Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual

IMPORTANT

READ THIS SECTION FIRST!

1.1 Suppliers of articles for use at work are required under section 6 of the Health and

Safety at Work Act 1974 to ensure as reasonably as is practical that the article will be
safe and without risk to health when properly used.An article is not regarded as prop-
erly used if it is used "without regard to any relevant information or advice" relating to
its use made available by the supplier.

1.2 This product should be installed, commissioned and maintained by or under the supervi-

sion of competent persons according to good engineering practice and:-

i)

IEE regulations for the electrical equipment of buildings.

ii) Codes of practice.
iii) Statutory requirements.
iv) Any instructions specifically advised by the manufacturer.

According to the provisions of the act you are therefore requested to take such steps as
are necessary to ensure that any appropriate information about this product is made
available by you to anyone concerned with its use.

1.3  This equipment is designed to be operated from 220-240V AC mains  supplies and is of

class I construction. As such it must be connected to a protective earthing conductor in
the fixed wiring of the installation.

1.4  Failure to ensure that all conductive accessible parts of this equipment are adequately

bonded to the protective earth will render the equipment unsafe.

SAFETY

Page 2 of 10

INSTALLATION

2.1 Remove the front panel by unscrewing the two Socket screws with a key. This  will

expose the internal equipment and three fixing holes.

2.2 Place the circuit boards in a safe area for later installation.

2.3 Locate the unit on the wall in the agreed position and mark  the fixing points through the

dished mounting holes (see annex 2). Drill and fit suitable wall plugs and screw the
panel  to the wall.

2.4 Use the knockouts provided to make off  the cables. Earth or drain wires should be

kept as short as is  practical and  be connected to a metal cable gland making sound
electrical contact with the enclosure.

2.5 If additional or larger cable entries are required, any swarf and debris must be cleared

from the inside of the equipment. Failure to do this will result in equipment malfunction
and could represent a danger to building occupants.

2.6  The mains fuse must only be replaced with a 2 amp fuse conforming to BS:4265.

Содержание K1000 Series

Страница 1: ...Sigma K1000 Series 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Man 1048 Issue 05 October 2009 ...

Страница 2: ...ontrols Front Panel Indications 3 FrontPanelIndications continued 4 InternalIndicators 5 InternalControls 6 InternalControls continued TerminalFunctions 7 TerminalFunctions continued 8 Annexe TypicalwiringConnections UseOfAux 24VOutput 1 SigmaInstallation MainsSupplyConnection 2 Connections To Detectors Sounders 3 K1002 PCB Layout 1 2 Zone K1006 PCB Layout 4 6 Zone 4 ...

Страница 3: ...o be operated from 220 240V AC mains supplies and is of class I construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation 1 4 Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe SAFETY Page 2 of 10 INSTALLATION 2 1 Remove the front panel by ...

Страница 4: ...e buzzer will sound the alarm tone FRONT PANEL CONTROLS 2 7 This equipment is designed to be powered from the 220 240V C mains supply The mains connection must include a protective Earth conductor to the requirements of BS 7671 see annex 2 2 8 The mains supply must be from a separate dedicated fused spur labelled FIRE ALARMS DO NOT SWITCH OFF 2 9 The installation should be carried out by or under ...

Страница 5: ...immediate attention Zone fault indicators will illuminate in the event of 1 Disconnection or severance of zone wiring 2 Short Circuit on zone wiring 3 Removal of a sensor from its base 4 Disconnection of the end of line monitor resistor or active end of line unit LCMU 4 5 Fire Indicators Upon detection of a fire the red zone fire alarm indicator will flash to give warning of the area zone in fire ...

Страница 6: ...inate in the event of a open circuit on one of the sounder lines 5 3 Fuse Fault Indicator This indicator will illuminate in the event of A Auxiliary fuse failure B System fuse failure 5 4 Earth Fault Indicator This indicator will illuminate in the event of a positive or negative earth fault i e Field wiring connected to earth 5 5 Rem Fire Sig disabled indicator Thisindicator will illuminateintheev...

Страница 7: ...S1 S2 These outputs will operate together upon activation of a smoke detection zone opera tion of the evacuate switch or the remote Alarm input Each sounder circuit is pro tected by a 500mA fuse 8 2 Both outputs are monitored against open and short circuit faults in the field wiring Any such faults are annunciated by the front panel system fault indicator immediately 8 5 The sounder circuit is nor...

Страница 8: ...ound 2 second on 2 second off This will pulse the Sounders at this rate if connected to the remote alarm input If continuous sounders Evacuate is required then link R143shouldberemoved as indicated on annex 3 Auxiliary 24V Output Max O P Current 100mA 12 1 The auxiliary 24V output is provided to power any additional equipment which is fitted to the system such as remote shutdown relays This output...

Страница 9: ...Sigma K1000 Series 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Page 8 of 10 ANNEXE 2 ...

Страница 10: ...oring wiring Standard bases are used Removal of a detector indicates fault but detectors beyond the removed one will be inoperative Line continuity unit wiring Diode bases are used Removal of a detector indicates fault and detectors beyond the removed one remain operative Connections to sounders Page 9 of 10 ...