INSTALLATION 

Install sediment trap in supply line as shown 

(see Fig. 14)

. Place sediment trap where it 

is within reach for cleaning. Place sediment 

trap where trapped matter is not likely to 

freeze. A sediment trap traps moisture and 

contaminants. This keeps them from going 

into heater controls. If sediment trap is not 

installed or is installed wrong, the heater may 

not run properly.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa) 

The appliance and the appliance main gas valve must be disconnected from the gas supply piping 

system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). 

Pressure Testing Gas Supply Equal To or less than 1/2 PSIG (3.5 kPa) 

The appliance must be isolated from the gas supply piping system by closing its equipment shutoff 

valve during any pressure testing of the gas supply piping system at test pressures equal to or less 

than 1/2 psi (3.5 kPa).

Leak Testing Heater Gas Internal Connections

 

1. 

Open equipment shutoff valve 

(see Fig. 15)

2. 

Make sure control knob of the heater is in the 

 

OFF position. 

3. 

Open gas supply tank valve (LP systems). 

4. 

Check all joints from equipment shutoff valve to  

 

control valve. Apply 50/50 mixture of liquid soap and  

 

water to gas joints. If bubbles form, there may be a  

 leak. 

5. 

Light heater (see “Lighting Instructions” on 

 

page 20). Check all other internal joints for leaks. 

6. 

Turn off heater (see “To Turn Off Gas to Appliance”      

 

on page 21). 

Closed

Open

Equipment

Shut off Valve

Fig. 15: Equipment Shutoff Valve

Fig. 14: Gas Connection

Sediment

Trap

Test

Gauge 

Connection

Tee Joint

1/8 in. 

Reducer

Bushing

1/8 in. NPT

Plug tap

3/8 in. NPT

Pipe Nipple

Ground Joint 

Union

Equipment

Shut off 

Valve

Tee Joint

Pipe Nipple

Gap

3 in. Minimum

Inlet Pipe From 

Gas Meter

WARNING

: Test all gas piping and connections for leaks after installing or servicing. Correct all 

leaks immediately. 

WARNING:

 Never use an open flame to check for a leak. Apply a 50/50 mixture of liquid soap 

and water to all joints. If bubbles form, there may be a leak. Correct all leaks immediately.

CHECKING GAS CONNECTIONS

Содержание C30000CLF

Страница 1: ...n from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air For Combustion and Ventilation section on page 7 of this manual INSTALLER...

Страница 2: ...U hr 15 000 15 000 15 000 15 000 Fuel Type Natural Gas Natural Gas Propane Propane Natural Gas Natural Gas Propane Propane Ignition Electronic Push Button Electronic Push Button Electronic Push Button...

Страница 3: ...ter will remain hot for a time after shutoff Allow surfaces to cool before touching WARNING Make sure any panel safety screen or guard removed for servicing an appliance is replaced prior to operating...

Страница 4: ...in a bedroom These units are not approved for bathroom use 3 This heater needs fresh air ventilation to run properly This heater has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shut...

Страница 5: ...ner on and off to maintain a desired room temperature For further information see page 20 State of Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth o...

Страница 6: ...Water vapor is a by product of gas combustion An unvented room heater produces approximately one 1 ounce 30 mL of water for every 1 000 BTU 3 Kw of gas input per hour An unvented room heater is inten...

Страница 7: ...LY TIGHT CONSTRUCTION The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of unusually tight construction you must provide addi...

Страница 8: ...as heater ___________ BTU hr Gas heater logs ___________ BTU hr Other gas appliances ___________ BTU hr Total ___________ BTU hr Do not include direct vent gas appliances Direct vent draws combustion...

Страница 9: ...se items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the National Fuel Gas Code NFPA 54 ANS Z223 1 Air for Combustion and Ventilation fo...

Страница 10: ...ng wall than required CAUTION This heater creates warm air currents These currents move heat to wall surfaces next to the heater Installing the heater next to vinyl or cloth wall coverings or operatin...

Страница 11: ...NOT dispose of batteries in fire Improper disposal may cause batteries to leak or explode PREINSTALLED FAN OPTIONAL WARNING This appliance is equipped with a three prong grounding plug for your prote...

Страница 12: ...ts wire connected to the receptacle mounting screw ACCESSING FAN 1 Turn off gas supply to appliance 2 Remove appliance from mounted position if applicable 3 Remove screws connecting front heater cover...

Страница 13: ...ION FAN WIRING ASSEMBLY DIAGRAM ELECTRICAL SCHEMATIC RED RED BLUE BLUE RED RED BLUE ON OFF AUTO SWITCH THERMAL SWITCH TO POWER CORD YELLOW GROUND YELLOW GROUND AUTO MANUAL OFF MOTOR AUTO MANUAL OFF TH...

Страница 14: ...er will be placed for leg installation to prevent scratching of the table and or the heater Set back of heater on table with the bottom of heater extending outside the table edge Fasten Support Legs t...

Страница 15: ...mounting Drill 5 16 in holes at least 1 in deep WARNING ELECTRICAL PLUMBING OR GAS LINES MAYBE IN WALL Before cutting drilling or hammering verify their location If needed contact your electrician plu...

Страница 16: ...ppliance using 2 wall hanging spacer screws 4 8 x 25 Check that the spacers are secure before mounting appliance Spacer Wall Hanging Spacer Screw Fig 13 Locate Mounting Slots on upper left right of ap...

Страница 17: ...line pressure is higher the unit will not work and heater regulator damage could occur CAUTION Never connect the heater directly to a LP supply This heater requires an external regulator not supplied...

Страница 18: ...5 kPa Leak Testing Heater Gas Internal Connections 1 Open equipment shutoff valve see Fig 15 2 Make sure control knob of the heater is in the OFF position 3 Open gas supply tank valve LP systems 4 Che...

Страница 19: ...y to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If y...

Страница 20: ...ilot is visible centered below the burner behind the front grill see Fig 18 Do not attempt to light the pilot by hand 7 Keep control knob depressed for 30 seconds after pilot lights Release control kn...

Страница 21: ...cool which shuts the heater off If pilot flame pattern is incorrect turn heater off see To Turn Off Gas to Appliance on page 21 see Troubleshooting pages 25 through 27 Ignitor Control Knob OFF P I L O...

Страница 22: ...orrect Abnormal Flame Pattern with tall flames with Control Knob Set to High Flame Infrared Flame NOTE Before servicing you will need to remove the front panel of the heater There are 4 tapping screws...

Страница 23: ...TION While the appliance is running press the switch to the MANUAL position see Fig 28 The fan will run continuously until turned to AUTO or OFF A DETAIL A SCALE 1 2 MANUAL Fig 28 MANUAL Switch Positi...

Страница 24: ...servicing CAUTION You must keep the control areas burner and circulating air passageways of the heater clean Inspect these areas of the heater before each use Have the heater inspected yearly by a qu...

Страница 25: ...lectrode is positioned wrong 2 Ignitor electrode is broken 3 Ignitor electrode is not connected to ignitor cable 4 Ignitor cable is pinched or wet 5 Damaged ignitor cable 6 Bad ignitor or ignition mod...

Страница 26: ...burner s 1 Manifold pressure is too low 2 Burner orifice is clogged 1 Contact your gas supplier 2 Clean burner orifice see Care and Maintenance on page 24 or contact customer service Burner backfiring...

Страница 27: ...ontrol valve is defective 1 Locate and correct all leaks see Checking Gas Connections on page 18 2 Contact customer service Moisture condensation noticed on windows 1 Not enough combustion ventilation...