User manual - METER SRT-N118-XA
Register Write
Range
Register description
51h
Yes
0 ÷ 9999
“
PEA
” parameter in “
HOLd
” menu (minimum detectable
change, no decimal point included)
52h
Yes
0 ÷ 199
“
timE
” parameter in “
HOLd
” menu,
maximum peaks'
(or drops') display time expressed in seconds
53h
Yes
0 ÷ 1
“
HdiS
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
54h
Yes
0 ÷ 1
“
H r1
” parameter in “
HOLd
” menu
:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
55h
Yes
0 ÷ 1
“
H r2
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
58h
1
Yes
0 ÷ 1
“
HOut
” parameter in “
HOLd
” menu:
0
- “
rEAL
” mode ;
1
- “
HOLd
” mode
A0h
1
Yes
0 ÷ 2
“
Omod
” parameter in “
OUtP
” menu (current output mode)
0
-
current output disabled
;
1
-
current output enabled
with
4
÷
20 mA
mode;
2
-
current output controlled via RS-485
interface
A1h
1
Yes
-999 ÷ 9999
“
OUtL
” parameter in “
OUtP
” menu,
no decimal point included
A2h
1
Yes
-999 ÷ 9999
“
OUtH
” parameter in “
OUtP
” menu,
no decimal point included
A3h
1
Yes
0 ÷ 299
“
Lo r
” parameter in “
OUtP
” menu, expressed in 0.1%
A4h
1
Yes
0 ÷ 199
“
Hi r
” parameter in “
OUtP
” menu, expressed in 0.1%
A5h
1
Yes
0 ÷ 2
“
AL
” parameter in “
OUtP
” menu (current output value on
critical exception):
0
- no change;
1
- 22.1 mA;
2
- 3.4 mA
1
- these registers are active only if device is equipped with current output
2
- after writing to register no 20h the device responds with an “old” address in the message.
3
- after writing to register no 22h the device responds with the new baud rate.
4
- the value of the “
mbAc
” parameter is also connected to write to this register, so it is possible to block a writes, but
impossible to unblock writes via RS-485 interface, The unblocking of the writes is possible from menu level only.
10.2.
TRANSMISSION ERRORS DESCRIPTION
If an error occurs while write or read of single register, then the device sends an error
code according to Modbus RTU specifications (example message no 1).
Error codes:
01h
- illegal function (only functions 03h, 06h and 10h are available),
02h
- illegal register address
03h
- illegal data value
08h
- no write permission ( see: “
mbAc
” parameter)
A0h
- exceed of upper border of input range
60h
- exceed of lower border of input range
A0h and 60h codes can appear only during reg. 01h is reading by 03h function (read of
a single register).
10.3.
EXAMPLES OF QUERY/ANSWER FRAMES
38