background image

All SIERRA Hearthstoves require floor protection when

installed on a combustible surface. For hearthstoves

without the ash pan or catalytic option, you must place your

stove on a anon-combustible floor protector equivalent to

two 3/8' layers of asbestos covered with one sheet of 24

gauge minimum sheet steel. The floor protector must

extend 16" in front of the door side, 12" from the rear side

on rear vents stoves, 8" from rear side on top vent stoves,

8" from the other side of the stove, under the chimney

connection and 2" beyond each side.

MINIMUM CLEARANCE TO COMBUSTIBLES

Rear Vented

Top Vent

Units To

18"

A

Side Wall

18"

26"

B

Back Wall

18"

16"

C

Corner

12'

Flue To

31"

D

Side Wall

30"

18"

E

Back Wall

19"

18"

F

Corner

24"

There are listed non-asbestos floor protectors available at

your local woodstove supplier.
Recommended floor protection is based on a standard of

3/8" Inch of asbestos millboard or equivalent. This is used

as a standard only.
The k, C or R factor that correlates with the floor protector

material used during the test if the room heater is not

provided with a floor protector.  The units of measure for k,

C and R factors shall use the same applicable units. 

Directions and examples on how to use alternate materials

and how to calculate equivalent thickness shall be shown.
An easy means of determining if a proposed alternate floor

protector meets requirements listed in the appliance

manual is to follow this procedure:
1.  Convent specifications to R-value

a.   R-value is given - no conversion is needed.

b.  K-factor is given with a required thickness (T) in

inches: R=1/k+T

c.   C-factor is given: R=1/C

2. Determine the R-value of the proposed alternate floor

protector.

a.   Use the formula in step 1 to convert values not

expressed as “R”.

b.   For multiple layers, add R-values of each layer to

determine the overall R-value.

3. If the overall R-value of the system is greater than the R-

value of the specified floor protector, the alternate is

acceptable.

EXAMPLE: 

The specified floor protector should be 3/4 inch thick

material with a k-factor of .84.  
The proposed alternate is 4" brick with a C-factor of 1.25

over 1/8" mineral board with a k-factor of .29.
Step 1:  Use formula above to convert specification to          

  R-value.  R=1/kT = 1/0.84 x .75 = .893

Step 2:  Calculate R of proposed system.

          4" brick of C - 1.25, therefore 

              R brick = 1/C = 1/1.25 = 0.80

              1/8" mineral board of k+ 0.29, therefore

              R min.bd. = 1/0.29 x 0.125 = 0.431

    Total R = R brick + R brick + R mineral Board

                           = 0.8 + 0.431 = 1.231

Step 3: Compare the proposed system R of 1.231 to            

      specified R of 0.893.  Since proposed system             

    R is greater than required, this is acceptable.

Definitions:

3/8 inch millboard has a “K” factor of 0.84. The newer

substitute CERAFORM board has a “K” factor of 0.21.

Your floor protector must have an equivalent or better “K”

factor than the above recommendations.

WARNING: The installation of this stove must comply with

state and local requirements and be inspected by the state

or local building inspector, if required.

This stove is not approved or recommended for use in

mobile homes.

7

Содержание S8000II

Страница 1: ...ion and operation of the Sierra S8000II wood heater EMISSION CERTIFICATION STATUS The S8000II model meets the U S Environmental Protection Agency s emission limits New Source 2020 ASTM E3053 2017 and EPA Alternate Test Method ATM 125 for cordwood Under specific test conditions this heater has been shown to deliver heat at rates ranging from 16 700 to 71 300 Btu hr capable of heating approximately ...

Страница 2: ... heater design specifications can result in permanent damage to the heater A glowing stove or connector pipe is hazardous HEARTH PROTECTION Floor protection and or hearth extension is required for the Sierra Stove All floor protection materials must be non combustible i e metals brick stone mineral fiber boards etc Floor protector must be a 1 2 minimum thickness non combustible material having an ...

Страница 3: ...ve door and bottom air control The fire should die down once deprived of oxygen If the fire doesn t die call the fire department for assistance CAUTION In airtight stoves after closing the bottom air control volatile gases are still given off by the wood smoldering in the firebox A sudden burst of oxygen caused by opening the draft control or door while stove is smoldering will ignite the volatile...

Страница 4: ...placed before using 7 The chimney should be the proper size Some fireplace chimneys are quite large and will cause poor stove performance and excessive creosote The rule of thumb is that the chimney flue should be roughly no more than three times the flue opening on the stove A 6 inch stove flue will work in an 8 inch by 12 inch fireplace flue It may be necessary to install another liner in an ove...

Страница 5: ...e thickness with a ventilated thimble minimum 24 gauge in thickness having two 1 inch air channels separated from combustibles by a minimum of 6 inch of glass fiber insulation Opening shall be covered and thimble supported with a sheet steel support minimum 24 gauge in thickness D Solid insulated listed factory build chimney length with an inside diameter 2 inch larger than the chimney connector a...

Страница 6: ...tween the stove and an approved chimney but never as the chimney itself To minimize creosote formation in the chimney connector pipe place stove as close to the chimney as safety clearances will allow Never use more than two elbows Any horizontal pipe section should rise 1 4 per foot towards chimney This will allow creosote to run back into the stove Special methods are required when passing a chi...

Страница 7: ... follow this procedure 1 Convent specifications to R value a R value is given no conversion is needed b K factor is given with a required thickness T in inches R 1 k T c C factor is given R 1 C 2 Determine the R value of the proposed alternate floor protector a Use the formula in step 1 to convert values not expressed as R b For multiple layers add R values of each layer to determine the overall R...

Страница 8: ...tion or sections of stove connector pipe that connect the stove flue outlet to the fireplace chimney Method I is normally used and is generally the easiest to install Method II may be used in chimneys that need a new flue liner 8887 There are qualified installers in most areas that can install your stove for you Sierra recommends that you contact the National Chimney Sweep Guild for a member in yo...

Страница 9: ...a 30 minimum clearance between mantel and stove top If less clearance is needed there are approved mantel shield kits available so check with your Sierra dealer 6 The Sierra Fireplace Cover Kit FPCK may be used to enhance the looks of the hearthstove installation but it is not required with the direct connection method of installation Instructions for installation are supplied with this kit THE FP...

Страница 10: ...ur stove has a blower do not run the electrical cord in front or near the fire box V USING A CATALYTIC COMBUSTOR Definition and Purpose of a Catalytic Combustor Catalytic combustors for woodstoves cats are simular in principle to catalytic converters on automobiles The big difference is that the heat generated by your woodstove is put to use heating your home instead of being dumped out the tailpi...

Страница 11: ... firebox heat and coal bed for the large long burn load Kindling Made from small pieces diameter and 6 12 long A hatchet works well for splitting a small piece of cord wood length wise You ll need about 4 lbs of kindling to heat up the flue and start a small draft Starting Load Made up of 2 diameter pieces 12 16 long You ll need about 6 lbs of start up fuel to build the coal bed and warm up the st...

Страница 12: ...the bottom of the firebox This allows the air to get under the fire better 3a High Altitude Starting Instructions Follow all steps above l through 3 however due to the decreased density of oxygen supplied in a given volume of air at higher elevations it will be necessary to allow the stove to burn for a longer period of time with the air control rod pulled all the way out It may also be necessary ...

Страница 13: ...t or oxygen present in the stove this wet and steamy smoke does not ignite and burn Instead it is drawn through the exhaust vent and into the chimney As this steam begins to cool down in the flue it condenses as droplets of moisture on the inside walls of the chimney This becomes creosote which is flammable and is the fuel which burns in a flue fire It is necessary to periodically clean these depo...

Страница 14: ...re 4 If you do have a chimney fire call the fire department immediately Only then attempt to control the fire Throw soda on the logs close the draft regulators completely to shut off air to the fire Wet down your roof and adjacent areas to keep the fire from spreading 5 If you must use green wood and we urge you to avoid doinf so be sure to mix with dry logs Glass In the event that you need to cle...

Страница 15: ...od Stove notify your nearest dealer or contact Sierra Products Inc at www sierraproductsinc net customer support technical service Sierra Products Inc 63 Laxalt Dr Carson City NV 89706 www sierraproductsinc net P N 140821r2 S8000II WOOD STOVE MANUAL 15 ...

Страница 16: ...service center SPI may require the consumer to supply reasonable proof of the stoves purchase date This warranty is in lieu of any other express warranty Any implied warranties including but not limited to any implied warranty of merchantability or fitness for a particular purpose shall not extend beyond one year from the date of purchase The purchaser s sale and exclusive remedy shall be for the ...

Отзывы: