DC 061-1 

S-DIAS AXIS MODULE 

 

 

Page 8 

23.08.2019 

1.3 

General Safety Guidelines 

 

According to EU Guidelines, the operating instructions are a  component of 
a product. 

This  manual  must  therefore  be  accessible  in  the  vicinity  of  the  machine 
since it contains important instructions. 

This technical documentation should be included in the sale, rental or trans-
fer of the product, or its online availability indicated. 

Maintain this manual in readable condition and keep it accessible for refer-
ence. 

This  device  contains  a  Li-Ion  battery.  For  this  reason,  we  refer  you  to  the 
manufacturer’s specification (battery safety data sheet). This can be found 
on our website. 

Regarding the  requirements for  Safety  and  health connected  to  the  use of 
machines, the manufacturer must perform a risk assessment in accordance 
with  machine  guidelines  2006/42/EG  before  introducing  a  machine  to  the 
market. 

Before commissioning this product, check that conformance with the provi-
sions of the 2006/42/EG guidelines is correct. As long as the machine, with 
which the with the HGW or BWH should be used does not comply with the 
guideline, operating this product is prohibited. 

Operate  the  unit  with  devices  and  accessories  approved  by  SIGMATEK 
only. 

 

CAUTION

 

 

Handle the device with care and do not drop or let fall. 

Prevent foreign bodies and fluids from entering the device. 

The device must not be opened, otherwise it could be damaged! 

 

Manipulez l’appareil avec précaution et ne le laissez pas tomber. 

Empêchez les corps étrangers et les liquides de pénétrer dans l’appareil. 

L’appareil ne doit pas être ouvert, sinon il risque d’être endommagé! 

Regularly check the housing for mechanical damage. 

 

Vérifier régulièrement l’absence de dommages mécaniques sur le boîtier. 

 
 

Содержание DC 061-1

Страница 1: ...DC 061 1 S DIAS Axis Module Date of creation 26 07 2016 Version date 23 08 2019 Article number 20 014 061 1E...

Страница 2: ...t of this work may be reproduced edited using an electronic system duplicated or dis tributed in any form print photocopy microfilm or in any other process without the express permission We reserve th...

Страница 3: ...r input 1 holding brake The S DIAS DC 061 1 axis module is used to control a brushless DC motor with a 48 Volt supply voltage and phase current of up to 6 A A resolver input is available for position...

Страница 4: ...ications 9 2 2 Resolver Specifications 9 2 3 Enable Inputs Specifications 9 2 4 Holding Brake Specifications 10 2 5 Regen Brake Specifications 10 2 6 Electrical Requirements 11 2 7 Miscellaneous 14 2...

Страница 5: ...le M23 and Y Tec 27 5 4 1 M23 27 5 4 2 Y Tec 27 6 Motor Overload Protection 28 7 Safety Conformity 28 7 1 Functional Safety Standards 28 7 2 EU Conformity Declaration 28 7 3 Safety Relevant Parameters...

Страница 6: ...1 S DIAS AXIS MODULE Page 4 23 08 2019 9 4 Performance Level d Category 2 or SIL 2 Conventional 39 10 Transport Storage 41 11 Mounting 42 12 Maintenance 44 12 1 Maintenance 44 12 2 Repairs 44 13 Dispo...

Страница 7: ...a mid level risk which can lead to death or serious injury if not avoided Indique un danger possible d un risque moyen de d c s ou de graves blessures si les consignes de s curit ne sont pas respect e...

Страница 8: ...ides user tips informs of special features and identifies especially important information in the text Fournit des conseils d utilisation informe sur les fonctions particulaires et souligne les inform...

Страница 9: ...ument can be found on our website If necessary contact our support Subject to technical changes which improve the performance of the devic es The following documentation represents a series of product...

Страница 10: ...orm a risk assessment in accordance with machine guidelines 2006 42 EG before introducing a machine to the market Before commissioning this product check that conformance with the provi sions of the 2...

Страница 11: ...mperature monitor I2T monitor over and under voltage monitor 2 2 Resolver Specifications Type resolver Resolution 12 bit Output voltage EXC typically 7 Vrms Maximum output current EXC 200 mA Output fr...

Страница 12: ...resistor is sufficient If multiple DC 061 1s are driven with one intermediate circuit supply it is possible to equip only one module with regen braking The recommended regen resistor is available at S...

Страница 13: ...X4 must be limited to a max 5 A at voltages from 0 20 V DC or b 100 W at voltages from 20 60 V DC The limiting component e g transformer power supply or fuse must be certified by an NRTL Nationally Re...

Страница 14: ...acitors in the power supply are insufficient a regen resistor which converts the excess energy into heat must be connected to the servo motor output stage When selecting the power supply it is importa...

Страница 15: ...S DIAS AXIS MODULE DC 061 1 23 08 2019 Page 13...

Страница 16: ...environmental temperature by 0 5 C per 100 m Operating conditions Pollution degree 2 EMC resistance in accordance with 61000 6 7 2015 Generic standards Immunity re quirements for equipment intended to...

Страница 17: ...S DIAS AXIS MODULE DC 061 1 23 08 2019 Page 15 3 Mechanical Dimensions...

Страница 18: ...08 2019 4 Connector Layout 4 1 Baum ller Both holding brake outputs BR are internally connected in parallel Therewith the hold ing brake can be wired optionally to X3 pin 7 pin 8 or X4 pin 3 GND With...

Страница 19: ...IS MODULE DC 061 1 23 08 2019 Page 17 4 2 Kollmorgen Both holding brake outputs BR are internally connected in parallel The holding brake can therewith be optionally connected to X3 pin 7 Pin 8 or X4...

Страница 20: ...in the control cabinet OFF BLINKING 2 Hz BLINKING 4 Hz Motor Error red BLINKING motor output stage error OFF normal operation Motor DC OK green OFF no motor supply voltage BLINKING power applied but m...

Страница 21: ...n AWG kcmil 26 16 Conductor cross section flexible with ferrule without plastic sleeve DIN 46228 1 0 25 1 5 mm2 Conductor cross section flexible with ferrule with plastic sleeve DIN 46228 4 0 25 1 mm2...

Страница 22: ...DC 061 1 S DIAS AXIS MODULE Page 20 23 08 2019 IMPORTANT Le module S Dias NE PEUT PAS tre ins r ou retir sous tension...

Страница 23: ...61 1 23 08 2019 Page 21 4 5 Label Field Manufacturer Weidm ller Type MF 10 5 CABUR MC NE WS Weidm ller article number 1854510000 Compatible printer Weidm ller Type Printjet Advanced 230V Weidm ller ar...

Страница 24: ...DC 061 1 S DIAS AXIS MODULE Page 22 23 08 2019 5 Wiring 5 1 Wiring Example...

Страница 25: ...S DIAS AXIS MODULE DC 061 1 23 08 2019 Page 23 5 2 Wiring AKM Motors with SIGMATEK resolver and motor cables AKM...

Страница 26: ...m M061E 10 1 050 0 0 5 0 m M061E 10 1 100 0 0 10 0 m Without Holding Brake Length M061E 10 0 015 0 0 1 5 m M061E 10 0 030 0 0 3 0 m M061E 10 0 050 0 0 5 0 m M061E 10 0 100 0 0 10 0 m The Shielding PE...

Страница 27: ...onnections of the motor cable as well as the encoder cable shielding must be grounded via the 6 3 mm blade receptacle provided on the respec tive cables With increased interference it may be necessary...

Страница 28: ...abrasion and cut resistant polyurethane jacket allows use especially in industrial environments Advantages UL and CSA approved halogen free and cold resistant The cables are available in fixed prefab...

Страница 29: ...on motor side and device connector 5 4 1 M23 Name Encoder type Length Outer diameter F RO 061 015 0 00 Resolver 1 5 m 6 4 mm F RO 061 030 0 00 Resolver 3 m 6 4 mm F RO 061 050 0 00 Resolver 5 m 6 4 m...

Страница 30: ...an directives 2006 42 EG Directive of the European Parliament and of the Council of 17 May 2006 on Machinery and Change to the Directive 95 16 EC machine guideline 2014 30 EU Electromagnetic Compatibi...

Страница 31: ...afety modules can only be performed by qualified per sonnel Qualified personnel in this context are people who have completed training or have trained under supervision of qualified personnel and have...

Страница 32: ...ENABLE 2 inputs must be laid in a cable duct outside of the control cabinet Short and cross cir cuits have to be avoided See EN ISO 13849 When using the SS1 Safe Stop 1 safety function the typical tur...

Страница 33: ...t also be shut down externally 8 2 Function The safety functions in the DC 061 1 are controlled over two digital inputs The following table shows the status that the ENABLE 1 and ENABLE 2 inputs must...

Страница 34: ...t be tested for full functionality Tests must be performed at the following times After installation In regular intervals or at least once a year If the function test results in an invalid machine sta...

Страница 35: ...and applied in order to fulfill the requirements of the category used 9 1 Performance Level e Category 4 or SILCL 3 Safety PLC To meet the requirements of category 4 performance Level e for EN ISO 138...

Страница 36: ...DC 061 1 S DIAS AXIS MODULE Page 34 23 08 2019...

Страница 37: ...CL 3 Safety PLC To meet the requirements of safety category 3 performance level e for EN 13849 1 and SILCL 3 according to EN IEC 62061 an error proof output of a safety PLC must be used The reason of...

Страница 38: ...DC 061 1 S DIAS AXIS MODULE Page 36 23 08 2019...

Страница 39: ...meet the requirements of safety category 4 performance level e for EN ISO 13849 1 and SILCL 3 according to EN IEC 62061 the placement of the lines must comply with EN ISO 13849 2 table D 4 separate pl...

Страница 40: ...DC 061 1 S DIAS AXIS MODULE Page 38 23 08 2019...

Страница 41: ...ODULE DC 061 1 23 08 2019 Page 39 9 4 Performance Level d Category 2 or SIL 2 Conventional This involves 1 channel wiring whereby the Enable inputs are tested separately Here no cross circuit detectio...

Страница 42: ...DC 061 1 S DIAS AXIS MODULE Page 40 23 08 2019...

Страница 43: ...transport as well as during storage avoid excessive mechanical loads The same values for moisture and vibration shock vibration must be ob served for storage and transport as during operation CAUTION...

Страница 44: ...of the control cabinet The individual S DIAS modules are mounted on the DIN rail as a block and secured with latches The modules must be mounted horizontally module label up with sufficient clearance...

Страница 45: ...S DIAS AXIS MODULE DC 061 1 23 08 2019 Page 43 Recommended minimum distances of the S DIAS modules to the surrounding components or control cabinet wall a b c distances in mm inches...

Страница 46: ...ansported in the original pack aging when possible Otherwise packaging should be selected that suffi ciently protects the product from external mechanical influences Such as cardboard filled with air...

Страница 47: ...cal Requirements Note Servo Motor Braking added 31 01 2018 13 3 4 Applicable Connectors Connections Weidm ller added 04 04 2018 5 1 5 Regen Brake Specifica tions Lowest possible resistance added 18 06...

Отзывы: