30
Fig 10. Measurement of 60 minutes’ active power consumption
synchronized with the clock, with alarm set on a 90% consumption.
An example of the parameter value utilization of ordered active power to
switch the alarm on is presented on the fig. 10. The time delay is set on
0 sec. In the calculated example, for remaining 10% of ordered power,
at the maximum power consumption, devices could still work during 60
sec without exposing customers to fines. when setting the time delay
ALdt on 60 sec, the alarm would not be enabled.
Set:
Monitored quantity: P_ord, Kind of alarm: n-on, ALon = 90.0, ALoF = 89.9,
Tr_1 = 500, Syn = c_60, Time delay ALdt = 0 or 240 s.