While measuring, it is also possible to display the leakage current, the DAR (Dielectric Absorp on
Ra o if test dura on > 1 minute), the PI (Polariza on Index if test dura on > 10 minutes) which
cyclically show when pressing the arrow keys (see § 11.1)
10.
If no measuring me was set when se ng the parameters or if you want to stop the test in
advance before the set me elapses, press the
START/STOP
key
11a. Once measurement is complete and any
capacitance has been discharged, the
instrument shows:
The value of the measured insula on
resistance;
The value of the generated voltage;
The dura on of the test
If the measured resistance value is
between the (MIN - MAX) limits
previously set, the instrument shows
OK and gives a double acous c signal
(see § 4.10.1)
OR
11b. Once measurement is complete and any
capacitance has been discharged, the
instrument shows:
The value of the measured insula on
resistance
The value of the generated voltage
The dura on of the test
If the measured resistance value is not
between the (MIN - MAX) limits
previously set, the instrument shows
NOT OK, the alarm bell and gives a
long acous c signal (see § 4.10.1)
12.
Once measurement is complete, it is also possible to display the leakage current, the DAR
(Dielectric Absorp on Ra o), the PI (Polariza on Index) and the cap acitance which cyclically
show when pressing the arrow keys (see § 11.1)
CAUTION
If the measured resistance value < 5.0MΩ , the screen displaying the capacitance
shows three hyphens “---“, to indicate that it was impossible to measure the
capacitance, and the symbol
If, when scrolling the results obtained, the capacitance value is > 1nF, it is
recommended to repeat the measurement by ac va ng the SMOOTH func on
(see § 4.11)
13.
Measures can be saved by pressing the
SAVE
key twice (see § 5.1)