The boiler must be installed in a fixed loca-
tion  and  only  by  specialised  and  qualified
firms  in  compliance  with  all  instructions
contained in this manual. 
Furthermore,  the  installation  must  be  in
accordance  with  current  standards  and
regulations.

2.1

INSTALLATION

–  These  boilers  can  be  installed  in  all  normal

domestic  environments  as  a  room  sealed
multi function boiler.

–  These  boilers  can  also  be  installed  in  par-

tially covered areas, as per EN 297, with a
maximum  ambient  temperature  of  60°C
and  a  minimum  ambient  temperature  of  -
5°C.  It  is  generally  advisable  to  install  the
boilers below weathered roofs, on the bal-
cony  or  in  a  protected  niche,  to  protect
them from exposure to weathering agents
(rain,  hail  and  snow). All  boilers  provide  a
standard antifreeze function. 

2.1.1

Anti-freeze function

The  boilers  are  equipped  with  anti-freeze
function which activates the pumps and the
burner when the temperature of the water
contained  inside  the  appliance  drops  to
below 6°C. 
The  anti-freeze  function  is  ensured,  howe-
ver, only if:
- the  boiler   is  correctly  connected  to  the

gas and electricity supply circuits;

- the boiler is constantly fed;
- the boiler ignition is not blocked;
- the  essential  components  of  the  boiler

are all in working order.

In  these  conditions  the  boiler  is  protected
against  frost  down  to  an  environmental
temperature of -5°C.

ATTENTION: In the case of installation in a
place where the temperature drops below
0°C,  the  connection  pipes  must  be  pro-
tected. 

2.2

COMPLEMENTARY 

ACCESSORIES

To simplify connections to the hydraulic and
gas  supplies,  it  is  also  possible  to  use  the
following accessories:
– Mounting plate, code 8101218
– Kit  with bends, code 8075423
– Kit with faucets, code 8091820
– Solar  kit  INSOL  only  for  heating  boilers,

code 8092235

– Mixed area kit ZonaMIX, code 8092234
– Antifr eeze  heat er s  kit  -15° C,  code

8089805.

– Hydraulic  connection  kit  boiler/tank  unit

code 8091112.

For detailed information on the assembly of
fittings,  see  the  instructions  contained  in
the box.

2.3

CONNECTING UP SYSTEM

To protect the heat system from damaging
corrosion,  incrustation  or  deposits,  before
installation  it  is  extremely  important  to
clean  the  system  using  suitable  products
such  as,  for  example,  FERNOX.  Complete
instructions are provided with the products
but,  for  further  information  please  contact
the Hunt Heating technical department.
For  long-term  protection  agains  corrosion
and  deposits,  the  use  of  inhibitors  such  as
Fernox is recommended after cleaning the
system.  It  is  important  to  check  the  con-
centration  of  t he  inhibit or  af t er  each
system modification and during maintenan-
ce  following  the  manufacturer’s  published
instructions. The safety valve drain must be
connected  to  a  collection  funnel  to  collect
any  discharge  during  interventions.  If  the
heating system is on a higher floor than the
boiler, install the on/off taps supplied in kit
op tional  on  t he  heating  sy s t em
delivery/return pipes. 

WARNING:  Failure  to  clean  the  heat
system or add an adequate inhibitor inva-
lidates the appliance’s warranty.

Gas  connections  must  be  made  in  accor-
dance  with  current  standards  and  regula-
tions.  When  dimensioning  gas  pipes  from
the  meter  to  the  module,  both  capacity
volume  (consumption)  in  m

3

/h  and  gas

density must be taken into account. 
The  sections  of  the  piping  making  up  the
system  must  be  such  as  to  guarantee  a
supply  of  gas  sufficient  to  cover  the  maxi-
mum  demand,  limiting  pressure  loss
between the gas meter and any apparatus
being used to not greater than:

– 1.0 mbar for family II gases (natural gas);
– 2.0  mbar  for  family  III  gases  (butane  or

propane).

An adhesive data plate is sticked inside the
front panel; it contains all the technical data
identifying the boiler and the type of gas for
which the boiler is arranged.

2.3.1

Connection of condensation 

water trap

The drip board and its water trap must be
connected  to  a  civil  drain  through  a  pipe
with a slope of at least 5 mm per metre to
ensure drainage of condensation water. 

The  plastic  pipes  normally  used  for  civil
drains  are  the  only  type  of  pipe  which  is
appropriate  for  conveying  condensation
to the building’s sewer pipes.

2.3.2

Filter on the gas pipe

The gas valve is supplied ex factory with an
inlet  filter,  which,  however,  is  not  adequate
to entrap all the impurities in the gas or in
gas main pipes. 
To prevent malfunctioning of the valve, or in
certain  cases  even  to  cut  out  the  safety
device  with  which  the  valve  is  equipped,
install an adequate filter on the gas pipe.

2.4

SYSTEM FILLING

Filling  of  the  boiler  and  the  system  is  done
by the charge system (10 fig. 4). The char-
ge pressure, with the system cold, must be

4

5

6

7

8

10

Fig. 4

2

INSTALLATION

KEY

4 3 BAR safety valve
5 Boiler discharge
6 By-pass (blue)
7 Water pressure transducer
8 Diverter valve

10 System loading

NOTE:  They  are  evidenced  in
blue/white  the  members  for
which are previewed the verifica-
tion and the control.

Page 18 of 40

Содержание Green Planet I-HE 35 MF

Страница 1: ...MURELLE GREEN PLANET I HE 35 MF E HE35 MF CONDENSING BOILER AUS User Service and Installation Instructions...

Страница 2: ...cifications provided to you or your licensed instal ler the boiler is warranted by Hunt Heating against defects caused by the manufacturer s faulty materials and or work manship in respect to parts an...

Страница 3: ...ed out by qualified technical personnel Successively if it is necessary to start up the boiler again adhere strictly to the fol lowing instructions open the gas tap to allow the flow of the fuel Move...

Страница 4: ...agraph The level of various correction of a value of temperature proportional cal culated The display will be as shown in fig 26 a REGULATION OF THE D H W TEMPERATURE fig 26 To set the desired tempera...

Страница 5: ...s request assi stance from qualified technical personnel ALL 07 fig 27 d Press the key of the controls 2 to re start the boiler If the anomaly persists request assi stance from qualified technical per...

Страница 6: ...the room thermostat may be faulty Bridging out the switch can be used to test this Check voltage before re moving cover Does it work If NO go to Q5 5 Boiler Does the boiler start to work and then shut...

Страница 7: ...nternal External Gas pressure Settings Max Pa Adjusted output setting kW Central Heating Water treatment System Volume Litres No Yes Yes Product Qty Used Litres Dilution rate Litres per 100 litres Sys...

Страница 8: ...ON at the boiler front panel control 9 Boiler should start fan pump and ignite gas If it fails first few times this may be just residual air In the gas line A noisy water pump indicates there is air i...

Страница 9: ...jor items are their functions and how to check and turn them on or off Simple fault resolution i e power on 5 How to check and remove air in the radiators Give them a bleed key 6 The importance of thi...

Страница 10: ...ct phone number Work Completed Service Service 3 4 year 5 year 7 Date Date Service technician Service technician Name PIC L icence No Name PIC L icence No Service Company Service Company Contact phone...

Страница 11: ...Service 7 8 year 11 year 13 Date Date Service technician Service technician Name PIC L icence No Name PIC L icence No Service Company Service Company Contact phone number Contact phone number Work Co...

Страница 12: ...6 0 INSTALLER INSTRUCTIONS CONTENTS 1 DESCRIPTION OF THE BOILER page 4 2 INSTALLATION page 9 3 CHARACTERISTICS page 16 4 USE AND MAINTENANCE page 23 Page 12 of 40...

Страница 13: ...water for heating only hot water for DHW using a calorifier or both functions 1 DESCRIPTION OF THE BOILER 385 135 85 70 70 70 70 350 60 125 42 5 450 170 92 5 760 15 60 100 125 175 125 60 700 65 190 F...

Страница 14: ...tional plumbing connec tions Standard connections brass male iron fittings KEY R Central Heating Return 3 4 BSP MI M Central Heating Flow 3 4 BSP MI G Gas connection 3 4 BSP MI R3 D H W tank return 3...

Страница 15: ...emperature C 85 Capacity of the heating expansion vessel l 10 Pressure of the heating expansion vessel bar 1 Exhaust fumes temperature at max flow rate 80 60 C C 70 Exhaust fumes temperature at min fl...

Страница 16: ...W cock optional 24 Gas cock optional 25 C H flow cock optional 26 C H return cock optional 27 D H W tank discharge cock optional 28 D H W expansion vessel optional 29 7 BAR D H W tank safety valve opt...

Страница 17: ...in tap 4 Air pressure tap 5 Ignition transformer 6 Safety thermostat 7 C H sensor SM 8 Ignition electrode 9 Primary exchanger 10 Sensor fumes 11 Suction discharge fitting 12 Expansion vessel 13 Detect...

Страница 18: ...For long term protection agains corrosion and deposits the use of inhibitors such as Fernox is recommended after cleaning the system It is important to check the con centration of the inhibitor after...

Страница 19: ...the load los ses of single accessories 2 6 1 Separate duct kits The diagrams of Figure 9 show a few examples of the permitted exhausts configurations C33 6 5 3 2 C43 3 4 2 x y x y L m H m C13 1 2 1 L...

Страница 20: ...nlet Pa outlet Pa Co axial duct kit 90 Elbow MF 3 0 4 0 25 0 5 0 45 Elbow MF 2 5 2 5 6 0 1 4 Extension L 1000 Horizontal 2 5 2 5 6 0 14 0 Extension L 1000 Vertical 2 5 2 5 6 0 8 0 Walk terminal 1 5 5...

Страница 21: ...nternal part of the gaskets with silicon products Avoid using oils and greases LIST OF 60 ACCESSORIES 1 Coaxial duct kit code 8089913 2 a Additional 90 MF curve code code 8089921 2 b MF 90 bend with s...

Страница 22: ...h input 1500 500 Appliances over 250 MJ h input 1500 1500 1500 1000 j All fan assisted flue appliances in the direction of discharge 1500 k From a mechanical air inlet including a spa blower Verticall...

Страница 23: ...control CR73 connection optional The boiler is designed for connection to a remote control unit code 8092226 The remote control unit CR73 allows for complete remote control of the boiler except relea...

Страница 24: ...1 Zone 1 environment thermostat TA2 Zone 2 environment thermostat SB D H W tank sensor CR Remote control CR 73 optional SE External sensor optional OP Internal time clock optional EXP Expansion card A...

Страница 25: ...with the HUNT programming kit and only by authorised personnel Do not connect other electro nic devices cameras telephones mp3 players etc Use a tool to remove the cap and reinsert after use ATTENTIO...

Страница 26: ...ssi 1 Visualisation of external temperature only with external sensor connected 2 Visualisation of heating temperature sensor SM 3 Visualisation of D H W temperature sensor SS 4 Visualisation of auxil...

Страница 27: ...sualizzazione rel solare R2 con schedino solare INSOL rispettivamente ON e OFF 33 Visualizzazione rel solare R3 con schedino solare INSOL rispettivamente ON e OFF 17 Indication of D H W flowmeter load...

Страница 28: ...and 2 8 Fan rpm Step ignition 0 0 81 rpmx100 0 1da 0 1a19 9 0 0 1da 20 a 81 9 Long chimneys 0 20 1 0 1 CR 73 10 Remote control option setting 2 CR 53 1 3 RVS 11 Correction values external sensor 5 5...

Страница 29: ...FAULT MEASUREMENT UNIT SETTING 40 Number of expansion boards 0 3 1 0 41 Mix valve stroke time 0 199 10 sec 1 12 42 Priority of D H W over mixed zone 0 Paralle 1 1 Absolute 43 Floor drying 0 No activat...

Страница 30: ...faulty or open circuit the boiler will not function on either heating or D H W ALL 14 3 7 ELECTRONIC IGNITION Ignition and flame detection is controlled by a single electrode on the burner which guara...

Страница 31: ...it is fitted with the arrow pointing in the correct direction 3 9 HEAD AVAILABLE TO SYSTEM Residual head for the heating system is shown as a function of rate of flow in the graph in fig 14 The speed...

Страница 32: ...econds The table below shows the SET settings to enter when the type of gas fuel is changed 4 2 2 Calibrating the gas valve pressures Measure the CO2 values with a combustion analyzer Sequence of oper...

Страница 33: ...uld be inspected at least once a year by a qualified technician During maintenance operations it is important to verify that the drip plate with drain trap contains water this check is particularly im...

Страница 34: ...iler will func tion at maximum power with the D H W cir cuit kept at between 60 C and 50 C During the test the hot water taps must remain open If the key and are pressed during the 15 minutes of the c...

Страница 35: ...50 45 40 35 30 20 5 10 15 18 Tag 0 25 55 A B 1 1 5 7 X A B 1 25 TVw Fig 22 a TVw Flow temperature setpoint Tag Period in days x Start day A Functional heating B Floor curing heating 2 175 125 60 Page...

Страница 36: ...etected the presence of the flame after a complete ignition sequence or for any other rea son the card cannot see the flame the boiler will stop and the display will show the alarm ALL 06 Press the ke...

Страница 37: ...ess the key of the controls 2 to start up the boiler again EXHAUST FUMES SENSOR ERROR 14 fig 23 m If the exhaust fumes sensor is open or short circuit the boiler will stop and display ALL 14 FAN ERROR...

Страница 38: ...ay indicates ALL 26 During this error the boiler functions normally SOLAR APPLICATION CONFIGURATION ALL 27 fig 23 w When the solar board is connected to the boiler If the hydraulic configuration of th...

Страница 39: ...Page 39 of 40...

Страница 40: ...E HE 35 MF CONDENSING BOILERS version 1 Issued December 2009 HYDRONIC SYSTEMS Australia Pty Ltd 11 Fiveways Boulevard Keysborough Victoria 3173 Telephone 1300 00 1800 Facsimile 9798 5133 www huntheat...

Отзывы: