6.5.3. Setting of Alarm Parameters
Select the
ALr
mode in options and approve the choice by the
push-button.
Item
Para
-
meter name
Desi- gnation
Range
Notes/ des
-
cription
Manufac-
turer’s value
1
Quantity in
the alarm
output
AL_n
table 6
(code acc. to the table 6)
P
2
Alarm type
AL_t
n-on,
n-oFF,
on, oFF,
H-on,
H-oFF,
A3non,
A3nof,
A3_on,
A3_of
Fig. 9
n-on
Table 5
3
Lower value
of the input
range
ALoF
-144.0 ...
144.0
in % of the rated quantity value
99,0
4
Upper value
of the input
range
ALon
-144.0 ...
144.0
in % of the rated quantity value
101,0
5
Time delay of
the switching
reaction
ALdt
0 ... 900
in seconds (for quantities AL_n
=P_ord the delay occurs only when
switching the alarm on)
0
6
Support of
the alarm
occurrence
signaling
AL_S
oFF, on
In the situation when the support
function is enabled, after the
retreat of the alarm state the alarm
symbol is not blanked but begins to
pulsate. The signaling exists till the
moment of blanking it by means of
the and push-buttons
combination (during 3 seconds).
The function concerns only and
exclusively the alarm signaling, then
relay contacts will be active without
support, acc. to the selected type of alarm.
oFF
7
Interlocking
of a renewed
alarm
switching on
AL_b
0...900
in seconds
0
8
Manufacturer’s
parameters
dEF
no, yES
Restoration of manufacturer’s
parameters of the group.
no
The write of the value ALon lower than ALoF switches the alarm off.