Wet Location
Series MHE-RE
Moonlite LED
™
Emergency & Security Light
CEILING
BRACKET
SPLITTER
(SUPPLIED)
BUSHING
CONDUIT
EM OPERATION ONLY
EM & NORMAL OPERATION ONLY
CONDUIT
LAMP CABLE
LIQUID TIGHT
OUTLET BOX
G
24 VDC INPUT
CIRCUIT
24 VDC OUTPUT
CIRCUIT
B
G
G
W
W
R
W
R
R
B
B
LIQUID TIGHT
OUTLET BOX
G
24 VDC INPUT
CIRCUIT
24 VDC OUTPUT
CIRCUIT
W
G
W
W
R
B
R
B
B
12" MAX
-2-
SURFACE BRACKET TOP MOUNT WITH EXTERNAL J-BOX
SURFACE HOUSING TOP MOUNT WITH EXTERNAL J-BOX
G
G
G
R
R
R
B
B
1. See Fig 2 and wiring details for EM Lighting Only, and Normal On Lighting Option. Identify
mount position and install 4” x 4” LIQUID TIGHT J-Box near to fixture. Route 24 VDC wiring
IN/OUT as shown and connect pigtail (supplied) with lamp plug.
2. Install screw anchors in mounting surface for (4) #8-32 screws to match holes provided in
Bracket or Housing.
3. Remove Lamp Assembly and install (4) #8-32 screws to secure Bracket or Housing in position.
4. Secure lamp assembly to bracket with screws provided and route lamp cable through opening
in end of bracket. Insert lamp cable through liquid tight bushing into LIQUID TIGHT j-box.
5. Connect WHITE +24V lamp wire to PO24V power input circuit and BLACK -24V lamp
wire to COMMON NEGATIVE -24V power input circuit with standard wire nuts.
CHECK CONNECTIONS BEFORE SUPPLYING POWER :
REVERSE POLARITY WILL PERMANENTLY DAMAGE FIXTURE
6. Supply 24VDC power from central battery or normal on/security power system to check lamp
operation.
LAMP
ASSBY
LAMP
ASSBY
(2) 8-32 X 3/8"
HEX HD SST
Fig. 2
COVER
BUSHING
8”
12" MAX
CEILING
LAMP
HOUSING
REV 8.17.04