страница 42: ...ESC Scod A r1 A r2 A r3 A r4 ENTER MENU ESC ENTER ENTER MENU ESC modE PEA timE Hdis H r1 H r2 H r3 H r4 MENU ESC SEt 0 _ _ _ ENTER ENTER MENU ESC ENTER MENU ESC ENTER ENTER MENU ESC SCoL C r1 C r2 C...

Страница 43: ...tion of the normalized result it means result of 0 1 range To do it the begin of the input range 0 mA for 0 20mA range and 4mA for 4 20mA range must be subtracted from measured value Next received res...

Страница 44: ...er In such a case for an increasing value of input current the displayed value decreases Figure 9 1 Normal Lo C Hi C and inverted Lo C Hi C characteristic 9 1 2 Square characteristic The normalized re...

Страница 45: ...normalized result In the device computes specific segment e g for characteristic from figure below and In 0 65 the segment between points X 50 0 and X 70 0 will be chosen Let s mark those points as PL...

Страница 46: ...mA 6 mA and this result should be divided by the width of input range 16 mA Finally the normalized result In 6 16 0 375 In case when input current exceeds nominal measurement range calculations are si...

Страница 47: ...square characteristic 0 375 2 1200 300 211 and next the Lo C value is added to the result so the displayed value W 211 300 89 b Iin 2 5 mA and In 0 0938 W 287 c Iin 20 5 mA and In 1 0313 W 1295 Exampl...

Страница 48: ...Y6 PL 30 X7 PH 40 Y7 PH 80 and Ip 0 3 the displayed value W In I p Y PH Y PL X PH X PL 100 Y PL 0 375 0 3 80 30 40 30 100 30 67 b Iin 2 5 mA and In 0 0938 because of the normalized In value is lower...

Страница 49: ...e read by 03h function and wrote by 06h single registers or 10h group of the registers accordingly to Modbus RTU specification Maximum group size for 03h and 10h functions can not exceeds 16 registers...

Страница 50: ...nu characteristic type 0 linear 1 square 2 square root 3 user defined 12h Yes 0 255 FiLt parameter in InPt menu time constant in seconds 13h Yes 0 3 Pnt parameter in InPt menu the copy of 03h register...

Страница 51: ...99 HySt parameter in rEL1 menu no decimal point included 32h Yes 0 5 modE parameter in rEL1 menu 0 noAC mode 1 on mode 2 oFF mode 3 in mode 4 out mode 5 modb mode 33h Yes 0 999 t on parameter in rEL1...

Страница 52: ...u no decimal point included 48h Yes 999 9999 SEtP parameter in rEL4 menu no decimal point included 49h Yes 999 999 HySt parameter in rEL4 menu no decimal point included 4Ah Yes 0 5 modE parameter in r...

Страница 53: ...red 9 green 66h Yes 0 1 CrES parameter in CoL menu reset of colour indication 0 oFF 1 on 67h Yes 0 1 dir parameter in CoL menu direction of value changes 0 morE 1 LESS 68h Yes 999 9999 SEtP parameter...

Страница 54: ...meter in OUtP menu for active and passive current output expressed in 0 1 Yes 0 99 Hi r parameter in OUtP menu for active voltage output expressed in 0 1 A5h1 Yes 0 3 AL parameter in OUtP menu active...

Страница 55: ...EXAMPLES OF QUERY ANSWER FRAMES Examples apply for device with address 1 All values are represent hexadecimal Field description ADDR Device address on modbus network FUNC Function code REG H L Starti...

Страница 56: ...7B DATA identification code 21DAh 3 Change of the device address from 1 to 2 write to reg 20h ADDR FUNC REG H L DATA H L CRC L H 01 06 00 20 00 02 09 C1 DATA H 0 DATA L new device address 2 The answe...

Страница 57: ...UNT L the count of being read registers max 16 The answer ADDR FUNC BYTE C DATA H1 L1 DATA H2 L2 DATA H3 L3 CRC L H 01 03 06 00 0A 00 00 00 01 78 B4 DATA H1 L1 reg 01h 10 displayed value 1 0 DATA H2 L...

Страница 58: ...ysteresis of relay R2 0 0 29 modE Operation mode of relay R2 on 29 t on Turn on delay of relay R2 0 0 30 toFF Turn off delay of relay R2 0 0 30 unit Unit of t on toFF parameters of relay R2 SEC 30 AL...

Страница 59: ...Shifting of measurement scale 0 0 32 CHAr Conversion characteristic mode Lin 32 Pnt Decimal point position 0 0 32 Lo C Minimum displayed value for nominal range 000 0 32 Hi C Maximum displayed value...

Страница 60: ...menu modE Kind of detected changes norm 38 PEA Minimum detected change 0 0 38 timE Maximum time of peak displaying 0 0 38 HdiS The type of displayed value HOLd 39 H r1 Source of relay R1 and LED R1 co...

Страница 61: ...cription Default value User s value Desc page mbtO Maximum delay between received messages 0 40 rESP Additional delay of answer transmission Std 40 Configuration of numerical parameters edition Edit N...

Страница 62: ...SIMEX Sp z o o ul Wielopole 11 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Отзывы: