INTEGRITY VOICE ALARM ROUTING MATRIX
Integrity Voice Alarm Routing Matrix Installation & Maintenance Manual • Approved Doc. No. DCS0003214 Rev 0 (8/2/05) • Page 10
The display is a 32 character, two line, backlit LCD,
Note that, in order to conserve power, the backlight only operates when necessary.
There are four control keys (NO, UP, DowN, YES), green LEDs for main and auxiliary
power present indication and a yellow LED for general fault indication.
The rear panel
There are 17 ‘slots’ for audio and control input and output cards.
As supplied, only the CPU card is fitted.
Display and controls
Power supply
The mainframe does not have its own mains power supply. It is powered by either one or
two 24 Vd.c. supplies, depending on the specification of the system, connected via the
CPU card.
The d.c. power should be derived from a regulated power supply with integral battery
charger connected to standby batteries. Overall battery size should be calculated as speci-
fied in the relevant installation standards. See separate product sections for current con-
sumption.
Serial port - RS232C
The serial port, which is located on the CPU card, has two functions.
• It is used to allow downloading of system configuration files created in Integrity Editor
software.
• In an operational system it can be connected to a PC to provide status and fault informa-
tion to a terminal program such as HyperTerminal, from which the data may be printed.
CPU
EIGHT INPUT CARDS
EIGHT OUTPUT CARDS (16 ZONES)