11 COMMISSIONING BOILER CHECKLIST
A suggested method of commissioning the boiler; the actual method can vary according to the boiler make, type and installation. The
boiler must always be installed and commissioned by an approved gas technician. The installer certifies that this Boiler has been in-
stalled to the manufacturer's instructions, has been filled, commissioned and is ready for use.
N°
Description
When done
1
Read carefully the instruction manuals supplied with this boiler.
2
BEFORE INSTALLING THIS BOILER, FLUSH OUT THE PIPE UNTIL WATER RUNS CLEAR.
3
Turn off all services to–this boiler - water, gas and power.
Install the boiler as shown in the instructions following and connect all services.
4
Turn off all services to the boiler (water, gas, power). Install the boiler as shown in the instruction
manual and reconnect all services.
5
Check that all radiator valves are open, remove the thermostatic valve heads, and fully open all
lockshield valves.
6
Turn ON gas, bleed air out at the isolation valve union. Reseal and check for gas leaks.
Turn gas OFF.
7
Turn electricity on at the power point. At the boiler front panel set the temperature setting to the
lowest setting, switch boiler to ON position.
The “Power on” Indicator should light. Turn the boiler off at the front panel.
8
Turn the room thermostat to the manual ON position, set the temperature to a high level (eg?) so that
it does not switch off during the commissioning phase. The thermostat will make a clicking sound
and show an indicator in the window.
9
Switch the boiler ON at the boiler front panel control.
10
Fan and pump should start, and gas will ignite. If the boiler fails to start, there may be residual air in
the gas line. If the water pump is making noise, that may be a sign of air in the piping.
11
The boiler will ignite and heat the water. Check the flame is stable and blue in colour, and check for
gas and water leaks as the system heats up.
12
Check that the heat is going into the radiators through the manual or thermostatic valve first, and
returning via the lockshield valve. If heat is entering through the lockshield valve, turn boiler OFF and fix.
13
Allow the boiler to heat up to the set temperature and switch off. Re-adjust the boiler temperature to
a mid temperature point. CAUTION, If this is connected to a floor heating system. The boiler should re
light and increase the water temperature to the new setting.
14
Check that the radiators are heated evenly from bottom to top. If the radiator is cold at the top, there may
be air in the system that needs to be bled out. Balance the system so that all radiators are the same
temperature, according to the installation manual. Adjust the boiler water temperature accordingly.
15
Set the room thermostat to the correct times and temperatures according to the end user's
requirements and the manufacturer's instructions.
16
On completion of the commissioning phase, complete the information sheet at the front of this manual.
Hand over the installation to the owner and demonstrate how the system works plus basic fault resolution
and safety procedures. Make sure that this important document is kept in a safe accessible place.
Содержание 8112265
Страница 42: ...42 12 EXPLODED VIEWS Brava Slim HE 20 R i Brava Slim HE 40 R i ...
Страница 43: ...43 Brava Slim HE 20 R e Brava Slim HE 40 R e ...
Страница 44: ...44 Brava Slim HE 20 R i Brava Slim HE 20 R e Brava Slim HE 40 R i Brava Slim HE 40 R e ...
Страница 45: ...45 Brava Slim HE 20 R i Brava Slim HE 20 R e Brava Slim HE 40 R i Brava Slim HE 40 R e ...
Страница 46: ...46 Brava Slim HE 20 R i Brava Slim HE 20 R e Brava Slim HE 40 R i Brava Slim HE 40 R e ...
Страница 55: ...55 ...
Страница 56: ...Fonderie Sime S p A Via Garbo 27 37045 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 www sime it ...