background image

Wet Location

Series MHE-RE

Moonlite LED

Emergency & Security Light

-3-

Fig. 3. RECESSED MOUNT- WIRING

1. Route 24VDC IN/OUT wiring from CBS system into Housing. 
 
2. Connect wiring with standard wire nuts to the supplied wiring pigtail, as shown. For emergency lighting 
    operation only, connect RED and GREEN; for normally ON/security lighting operation, connect RED, 
    GREEN and BLACK. (WHITE wire is passed through and not connected to this fixture). 

3. Connect lamp plug and install lamp assembly with (4) #8 screws. Attach Trim Plate with (2) color- matched
    #8-32 screws as shown. Ensure gasket is properly seated on flat surface. Use silicone on outer edge if 
    surface is rough.

4. Supply 24 VDC power from Central Battery System to check lamp operation.

POLARIZED

LAMP

CONNECTOR

LAMP

ASSBY

TRIM PLATE

FRAMING (BY OTHERS)

GASKET

24 VDC

OUTPUT

24 VDC

INPUT

B

B

W

G
R

B

W

G
R

WG R

CEILING

WIRING FOR EM OPERATION ONLY

PIGTAIL 

(SUPPLIED)

24 VDC

OUTPUT

CEILING

B

W

G
R

BWG R

KEY

G= GREEN: COMMON: 24 VDC NEG -
W= WHITE: EXITS: 12-24 VDC POS +
R= RED: EMERGENCY: 24VDC POS +
B= BLACK: NORMAL ON LIGHTING 
     (NOL): 24 VDC POS +

WIRING FOR EM & NORMAL ON OPERATION 

PIGTAIL 

(SUPPLIED)

24 VDC

INPUT

B

W

G
R

 REV 8.17.04

Содержание Moonlite LED MHE Series

Страница 1: ...L Normal On Lighting Option PIGTAIL WITH SPLITTER SUPPLIED R B B R B 24 VDC INPUT CIRCUIT 24 VDC OUTPUT CIRCUIT 1 See Fig 1 and wiring details for EM Lighting Only and Normal On Lighting Option Identify mount position and install 4 x 4 J Box Route 24VDC wiring IN OUT as shown and connect pigtail supplied with lamp plug Connect Pigtail RED 24V power input circuit and Pigtail RED 24V wire to COMMON ...

Страница 2: ...onnect pigtail supplied with lamp plug 2 Install screw anchors in mounting surface for 4 8 32 screws to match holes provided in Bracket or Housing 3 Remove Lamp Assembly and install 4 8 32 screws to secure Bracket or Housing in position 4 Secure lamp assembly to bracket with screws provided and route lamp cable through opening in end of bracket Insert lamp cable through liquid tight bushing into L...

Страница 3: ...mbly with 4 8 screws Attach Trim Plate with 2 color matched 8 32 screws as shown Ensure gasket is properly seated on flat surface Use silicone on outer edge if surface is rough 4 Supply 24 VDC power from Central Battery System to check lamp operation POLARIZED LAMP CONNECTOR LAMP ASSBY TRIM PLATE FRAMING BY OTHERS GASKET 24 VDC OUTPUT 24 VDC INPUT B B W G R B W G R WGR CEILING WIRING FOR EM OPERAT...

Страница 4: ...ILING MOUNT BRACKET 2 SUPPLIED B CLIP 4 REQD BACK BOX For T Bar installations rotate side bracket clips as required to fit T Bar hangers For masonry ceilings attach side brackets to framing MOUNT BRACKET 4 SUPPLIED B CLIP 4 SUPPLIED DROPWIRES BAR HANGER SUPPLIED BY OTHERS CEILING 14 1 2 Install Housing in ceiling using supplied end brackets with B Clips to framing or hanger bars supplied by others...

Отзывы: