- 7 -
2-3 The Appearance and Mechanical Drawing of TPH Series
2-4 Features
Smart LED Remote Control
Battery Temperature Sensor (BTS)
Automatic Generator Start (AGS)
Designed For Harsh Environment Operation
DC Start & Automatic Self-Diagnostic Function
Easy to Install & Easy to Operate & Easy to Solve
Low DC Voltage Supports Home & Office Appliances
High Energy Charging Function, Selectable From 0%-100%
High Efficiency Design &“Power Saving Mode”to Conserve Energy
Battery Priority Mode, Designates the Inverter-Preferred UPS Configuration
26/52Vdc Battery Recover Point, Dedicated for Renewable Energy Systems
8 pre Set Battery Type Selector plus De-sulphation for Totally Flat Batteries
4-step Intelligent Battery Charging, PFC (Power Factor Correction) for Charger
Independently controlled three-phase output voltages & Load,100% Unbalanced load
0ms Transfer Time From Battery to Utility ;8ms Typical Transfer Time From Utility to Battery
15s Delay Before Transfer when AC Recover, Protection for Load when Used with Generator
2-5 Electrical Performance
2.5.1 Inverter
Topology
The TPH inverter/charger is built according to the following topology.
Inverter: Full Bridge Topology.
AC Charger: Isolate Boost Topology
Solar Charger: MPPT PV Controller
Because of high efficiency IGBT and 32bit, 30MHz microprocessor and heavy transformers, it outputs
PURE SINE WAVE Waveform with an average THD of 3% (Max 8%) depending of load connected and
battery voltage.
The peak efficiency of TPH-PV series is 88%.
Overload Capacity
The TPH series inverters have different overload capacities, making it ideal to handle demanding loads.
1 For 110%<Load<125%(±10%), no audible alarm in 14 minutes, beeps 0.5s every 1s in the 15th minute,
and Fault(Turn off) after the 15th minute.
2 For 125%<Load<150%(±10%), beeps 0.5s every 1s and Fault(Turn off) after the 1 minute.
Содержание TPH 12KW
Страница 20: ... 20 TPH 24 36KW Model TPH 45KW Model ...