FLAME DETECTION
ERROR 08
(fig. 23/g)
If the flame control detects aflame when
one should not be detected, the boiler
will stop and display “ALL 08”.
–
SYSTEM WATER CIRCULATION
ERROR 09
(fig. 23/h)
If the system flow switch detects inade-
quate circulation, the boiler will stop and
the display will show “ALL 09”. If the
error persists for more than 1 minute,
the boiler will stop and wait for 6 minu-
tes. The boiler will then attempt to
restart. Possible causes of this error
are faulty or jammed pump, blocked
Aqua Guard filter, closed flow or return
valve, blocked heating system.
–
AUXILIARY SENSOR
ANOMALY ERROR 10
(fig. 23/i)
BOILER WITH ACCUMULATION: anomaly
of the D.H.W. sensor. When the D:H.W.
sensor is open or short circuited, the
display will show anomaly “ALL 10”. The
boiler will function but will not modulate
power for the D.H.W.
BOILER ONLY FOR HEATING: antifreeze
sensor anomaly for boilers which fore-
see the use of antifreeze sensors.
When the sensor is open or short circui-
ted, the boiler loses part of its anti-freeze
functions and the display will show ano-
maly “ALL 10".
BOILER COMBINED WITH SUN-PANEL
SYSTEM: anomaly of the D.H.W. input
sensor. When the sensor is open or
short circuited, the boiler loses the sun-
panel function and the display will show
anomaly “ALL 10".
–
ACTIVATION OF THE EXHAUST FUMES
SENSOR ERROR 13
(fig. 23/l)
The activation of this probe causes the
boiler to stop and error message “ALL
13” to display.
Press the key
of the controls (2)
to start up the boiler again.
–
EXHAUST FUMES SENSOR
ERROR 14
(fig. 23/m)
If the exhaust fumes sensor is open or
short circuit, the boiler will stop and
display “ALL 14”.
–
FAN ERROR 15
(fig. 23/n)
If the fan speed is not within the rated
speed range,the display will show “ALL
15”. If the problem persists for more
than two minutes the boiler will stop
thirty minutes, after which it will attempt
to resume operating.
–
SAFETY THERMOSTAT INTERVENTION
FIRST MIXED ZONE “ALL 20”
(fig. 23/p)
When the mixed zone board is connec-
ted to the boiler, a safety thermostat
intervention switches the mixed zone
pump, the mixed zone valve closes and
the display indicates error ALL 20.
During this this error the boiler functions
normally
–
DELIVERY PROBE FAILURE FIRST
MIXED ZONE “ALL 21”
(fig. 23/q)
When the mixed zone board is connec-
ted to the boiler. If the delivery probe
becomes open or shor t cir cuit t he
display will indicate ALL21. During this
error the boiler continues to function
normally.
–
SAFETY THERMOSTAT INTERVENTION
SECOND MIXED ZONE “ALL 22”
(fig. 23/r)
When the mixed zone board is connec-
ted to the boiler. An intervention of the
safety thermostat switches the mixed
zone pump , the mixed zone valve closes
and the display indicates ALL 22.
During this error the boiler functions
normally.
–
DELIVERY PROBE BREAKDOWN ANO-
MALY SECOND MIXED ZONE “ALL 23”
(fig. 23/s)
When the mixed zone board is connec-
ted to the boiler. If the delivery probe is
open or short circuited the display indi-
cates error ALL 23. During this error
Fig. 23/i
Fig. 23/g
Fig. 23/h
Fig. 23/l
Fig. 23/n
Fig. 23/m
Fig. 23/p
Fig. 23/q
Fig. 23/r
Page 37 of 40