Start-up, calibration and operation of the burner

6.1

Notes on safety for the first start-up

6.2

Combustion adjustment

In conformity with EN 267, the application of the burner on the
boiler, adjustment and testing must be carried out observing the
instruction manual of the boiler, including verification of the CO
and CO2 concentration in the flue gases, their temperatures and
the average temperature of the water in the boiler. 

To suit the required appliance output, choose the proper nozzle
and adjust the pump pressure and the air damper opening in ac-
cordance with the following data.
The values refer to 11.6% of CO

2

 at sea level, and with the light

oil and ambient temperature at 10°C.
The  values  in  Tab. D  are  obtained  on  a  boiler  (according  to
EN267). They refer to 12.5 % CO

2

, at sea level and with an am-

bient and light oil temperature of 20 °C.

Tab. D

6.3

Recommended nozzles

The burner complies with the emission requirements of the EN
267 standard.
In order to guarantee that emissions do not vary, recommended
and/or  alternative  nozzles  specified  by  manufacturer  in  the  In-
struction and warning booklet should be used. 

Delavan type W

Steinen type Q

Danfoss type S

6.4

Pump pressure 

The pump is calibrated in the factory as shown in Tab. D.

6

Start-up, calibration and operation of the burner

WARNING

The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
tions of the laws in force.

WARNING

Check the correct working of the adjustment, com-
mand and safety devices.

WARNING

The combustion air is sucked from outside, there-
fore,  there  can  be  sensitive  temperature  varia-
tions  that  can  influence  the  percentage  value  of
the CO

2

. It is advisable to adjust the CO

2

 accord-

ing to the diagram. 
For example: with an external air temperature of
10°C, adjust the CO

2

 to 12.5% (± 0.2%).

Burner

Nozzle

Pump 

pressure

Burner 

output

Combustion 
head adjust.

Air Damper 
adjustment

Code

Model

Type

GHP

Angle

bar

kg/h ± 4%

Set-point

Set-point

20119424 
20131439

SIME FUEL 25 ErP Danfoss

0.55

60°S

12.5

2.0

Fixed

5.0

20119426
20131442

SIME FUEL 35 ErP Danfoss

0.65

80°S

13.0

2.7

Fixed

4.75

WARNING

It is advisable to replace nozzles every year dur-
ing regular maintenance operations.

CAUTION

The use of nozzles other than those specified by
manufacturer  and  inadequate  regular  mainte-
nance  may  result  into  emission  limits  non-con-
forming to the values set forth by the regulations
in force, and in extremely serious cases, into po-
tential hazards to people and objects.
The manufacturing company shall not be liable for
any such damage arising from non-observance of
the requirements contained in this manual.

Содержание 20119424

Страница 1: ...ions Instructions pour installation utilisation et entretien Bruciatori di gasolio Light oil burners Br leurs fioul domestiques Funzionamento monostadio One stage operation Fonctionnement 1 allure COD...

Страница 2: ...ty for the installation 8 5 2 Handling 8 5 3 Preliminary checks 8 5 4 Operating position 9 5 5 Boiler fixing 9 5 6 Burner assembly 10 5 7 Hydraulic systems 11 5 7 1 Pump 11 5 7 2 Priming pump 12 6 Sta...

Страница 3: ...th the following Technical Standards EN 12100 EN 267 According to the European Directives MD 2006 42 EC Machine Directive LVD 2014 35 UE Low Voltage Directive EMC 2014 30 UE Electromagnetic Compatibil...

Страница 4: ...ed out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shocks wit...

Страница 5: ...vent of damage to things or injury to people if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreas...

Страница 6: ...e Only those parts envisaged by the manufacturer can be replaced 3 2 Personnel training The user is the person body or company that has acquired the machine and intends to use it for the specific purp...

Страница 7: ...mper adjustment screw 6 Flange with insulating gasket 7 Pump 8 Pressure gauge port 9 Pump pressure adjustment 10 Control box 4 Technical description of the burner Model SIME FUEL 25 ErP SIME FUEL 35 E...

Страница 8: ...g gasket No 1 Screws for fixing the flange to the boiler No 4 Screw and nuts for flange No 1 Flexible hoses with nipples No 2 Only for burners code 20131439 and 20131442 instruction manual No 1 spare...

Страница 9: ...ing and maintenance more frequently WARNING The handling operations for the burner can be highly dangerous if not carried out with the great est attention keep any unauthorised people at a distance ch...

Страница 10: ...g screws 2 and if necessary the nuts 3 interposing the insulating gas ket 5 WARNING The burner is designed to operate only in the po sition 1 WARNING Any other positioning could compromise the cor rec...

Страница 11: ...t if you use flues for pressure exhaust of flue gases the condensation kind Make sure the air intake tube s inlet is positioned so that it is not likely to be obstructed by foreign matter and where ne...

Страница 12: ...ng any operation on the burner WARNING The fuel supply line must be installed by qualified personnel in compliance with current standards and laws WARNING Before starting the burner make sure that the...

Страница 13: ...perfectly sealed Tab C In vacuum systems Fig 12 you are advised to bring the return line to the same height as the suction line In this case a non return valve is not required Should however the retur...

Страница 14: ...wn in Tab D 6 Start up calibration and operation of the burner WARNING The first start up of the burner must be carried out by qualified personnel as indicated in this manual and in compliance with th...

Страница 15: ...ermostat calls for heat and after a delay of approximately two minutes depending on room temperature the motor will start The resistance remains energised during working and cuts out when burner shuts...

Страница 16: ...thermostat pressure switch ensures the stopping of the burner If this is not the case a timer should be fitted in series to L N to stop the burner at least once every 24 hours Refer to the wiring dia...

Страница 17: ...y thermostat WARNING Do not invert the neutral with the phase in the electrical supply line Check that the electrical supply of the burner corresponds to that shown on the identifica tion label and in...

Страница 18: ...ess the reset or remote reset button WARNING In the event the burner stops in order to prevent any damage to the installation do not unblock the burner more than twice in a row If the burner locks out...

Страница 19: ...lock out The flame sensor sees false light Eliminate the light Resistance or start thermostats are faulty Replace them The connections in the control box are wrong ly inserted Check and connect comple...