SIGMATEK FDD Step By Step Guide Size 5 to 9
STEP 8: Run the motor
This step will provide instruction on how to set-up the basic drive parameters, perform an auto-tune and run the
motor in analog input terminal mode or keypad mode.
Action
Detail
Power Up
Ensure:
•
The drive displays: inh (Enable terminal(s) is open)
Minimum and
maximum speed
Enter:
•
Minimum speed Pr
01
(Hz)
•
Maximum speed Pr
02
(Hz)
Accel and Decel
rates
Enter:
•
Acceleration rate Pr
03
(s)
•
Deceleration rate Pr
04
(s)
Motor nameplate
details
Ready to autotune
Autotune
The drive is able to perform either a stationary or a rotating autotune. The motor must be at
a standstill before any autotune is enabled and disconnected from the load for a rotating
autotune.
To perform an autotune:
•
Set Pr
10
to L2
•
Go to Pr
38
•
Set Pr
38
= 1 for a stationary autotune or set Pr
38
= 2 for a rotating autotune
•
Close the drive enable signal (apply +24 V to terminal 11 or terminal 31 and 35 on
FDD3. The drive will display ‘rdy’.
•
Give a Run command (apply +24 V to terminal 12 - Run forward or terminal 13 -
Run reverse. The display will flash ‘tuning’ while the drive is performing the autotune.
•
Wait for the drive to display ‘inh’ and for the motor to come to a standstill.
•
Remove the drive enable and run signal from the drive.
Ready to run (Analog input terminal mode by default)
Run
The drive is now ready to run the motor. Close Safe Torque Off (FDD3) and the Run Forward
or Run Reverse terminals.
Increasing and
decreasing speed
Changing the selected Analog frequency reference will increase and decrease the speed of
the motor.
Stopping
To stop the motor by following the selected deceleration rate, open either the run forward or
run reverse terminals. If the enable terminal is opened while the motor is running, the drive
output is immediately disabled and the motor will coast to a stop.
Ready to run (Keypad mode)
Run
The drive is now ready to run the motor. Set Pr
05
to 'PAd'. Close Safe Torque Off (FDD3).
Press the start key
Increasing and
decreasing speed
Press the up and down keys
to increase and decrease the speed.
Stopping
Press the Stop/Reset key
Motor rated current in Pr
06
(Amps)
Motor rated speed in Pr
07
(rpm / min
-1
)
Motor rated voltage in Pr
08
(Volts)
Motor rated power factor in (cos
) Pr
09
MOT. 3
LS 80 L T
N
734570 BJ 002 Kg
9
40 C
S1
IP 55
I cl.F
V
Hz min kW
cos
-1
A
230 50 2800 0,75 0,83 0,3
1
2
3
4