Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual

Page 6 of 10

Smoke Detection Circuits

7.1  One to six smoke detection circuits are provided and supply 28 Volts ( + 5%) for the

operation of trigger devices, (smoke detectors or heat detectors).  Terminals for the
smoke detection circuits are labelled Z1+ and Z1- to Z6+ and Z6- for positive and
negative connections respectively.  It is important to observe the polarity of these
connections for correct operation of the system.

7.2   A 6K8 end of line resistor must be fitted to the last device on the smoke detection

circuit for correct operation of the monitoring functions.  Alternatively for greater system
integrity a line continuity monitoring unit (LCMU) may be fitted.

Sounder Circuits

8.1   Two sounder circuits outputs are provided and are labelled (S1 +&-) &( S2 + &-).

These outputs will operate together upon activation of a smoke detection zone, opera-
tion of  the evacuate switch or the remote Alarm input. Each sounder circuit is pro-
tected by a 500mA fuse.

8.2

Both outputs are monitored against open and short circuit faults in the field wiring.
Any such faults are annunciated by the front panel system fault indicator immediately.

8.5

The sounder circuit is normally fitted with a 20K end of line monitoring resistor.

Fault VFCO Contacts

9.1

Volt free contacts are provided for remote signalling or plant shutdown on the occurrence
of any fault condition.

Fire VFCO Contacts

10.1 Volt free contacts are provided for remote signalling or plant shut down on the

occurrence of any fire condition or evacuate condition.

10.2 All contacts are rated at 30V DC 1 Amp maximum and should under no circumstances

be used to switch greater voltages or currents (see annex 3).

INTERNAL CONTROLS - 

Continued

Two zone Sigma

Normal switch positions

Four zone Sigma

Normal switch positions

TERMINAL FUNCTIONS

Содержание K1000 Series

Страница 1: ...Sigma K1000 Series 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Man 1048 Issue 05 October 2009 ...

Страница 2: ...ontrols Front Panel Indications 3 FrontPanelIndications continued 4 InternalIndicators 5 InternalControls 6 InternalControls continued TerminalFunctions 7 TerminalFunctions continued 8 Annexe TypicalwiringConnections UseOfAux 24VOutput 1 SigmaInstallation MainsSupplyConnection 2 Connections To Detectors Sounders 3 K1002 PCB Layout 1 2 Zone K1006 PCB Layout 4 6 Zone 4 ...

Страница 3: ...o be operated from 220 240V AC mains supplies and is of class I construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation 1 4 Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe SAFETY Page 2 of 10 INSTALLATION 2 1 Remove the front panel by ...

Страница 4: ...e buzzer will sound the alarm tone FRONT PANEL CONTROLS 2 7 This equipment is designed to be powered from the 220 240V C mains supply The mains connection must include a protective Earth conductor to the requirements of BS 7671 see annex 2 2 8 The mains supply must be from a separate dedicated fused spur labelled FIRE ALARMS DO NOT SWITCH OFF 2 9 The installation should be carried out by or under ...

Страница 5: ...immediate attention Zone fault indicators will illuminate in the event of 1 Disconnection or severance of zone wiring 2 Short Circuit on zone wiring 3 Removal of a sensor from its base 4 Disconnection of the end of line monitor resistor or active end of line unit LCMU 4 5 Fire Indicators Upon detection of a fire the red zone fire alarm indicator will flash to give warning of the area zone in fire ...

Страница 6: ...inate in the event of a open circuit on one of the sounder lines 5 3 Fuse Fault Indicator This indicator will illuminate in the event of A Auxiliary fuse failure B System fuse failure 5 4 Earth Fault Indicator This indicator will illuminate in the event of a positive or negative earth fault i e Field wiring connected to earth 5 5 Rem Fire Sig disabled indicator Thisindicator will illuminateintheev...

Страница 7: ...S1 S2 These outputs will operate together upon activation of a smoke detection zone opera tion of the evacuate switch or the remote Alarm input Each sounder circuit is pro tected by a 500mA fuse 8 2 Both outputs are monitored against open and short circuit faults in the field wiring Any such faults are annunciated by the front panel system fault indicator immediately 8 5 The sounder circuit is nor...

Страница 8: ...ound 2 second on 2 second off This will pulse the Sounders at this rate if connected to the remote alarm input If continuous sounders Evacuate is required then link R143shouldberemoved as indicated on annex 3 Auxiliary 24V Output Max O P Current 100mA 12 1 The auxiliary 24V output is provided to power any additional equipment which is fitted to the system such as remote shutdown relays This output...

Страница 9: ...Sigma K1000 Series 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Page 8 of 10 ANNEXE 2 ...

Страница 10: ...oring wiring Standard bases are used Removal of a detector indicates fault but detectors beyond the removed one will be inoperative Line continuity unit wiring Diode bases are used Removal of a detector indicates fault and detectors beyond the removed one remain operative Connections to sounders Page 9 of 10 ...

Страница 11: ...es 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Page 10 of 10 ANNEXE 4 K1006 PCB layout 4 6 zone Sigma fuse option resistor locations K1002 PCB layout 1 2 zone Sigma fuse option resistor locations ...

Отзывы: