35
17.2 System Messages
Table 17.2-I shows the messages that could appear on the LCD of the model 5230 annunciator. You can
connect a 5230 temporarily to allow for troubleshooting.
Table 17.2-I: Explanations of Display Messages
5230 MESSAGE
EXPLANATION/ACTION TO BE TAKEN
BAD EEPROM
5230 buzzer goes on and off.
Replace the EEPROM.
REPORTING
An event is being reported to the central station.
SYSTEM NORMAL
No trouble, alarm, or other condition exists.
AC LOW
AC power has been lost. Check connection to AC power source.
TROUBLE DIALER
The dialer has made the programmed number of attempts (programmed in
steps 30 and 34) and has not been able to communicate with the central
station. (This is a dialer failed condition.)
TROUBLE LINE 1
A trouble condition exists on phone line 1.
TROUBLE LINE 2
A trouble condition exists on phone line 2.
TROUBLE (ZONE 1-4)
A trouble condition exists in the indicated zone. If you need help locating the
trouble, refer to Section 17.1 for information about zone troubleshooting
mode (mode 25).
ALARM ZONE 1-4
An alarm condition exists in the indicated zone.
TRY AGAIN
A keystroke error has been made. Press
CLEAR
and enter the correct
keystrokes.
Line 2: REPORTING
The system is reporting to the central station.
Line 2: CALLING COMPUTER
Message not explicable.
TIME?
The 5128/29 is in Time Set mode.
TROUBLE (line 1)
TROUBLE ZONE # (line 2)
Sprinkler supervisory trouble.
NOTE:When step programming mode is in use and the 5230 annunciator powers up, the LCD displays
messages that describe conditions currently in effect.
18. How to Contact Silent Knight
For questions and problems with Silent Knight products, contact Silent Knight Technical Support at
800-328-0103 (or 612-493-6455). To order parts, contact Silent Knight Sales at 800-446-6444
(or 612-493-6455).