1-4
Air Filters
(Inside Air Intake Grille)
TO OUTDOR UNIT
Wrap the Insulated pipe with the
Þ
nishing tape from bottom to top
Air Discharge Louver
Air Intake Grille
INSTALLATION DIAGRAM (AHQ71AV1)
Top Panel
Bottom Panel
Figure A
Preliminary Site Survey
Voltage supply
ß
uctuation must not exceed ±10% of the
rated voltage. Electricity supply lines must be independent
of welding transformers which can cause high supply
ß
uctuation.
Ensure that the installation location is convenient for wiring
and piping.
•
•
Standard Mounting
Ensure that the overhead supports are strong enough to hold
the weight of the unit. Position the hanger rods (wall mounting
bracket for
ß
oor standing), and check for its alignment with
the unit as shown in Figure A. Also, check that the hangers
are secured and the base of the fan coil unit is leveled in both
horizontal directions, taking into account the gradient for
drainage
ß
ow as recommended in Figure B.
A
B
C
H
G
E
D
F
Figure B
10mm or more
All dimensions are in mm
INSTALLATION OF THE INDOOR UNIT (AHQ71AV1)
Thermal insulation
Dimension
Model
A
B
C
D
E
F
G
H
AHQ71AV1
1073
534
268
135
336
630
145
485