C-DIAS SAFETY CPU
CSCP 012
1.6
Page 17
Environmental conditions
Storage temperature
-20 to +85 °C
Operating temperature
0 to +55 °C
Humidity
0 to 95 %, uncondensed
EMV stability
According to EN 61000-6-2: 2005 (industrial area) Raised requirements
according to IEC 26061
Shock resistance
EN 60068-2-27
15 g
Protection Type
EN 60529
IP 20
Table 8: Environmental conditions
Miscellaneous
Article number
12-890-012
Hardware version
1.x
Output Power Supply
So that a short circuit on the supply of the outputs resulting from an error does not
cause the PLC to fail, it is recommended that separate power supplies be used for
the 24 V C-DIAS bus supply (fed to the C-IPC or CIV) and the supply for the out-
puts and clock signals.