2

 

Features 

(continued from previous page)

 
• 

Active high, contact closure or direct monitoring input for monitoring control panel’s primary power.

• 

Compatibility with many Underwriters Laboratories (UL) Fire Listed receivers.  (See Section 1.3 for list.)

• 

Housed in plastic enclosure (8-5/8 x 4 x 1-3/8 inches) for mounting inside control panel.  (Refer to the
installation manual of the compatible control panel you are using for 5128 mounting instructions.)

• 

Model 5129 housed in metal enclosure (10 x 10) with AC monitoring transformer.

 

1.2 Optional Devices

The following accessories are available for use with the 5128/29:

• 

Model 5230 Remote Annunciator.  Can be temporarily connected to the system for programming and
troubleshooting only.  Only one model 5230 can be used.

• 

Cable for 5230, P/N 130294.

• 

Model 9230 Step Transformer.  Required for AC monitoring if the control panel used does not have a
distinctive AC trouble output.

1.3  UL Fire Listed Receivers

The following UL Listed receivers are compatible with the 5128/29:

RECEIVER

FORMATS

Silent Knight Model 9000

BFSK14
BFSK23
FSK
SK 3/1
SK 4/2
SIA8
SIA20

Osborn & Hoffman Quickalert

SK 3/1
SK 4/2
SIA8
SIA20
BFSK14
BFSK23

Ademco 685

SK 3/1
SK 4/2

FBI CP220

SK 3/1
SK 4/2

Radionics D6500

BFSK 1400
BFSK 2300

Содержание 5128

Страница 1: ... Tone rotary dialing Built in dual phone line seizure circuit Dual phone line monitor circuits Transient voltage protection of phone lines Built in audible trouble buzzer with a loudness of 80 decibels dB at 30 cm ie 300 mm or approximately 12 inches One relay output programmable for alarm or trouble conditions Light emitting diodes LEDs visible from front of plastic enclosure indicating trouble c...

Страница 2: ...1 2 Optional Devices The following accessories are available for use with the 5128 29 Model 5230 Remote Annunciator Can be temporarily connected to the system for programming and troubleshooting only Only one model 5230 can be used Cable for 5230 P N 130294 Model 9230 Step Transformer Required for AC monitoring if the control panel used does not have a distinctive AC trouble output 1 3 UL Fire Lis...

Страница 3: ...ystem s dialer needs to communicate with the central station it will NOT be possible to use any telephones that are on the same line s as the fire system Normally this condition will last less than one minute but could last for as long as 15 minutes under adverse telephone circuit conditions 2 2 Watchdog Circuit If the 5128 29 stops running the watchdog circuit automatically detects the problem an...

Страница 4: ... or return to Silent Knight Security Systems 7550 Meridian Circle Maple Grove MN 55369 612 493 6455 800 328 0103 4 If the Model 5128 29 causes harm to the telephone network the telephone company will notify the user in advance that temporary discontinuance of service may be required If advance notice is not practical the telephone company will notify the user as soon as possible The user has the r...

Страница 5: ...nformation 5128 Signaling device subassembly for use in Central Station Fire Protective Signaling Systems 4 3 Remote Signaling Service 4 5 5129 Signaling device for use in Central Station Fire Protective Signaling Systems 4 3 Remote Signaling Service 4 5 All UL installations must comply with the requirements described below Refer to the control unit s installation manual for complete information 5...

Страница 6: ...ost all power PHONE LINE 1 LED red ON Phone line 1 has a trouble condition OFF Normal condition PHONE LINE 2 LED red ON Phone line 2 has a trouble condition OFF Normal condition 4 2 Electrically Erasable Read Only Memory EEPROM The electrically erasable read only memory EEPROM is used to store specific information such as system configuration telephone numbers reporting format and account numbers ...

Страница 7: ...criptions PIN CONNECTOR FUNCTION P1 DC power P2 Channel zone inputs P3 AC monitor P4 5230 connect temporary for programming and troubleshooting only P6 Not used 4 4 2 Wiring and Board Layout Diagram Figure 4 4 2 A Model 5128 29 Wiring and Board Layout ...

Страница 8: ...e whole panel Instead separate the wiring as follows High current input output AC monitoring if monitored directly Low current input output 24 DC power and channel zone wiring Audio input output Telephone wiring Wires from different groups should not be pulled through the same conduit If you must run them together do so for as short a distance as possible or use shielded cable Connect the shield t...

Страница 9: ...efore attaching the 5129 6 1 Grounding the 5129 Cover Before connecting power to the 5129 connect the earth ground wire to the base and cover Make sure that the ring lugs are oriented properly Figure 6 1 A shows the proper connection and orientation After the 5129 s cover and base are attached make a slight bend to the wire that is attached to the cover This keeps the wire from getting caught betw...

Страница 10: ...Contact closure active high voltage input or active low voltage input CHANNEL 1 ZONE 1 FIRE ALARM CHANNEL 2 ZONE 2 FIRE TROUBLE CHANNEL 3 ZONE 3 SPRINKLER SUPERVISORY CHANNEL 4 ZONE 4 UNDEFINED ALARM 7 1 Dry Contact A short across the end of line resistor EOL causes an active channel zone An open loop causes a trouble condition Figure 7 1 A Contact Closure ...

Страница 11: ...ses an active channel zone At the time of this manual s printing the Cerberus Pyrotronics System 3 with CSI 35 is the only UL Listed model available Active Low A short across the EOL or pulling the input low causes an active channel zone An open loop causes a trouble condition This information is provided for the future At the time this manual was printed no compatible UL listed control panel with...

Страница 12: ...ormer see Section 8 3 AC monitoring can also be performed with a dry contact active low see Section 8 2 or an active high voltage input see Section 8 1 8 1 Voltage Input Active High If the fire control panel has an active high AC trouble voltage output 10 to 30 VDC attach this output directly to the AC monitor input on the 5128 29 At the time of this manual s printing the Cerberus Pyrotronics Syst...

Страница 13: ...monitors its AC input and has a contact closure AC trouble output apply 10 to 30 VDC to the AC monitor input of the 5128 29 through the normally closed contacts Select ACTIVE LOW in programming for this configuration Figure 8 2 A Dry Contact Input ...

Страница 14: ...ble output the model 9230 AC monitoring step down transformer must be used to allow the 5128 29 to monitor the fire control panel s 120 VAC power input Wire the secondary side of the transformer directly into the 5128 29 AC monitor input Figure 8 3 C AC Monitoring Input ...

Страница 15: ...tions or both The relay contacts are rated at 1 A 24 VDC 24 VAC See Figure 9 A for relay contact connections The relay can be used for either of the following To activate for any alarm To activate for system trouble conditions loss of AC power failure of the 5128 29 to communicate and phone line troubles Figure 9 A Relay Connection ...

Страница 16: ...rotective Signaling and Remote Signaling Systems both telephone lines must be installed Connect the 5128 29 to the phone line using an RJ31X type phone jack as shown in Figure 10 A The telephone company will install an RJ31X jack upon request Figure 10 A Telephone Wiring ...

Страница 17: ...230 key functions are described in Section 12 programming instructions are in Section 15 NOTE At the time this manual was printed the 5230 is the only available method for programming the 5128 29 11 1 5230 Installation The table below shows how to make the connections Figure 11 1 A below shows the location of the 5230 terminal block 5230 TERMINALS CABLE WIRE COLORS P N 130294 1 GROUND BROWN 2 POWE...

Страница 18: ...roubleshooting section of this manual Section 17 Figure 11 2 A Model 5230 Remote Annunciator Front 11 3 Power LED Indicator When DC power is being supplied the POWER LED glows steadily If DC power is not being supplied the POWER LED is off 11 4 Buzzer An audio transducer buzzer is built into the 5230 annunciator It produces short beeps to annunciate keystrokes It also emits a long high pitched ton...

Страница 19: ... high pitched tone CLEAR SYSTEM TEST Tests the communicator by sending a test report to the central station 0 ENTER Code CLEAR ALARM MEMORY Clears all data from the alarm memory 2 ENTER Code RESET DIALER Aborts an in progress call to the central station 3 ENTER Code DISPLAY ALARM MEMORY Displays events currently saved in the alarm memory NOTE It is recommended that you clear the alarm memory after...

Страница 20: ...s of the options see Section 15 The 5128 29 is shipped with a factory programmed EEPROM The options that have been programmed are shown in the step programming form in Section 15 Changing the Options To customize the features to suit a particular installation you can reprogram the options stored on the EEPROM using the Model 5230 Remote Annunciator The EEPROM is an 8 pin integrated circuit chip th...

Страница 21: ...PECIFIC STEP Press STEP The first line of the LCD will show ENTER THE STEP and the current step number Type in the new step number then press ENTER Line 1 of the LCD will show the option name line 2 will show the programmed data for the step If you try to go to a step that does not exist the display will go back to the previous step SELECT YES OR NO Press any digit to toggle Yes and No SELECT AN O...

Страница 22: ... a record of how you have programmed an installation by checking off or writing in your choices in Column 4 of the chart The factory programmed defaults also appear in Column 4 Note that if the system was reprogrammed after it left the factory the data you see on the display may be different from the data shown on the form This form is perforated for your convenience ...

Страница 23: ...r Sprinkler 5 SUPERVISORY CHANNEL ZONE Supervisory input 0 Fire 1 Sprinkler r Fire r Sprinkler D NOTES FOR STEPS 6 9 Channel zone response time speeds are not intended to be used as a smoke verification feature Possible choices for channel zone response times are 0 3 described below 6 CHANNEL ZONE RESPONSE 1 0 0 3 to 0 4 seconds 1 3 to 4 seconds 2 15 to 20 seconds 3 30 to 40 seconds r 0 3 to 0 4 s...

Страница 24: ... annunications and perform manual tests This code must be different from the installer s code ________________ Default 1111 13 DIALER TYPE 0 USA 1 9000 Direct Do not use this option 2 European used for Europe and Asia r USA D r European 14 COMPUTER ENABLE OPTION CURRENTLY NOT AVAILABLE DO NOT USE No selection 15 TOUCHTONE LINE 1 Yes Phone 1 will try both TouchTone and rotary No Phone 1 will use ro...

Страница 25: ...ilities The 3 1 sends only one digit or letter for an event It does not send the zone number with the event Use this format only if required by the receiver If you are using the 3 1 reporting format use Steps 22 25 to select the digit 0 9 that will be sent for each event The letters A through E can be used if the receiver can accept them Use SHIFT 1 for A SHIFT 2 for B and so on Do not duplicate a...

Страница 26: ...s D r No 27 TROUBLE 1 1ST Yes Report troubles to central station phone 1 first No Report troubles to central station phone 2 first r Yes D r No 28 TEST 1 1ST Yes Report tests to central station phone 1 first No Report tests to central station phone 2 first r Yes D r No 29 ACCOUNT 1 Account for central station phone 1 6 digits leading zeros if shorter ________________ Default 105128 30 ATTEMPTS 1 N...

Страница 27: ...ill try to dial each central station acct before DIALER FAILED displays on the 5230 LCD Range is 3 to 5 ____ Default 3 35 FORMAT 2 Select reporting format for phone line 2 Sec section 16 for descriptions of these formats 0 SIA8 1 FSK81 2 SK4 23 3 BFSK14 4 BFSK23 5 SIA20 6 3 1 14 7 3 1 23 r SIA8 D r FSK81 r SK4 23 r BFSK14 r BFSK23 r SIA20 r 3 1 14 r 3 1 23 36 PHONE 2 Enter phone 2 up to 16 digits ...

Страница 28: ...t model 9000 receiver with a 9004I SIA line card and a 9200 CPU card Revision E FSK81 High speed single round format for use with older receivers Transmits a 4 digit account number and a 2 digit alarm code at 20 pps SK4 2 Format used with receivers that can receive 4 2 at 20 pps and can send a 1400 Hz acknowledgment tone Uses a 4 digit account number BFSK14 High speed single round format used with...

Страница 29: ...ogrammed Table 16 1 I 9000 Printout for SIA Format 5128 29 9000 PRINTOUT ALARM 1 4 FIRE ALARM 1 4 ALARM RESTORE 1 4 FIRE ALARM RESTORE 1 4 TROUBLE 1 4 FIRE TROUBLE 1 4 TROUBLE RESTORE 1 4 FIRE TROUBLE RESTORE AC LOST AC TROUBLE 0 AC RESTORE AC RESTORE 0 MANUAL TEST MANUAL TEST 0 AUTOMATIC TEST AUTO TEST FIRE DRILL MANUAL TEST DOWNLOADING SUCCEEDED PROGRAMMING PASS 0 DOWNLOADING FAILED PROGRAMMING ...

Страница 30: ...4 2 Formats 5128 29 DIGITS TRANSMITTED 9000 RECEIVER ENGLISH LANGUAGE PRINTOUT ALARM 1 4 01 04 ALARM 01 ALARM 04 ALARM RESTORE 1 4 21 24 RESTORE 01 RESTORE 04 TROUBLE 1 4 61 64 TROUBLE 01 TROUBLE 04 TROUBLE RESTORE 1 4 71 74 AC TROUBLE AC LOST 60 AC RESTORE AC RESTORE 70 TEST MANUAL TEST 30 TEST AUTOMATIC TEST 30 TEST FIRE DRILL 30 TEST DOWNLOADING SUCCEEDED 30 TEST DOWNLOADING FAILED 30 TEST PHON...

Страница 31: ...FSK Format DIALER CONDITION DIGITS TRANSMITTED 9000 RECEIVER PRINTOUT ALARM 1 4 10 40 ALARM 01 ALARM 04 ALARM RESTORE 1 4 E1 E4 RESTORE 01 RESTORE 04 TROUBLE 1 4 F1 F4 TROUBLE 01 04 TROUBLE RESTORE 1 4 E1 E4 RESTORE 01 04 AC LOST FA TROUBLE 00 AC RESTORE EA RESTORE 00 MANUAL TEST EE RESTORE 0E AUTOMATIC TEST EE RESTORE 0F FIRE DRILL EE TROUBLE 0E DOWNLOADING SUCCEEDED EF TROUBLE 0F DOWNLOADING FAI...

Страница 32: ...mber in which each digit is programmed The third column indicates that the 9000 prints only the digit X that has been programmed for that event not an English message Table 16 4 I 9000 Printout for Silent Knight and Sescoa 3 1 Formats 5128 29 9000 RECEIVER PRINTOUT ALARM 1 4 CODE X ALARM ALARM RESTORE 1 4 CODE X RESTORE TROUBLE 1 4 CODE X TROUBLE TROUBLE RESTORE 1 4 CODE X RESTORE AC LOST CODE X T...

Страница 33: ...C Monitoring function The first line of the display will show the channel zone input number The second line will show a high low and present channel zone measurement The high and low values allow you to trip a zone momentarily then come back to the annunciator and see the result This procedure is also useful for locating intermittent connections Figure 17 1 A Example Mode 25 Display Table 17 1 I n...

Страница 34: ...e range may be acceptable depending on your application Mode 25 Values All Values Shown Are Approximate Normal Condition Active Tripped Trouble Valid Range Typ value Valid Range Typ value Supervised Channel or Zone Input Active High 8 to 11 9 21 to 31 27 0 to 7 or 12 to 20 Active Low 8 to 11 or 21 to 31 9 0 to 7 1 12 to 20 Contact Closure 8 to 11 9 0 to 7 1 12 to 31 Non Supervised Channel or Zone ...

Страница 35: ...NE 2 A trouble condition exists on phone line 2 TROUBLE ZONE 1 4 A trouble condition exists in the indicated zone If you need help locating the trouble refer to Section 17 1 for information about zone troubleshooting mode mode 25 ALARM ZONE 1 4 An alarm condition exists in the indicated zone TRY AGAIN A keystroke error has been made Press CLEAR and enter the correct keystrokes Line 2 REPORTING The...

Отзывы: