S-DIAS AXIS MODULE
DC 061-1
23.08.2019
Page 37
9.3
Performance Level e, Category 4 or SILCL 3
– Conventional
To meet the requirements of safety category 4, performance level "e" for EN ISO 13849-1
and SILCL 3 according to EN / IEC 62061, the placement of the lines must comply with EN
ISO 13849-2, table D.4 (separate placement, prohibiting of error via short circuits between
wires) as cross-circuit detection is not possible here.
Содержание DC 061-1
Страница 15: ...S DIAS AXIS MODULE DC 061 1 23 08 2019 Page 13...
Страница 17: ...S DIAS AXIS MODULE DC 061 1 23 08 2019 Page 15 3 Mechanical Dimensions...
Страница 24: ...DC 061 1 S DIAS AXIS MODULE Page 22 23 08 2019 5 Wiring 5 1 Wiring Example...
Страница 36: ...DC 061 1 S DIAS AXIS MODULE Page 34 23 08 2019...
Страница 38: ...DC 061 1 S DIAS AXIS MODULE Page 36 23 08 2019...
Страница 40: ...DC 061 1 S DIAS AXIS MODULE Page 38 23 08 2019...
Страница 42: ...DC 061 1 S DIAS AXIS MODULE Page 40 23 08 2019...