LAB939R, Issue 2, July 2014
Page 14
3.0
Electrical
3.1
Overview
3.1.1 WARNING: This appliance must be earthed.
3.1.2 Important: All wiring must conform to the prevailing national regulations, for example
the latest edition of BS7671: IEE Wiring Regulations.
3.1.3 Important: The electrical installation must be carried out by a qualified electrician.
3.1.4 This appliance is suitable for 230V 50Hz single phase supply only, fused at 3 Amps.
3.1.5 A double-pole switch having a minimum contact separation of 3mm must be used to provide
isolation for the appliance.
3.1.6 Refer to page 14 for HRX2-S, wiring diagram, page 15 for HRX2-B, wiring diagram, page 16
for HRX2-FP wiring diagram and page 17 for HRX2-BFP wiring diagram.
3.1.7 Supplementary sensor diagrams are shown on page 18.
3.1.8 External wiring (1.5mm² max.) and isolators to be supplied by others.
3.2
Frost protection only, wiring-centre fan connections (HRX2-FP, HRX2-BFP)
3.2.1 Important: the fan selected as
SUPPLY
FRESH AIR TO ROOMS must be connected as
shown in the diagram below.