water coils are also available in 2 turn coils for all models to heat approx.
15-20 gallons of water.
2. Important Notes
Here are some important notes to remember when installing a Sig Marine
diesel stove:
•
Mounting & location, 12v power hook-up, minimum 4ft and a
maximum 10ft of chimney, the location of hole for the chimney & the
fuel supply.
•
VERY IMPORTANT: Unrestricted permanent fresh air inlet
required to draw in outside air needed for correct operation.
•
Fuel must be filtered and not exceed a pressure of 4 psi or a fuel
pressure regulator must be used to avoid dangerous flooding (Sig
Marine part# 15074).
•
A barometric damper must be installed to help regulate the draft. A
barometric gives you more control in the “fuel to air” mixture needed
for correct operation. The valve controls the fuel whereas the fan
increases the air and the barometric decreases the air (See Pg. 9).
•
Install a CO alarm.
3. Ventilation
Do NOT operate this stove in an enclosed area without a permanent fresh air
inlet designated for your stove. This is required to draw in outside air for correct
operation. To guarantee that fresh air is available for your stove, good
ventilation is essential. You MUST replace the air inside your boat at the same
rate that the stove is removing it. The higher the stove’s burning rate, the more
air the stove will require. If the air flow is blocked or restricted, the stove will
burn inefficiently, create soot, blow out and can even be a very dangerous health
hazard.
A permanently open fresh air inlet MUST be installed or dedicated to the stove.
This inlet must be at least 3" in diameter. Ducting to the stove is also an option.