Control Unit
GFC 32
SIMATEK A/S
www.simatek.com
Hotline: +45 4046 7525
[email protected]
4
Doc. No.: 1400004_EN
Rev.: -
Date: 05.2017
3.
Installation guidelines
•
Do not expose the control unit to direct sunlight in order to prevent overheating of the circuit board.
•
Connect the control unit to a continually powered line to allow SHUT-DOWN CLEANING when the fan stops.
•
Protect the control unit from rain, water infiltration and humidity. Incomplete closing of the cover may cause
infiltration which can seriously damage the circuit board.
•
Do not have cables entering via the upper part of the control unit.
•
Do not install any electronic devices on vibrating structures.
•
Use only cable glands with protection grade IP65 and of proper size (according to the cable used).
•
A disconnecting switch has to be installed on the power line before the control unit.
•
Do not attempt to repair the control unit – contact Simatek!
•
All wiring has to be carried out by a qualified electrician to prevent any risk of fire and electrical shocks.
•
Control unit wiring has to be performed in such a way that the different types of cables, (power, relay’s contact,
valve output, 4-20 mA output) are kept separate and not passing close by the PCB.
•
Before opening the unit make sure that the control unit is switched off (switch on/off [1] on 0 and wires on
clamps [4] disconnected, including connection to alarm/signal relays.
•
All electrical connections of the control unit, including solenoid valves, have to use separate paths in respect to
the other loads.
•
Voltage selector’s jumpers have to be positioned only by skilled personnel and following the instructions.
•
A wrong voltage selector’s jumpers positioning may cause potential danger to the personnel safety.