Wet Location
Series MHE-RE
Moonlite LED
™
Emergency & Security Light
-3-
Fig. 3. RECESSED MOUNT- WIRING
1. Route 24VDC IN/OUT wiring from CBS system into Housing.
2. Connect wiring with standard wire nuts to the supplied wiring pigtail, as shown. For emergency lighting
operation only, connect RED and GREEN; for normally ON/security lighting operation, connect RED,
GREEN and BLACK. (WHITE wire is passed through and not connected to this fixture).
3. Connect lamp plug and install lamp assembly with (4) #8 screws. Attach Trim Plate with (2) color- matched
#8-32 screws as shown. Ensure gasket is properly seated on flat surface. Use silicone on outer edge if
surface is rough.
4. Supply 24 VDC power from Central Battery System to check lamp operation.
POLARIZED
LAMP
CONNECTOR
LAMP
ASSBY
TRIM PLATE
FRAMING (BY OTHERS)
GASKET
24 VDC
OUTPUT
24 VDC
INPUT
B
B
W
G
R
B
W
G
R
WG R
CEILING
WIRING FOR EM OPERATION ONLY
PIGTAIL
(SUPPLIED)
24 VDC
OUTPUT
CEILING
B
W
G
R
BWG R
KEY
G= GREEN: COMMON: 24 VDC NEG -
W= WHITE: EXITS: 12-24 VDC POS +
R= RED: EMERGENCY: 24VDC POS +
B= BLACK: NORMAL ON LIGHTING
(NOL): 24 VDC POS +
WIRING FOR EM & NORMAL ON OPERATION
PIGTAIL
(SUPPLIED)
24 VDC
INPUT
B
W
G
R
REV 8.17.04