- 18 -
CAUTION: Equipment Damage
The inverter is not reverse polarity protected. Reversing the battery polarity on the DC input connections
will cause permanent damage to the inverter which is not covered under warranty. Always check polarity
before making connections to the inverter.
WARNING: Shock Hazard
Ensure the inverter is off before disconnecting the battery cables, and that AC power is disconnected from
the inverter input.
Battery terminal must be clean to reduce the resistance between the DC terminal and cable connection. A
buildup of dirt or oxidation may eventually lead to the cable terminal overheating during periods of high
current draw. Use a stiff wire brush and remove all dirt and corrosion from the battery terminals and cables.
3-3 AC Wiring
We recommend using 10-5AWG wire to connect to the AC terminal block.
The three phase inverter only supports Y connection. It willn’t support delta connection.
There are 3 different ways of connecting to the terminal block depending on the model. All the wirings are CE
compliant, Call our tech support if you are not sure about how to wire any part of your inverter.
The TPH inverter will automatically bond the neutral with ground in DC to AC battery mode, and separate neutral with
ground in AC model.
3-Phase Wiring Mode
INPUT R
INPUT N
OUTPUT N
Battery
DC Power
Q1-R
Q3-R
Q2-R
Q4-R
MAIN TX-R
CT-R
Transfer SW-R
R-CB
TPP Series Inverter&Charger Topology Diagram
Inverter Mode
In Ground
CHARGE INPUT
PROTECT BREAKER
Transfer SW-N
Discharger Mode
R
Phase
CHARGE INPUT
PROTECT BREAKER
CHARGE INPUT
PROTECT BREAKER
Q1-S
Q3-S
Q2-S
Q4-S
S
Phase
Q1-T
Q3-T
Q2-T
Q4-T
CT-S
CT-T
T
Phase
INPUT S
Transfer SW-S
S-CB
INPUT T
AC Output
Transfer SW-T
T-CB
Out Ground
MAIN TX-S
MAIN TX-T
1 Phase Load * 3
120/230Vac
3 Phase Delta Load
Y- 220/400Vac
3 Phase
AC Circuit Breaker