Model SK-4224 Fire Alarm Control Panel Installation/Operation Manual
4-2
151068
4.2
Battery Connection
The SK-4224 battery charge capacity is 7.0 AH. Use two Model 12 VDC batteries of the same
AH rating. Determine the correct AH rating as per your current load calculation (see Table 3-
6).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase
the AH rating.
Note: The SK-4224 cabinet supports two 7.0 AH batteries.
Figure 4-2 Battery Connection
Backup Battery
Connector
Battery jumper (P/N 140694),
shipped with Control Panel.