This parameter can be set from 0 to 99.9% (for active current output and active
voltage output) or from 0 to 29.9% (for passive current output).
Parameter
“Hi r”
defines higher border of the range due to formula:
Out
max
=
B
+ (
B
× “
Hi r
” %), where:
B
– higher signal value range limit.
This parameter can be set from 0 to 19.9% (for active and passive current
output) or from 0 to 9.9% (for active voltage output).
DISPLAY VALUES CALCULATION
paragraph
the procedure of the analogue outputs determining is presented in details.
“
AL
”
- this parameter determines the behaviour of analogue output if any critical situation
occurs. According to version of the device, this parameter can be set:
For active current output:
“noCH”
- current will not change,
“22.1”
- current will be set to 22.1 mA,
“3.4”
- current will be set to 3.4 mA,
“0.0”
- current will be set to 0 mA.
For passive current output:
“noCH”
- current will not change,
“22.1”
- current will be set to 22.1 mA,
“3.4”
- current will be set to 3.4 mA,
For active voltage output:
“noCH”
- voltage will not change,
“11.0”
- voltage will be set to 11 V,
“5.5”
- voltage will be set to 5.5 V,
“1.2”
- voltage will be set to 1.2 V.
“0.6”
- voltage will be set to 0.6 V,
“0.0”
- voltage will be set to 0 V.
When the critical situation goes, the output signal will be set to value calculated due to
formulas given above.
7.3.7.
“
C
trL” Menu
The menu includes configuration options for the control loops of the PID controller
featured in the device.