User manual - MODULE SLI-8
6.1.
LIST OF REGISTERS
Register
Write
Range
Register description
01h
1
No
2
0000 ÷ FFFFh
Higher byte of counter corresponding to input 1
02h
No
2
0000 ÷ FFFFh
Lower word of counter corresponding to input 1
03h
1
No
2
0000 ÷ FFFFh
Higher byte of counter corresponding to input 2
04h
No
2
0000 ÷ FFFFh
Lower word of counter corresponding to input 2
05h
1
No
2
0000 ÷ FFFFh
Higher byte of counter corresponding to input 3
06h
No
2
0000 ÷ FFFFh
Lower word of counter corresponding to input 3
07h
1
No
2
0000 ÷ FFFFh
Higher byte of counter corresponding to input 4
08h
No
2
0000 ÷ FFFFh
Lower word of counter corresponding to input 4
09h
1
No
2
0000 ÷ FFFFh
Higher byte of counter corresponding to input 5
0Ah
No
2
0000 ÷ FFFFh
Lower word of counter corresponding to input 5
0Bh
1
No
2
0000 ÷ FFFFh
Higher byte of counter corresponding to input 6
0Ch
No
2
0000 ÷ FFFFh
Lower word of counter corresponding to input 6
0Dh
1
No
2
0000 ÷ FFFFh
Higher byte of counter corresponding to input 7
0Eh
No
2
0000 ÷ FFFFh
Lower word of counter corresponding to input 7
0Fh
1
No
2
0000 ÷ FFFFh
Higher byte of counter corresponding to input 8
10h
No
2
0000 ÷ FFFFh
Lower word of counter corresponding to input 8
11h
Yes
0000h
Simultaneous zeroing of all counters
This register is
write only
12h
Yes
0 ÷ 255
Denouncing Filter state:
0
- disabled;
1
- filter setting
F
Input frequency equals: 1 / (
F
x 100 us)
13h
Yes
0 ÷ 255
Current binary state of inputs
20h
3
Yes
1 ÷ FFh
Device address. New devices has default address = FEh
21h
No
Device identification code (ID)
22h
4
Yes
0 ÷ 7
Baud rate [bit/sec]:
0
- 1200;
1
- 2400;
2
- 4800;
3
- 9600;
4
- 19200;
5
- 38400;
6
- 57600;
7
- 115200
FFF3h
No
0000 ÷ FFFFh
Firmware version (hexadecimal):
e.g.: value
0123h
means version
1.23
1
- higher byte of this register is always set to 00h.
2
- it is possible to write value
0000h - zeroing of single counter
3
- after writing to register no 20h the device responds with an “old” address in the message.
4
- after writing to register no 22h the device responds with the new baud rate.
If register 20h is being written it is possible to use BROADCAST frame (with
address 00). This operation causes changing of addresses of all modules
connected to the RS-485 network. Modules receive and interprets BROADCAST
frames, but do not transmit answers.
10
i
Содержание SLI-8
Страница 14: ...User manual MODULE SLI 8 14...
Страница 15: ...User manual MODULE SLI 8 15...