Sigma K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels Operation and Maintenance Manual

Page 4 of 10

FRONT PANEL INDICATIONS - 

Continued

4.2 System Fault Indicator

The system fault indicator will illuminate under any abnormal condition.  Certain conditions
may be diagnosed without looking inside the enclosure as follows:-

(1) System Fault on. Supply Healthy off

=

Power failure or system fuse failure.

(2) System Fault on, Zone Fault on

=

Zone O/C or S/C in indicated zone.

(3) System Fault on, Zone test on

=

Zone indicated in test  mode.

(4) System Fault  on,  Disabled Led on

=

Zone indicated in disabled/isolated  mode.

(5) System Fault  on.  Sounder Fault on

=

Sounder Circuit O/C or S/C Fault.

4.3  Alarm Silenced Indicator

The alarm silenced indicator should only be accompanied by one or more steady fire
indicators, and indicates that the sounders have been silenced.
Operation of subsequent fire zones or the  evacuate switch will  extinguish the alarm
silenced indicator.

4.4 Zone Fault  Indicator

Illumination of a zone fault indicator may mean that one or more  trigger devices are
inoperative and  requires immediate attention.
Zone fault  indicators will illuminate in the event of:-

(1) Disconnection or severance of zone wiring
(2) Short Circuit on zone wiring
(3) Removal of a sensor from its base
(4) Disconnection of the end of line monitor resistor, or active end of line unit (LCMU)

4.5 Fire Indicators

Upon detection of a fire the red zone fire alarm indicator will flash to give warning of
the area (zone) in fire and the common fire indicator will be illuminated.  This will be
accompanied  by a pulsing buzzer within the control panel and the operation of the
sounders.

4.6 Sounder Fault Indicator

The sounder fault  indicator and the system fault indicator will be illuminated if a sounder
circuit is open or short circuit.

4.7 Zone Test Indicator

The zone test indicator will be illuminated if one or more  zones are in  zone  test mode.

4.8 Disabled Indicator

The disabled indicator will be illuminated if :-
(A) one or more zones are in the disabled mode. This is accompanied by the zone fault
indicator.
(B) The Sounder disable or remote signal, disable switch is operated. This Indicator will
be accompanied by the system fault indicator.

4.9 Common Fire/ Evacuate Indicator

The common fire indicator  will be illuminated if the panel is in an alarm condition  or in
an evacuate condition.

Содержание K1000 Series

Страница 1: ...Sigma K1000 Series 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Man 1048 Issue 05 October 2009 ...

Страница 2: ...ontrols Front Panel Indications 3 FrontPanelIndications continued 4 InternalIndicators 5 InternalControls 6 InternalControls continued TerminalFunctions 7 TerminalFunctions continued 8 Annexe TypicalwiringConnections UseOfAux 24VOutput 1 SigmaInstallation MainsSupplyConnection 2 Connections To Detectors Sounders 3 K1002 PCB Layout 1 2 Zone K1006 PCB Layout 4 6 Zone 4 ...

Страница 3: ...o be operated from 220 240V AC mains supplies and is of class I construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installation 1 4 Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe SAFETY Page 2 of 10 INSTALLATION 2 1 Remove the front panel by ...

Страница 4: ...e buzzer will sound the alarm tone FRONT PANEL CONTROLS 2 7 This equipment is designed to be powered from the 220 240V C mains supply The mains connection must include a protective Earth conductor to the requirements of BS 7671 see annex 2 2 8 The mains supply must be from a separate dedicated fused spur labelled FIRE ALARMS DO NOT SWITCH OFF 2 9 The installation should be carried out by or under ...

Страница 5: ...immediate attention Zone fault indicators will illuminate in the event of 1 Disconnection or severance of zone wiring 2 Short Circuit on zone wiring 3 Removal of a sensor from its base 4 Disconnection of the end of line monitor resistor or active end of line unit LCMU 4 5 Fire Indicators Upon detection of a fire the red zone fire alarm indicator will flash to give warning of the area zone in fire ...

Страница 6: ...inate in the event of a open circuit on one of the sounder lines 5 3 Fuse Fault Indicator This indicator will illuminate in the event of A Auxiliary fuse failure B System fuse failure 5 4 Earth Fault Indicator This indicator will illuminate in the event of a positive or negative earth fault i e Field wiring connected to earth 5 5 Rem Fire Sig disabled indicator Thisindicator will illuminateintheev...

Страница 7: ...S1 S2 These outputs will operate together upon activation of a smoke detection zone opera tion of the evacuate switch or the remote Alarm input Each sounder circuit is pro tected by a 500mA fuse 8 2 Both outputs are monitored against open and short circuit faults in the field wiring Any such faults are annunciated by the front panel system fault indicator immediately 8 5 The sounder circuit is nor...

Страница 8: ...ound 2 second on 2 second off This will pulse the Sounders at this rate if connected to the remote alarm input If continuous sounders Evacuate is required then link R143shouldberemoved as indicated on annex 3 Auxiliary 24V Output Max O P Current 100mA 12 1 The auxiliary 24V output is provided to power any additional equipment which is fitted to the system such as remote shutdown relays This output...

Страница 9: ...Sigma K1000 Series 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Page 8 of 10 ANNEXE 2 ...

Страница 10: ...oring wiring Standard bases are used Removal of a detector indicates fault but detectors beyond the removed one will be inoperative Line continuity unit wiring Diode bases are used Removal of a detector indicates fault and detectors beyond the removed one remain operative Connections to sounders Page 9 of 10 ...

Страница 11: ...es 1 2 4 6 Zone Fire Control Panels Operation and Maintenance Manual Page 10 of 10 ANNEXE 4 K1006 PCB layout 4 6 zone Sigma fuse option resistor locations K1002 PCB layout 1 2 zone Sigma fuse option resistor locations ...

Отзывы: