1.0 Product Description 

1.1  Introduction 

 

The Model 2102 is a dual Channel Gas 
Alarm Panel housed in a NEMA 12, JIC 
type enclosure. The unit provides DC 
power for two SMC fixed installation 
gas monitors of the 200x or 20x series 
and also provides tow individual relays 
for activation of remote devices such as 
alarms, lights or fans. LED indicator on 
the front of the panel provides visual 
indication of the  “SAFE” or “ALARM” 
status of each monitor. 

 
Once installed the Model 2102 requires 
no maintenance. The monitors require 
periodic calibration as explained in their 
respective instruction manuals. 

The unit shipped with the power supply 
set for installations up to 500 feet from 
the Alarm Panel using 22-AWG cable. 
Longer cable installations (see 
specifications) can be accomplished by 
adjustment of the power supply voltage. 

 

 

Figure 0 Outline Drawing 

Содержание Gas Alarm Panel 2102

Страница 1: ...Model 2102 Gas Alarm Panel...

Страница 2: ...This manual provides instructions for the following Sierra Monitor products Model Description 2102 00 Alarm Panel 2 Channel 2102 01 Alarm Panel 2 Channel with audible Sierra Monitor Corporation 1991 T...

Страница 3: ...2102 Alarm Panel Table of Contents Table of Contents 1 0 Product Description 1 1 1 Introduction 1 1 2 Configuration 2 2 0 Operation 2 2 1 Installation 2 3 0 Specifications 4 4 0 Warranty 5...

Страница 4: ...such as alarms lights or fans LED indicator on the front of the panel provides visual indication of the SAFE or ALARM status of each monitor Once installed the Model 2102 requires no maintenance The...

Страница 5: ...able 1 for wire gauge requirements The normal SMC color coding is green red black white CABLE LENGTH GAUGE CONDUCTORS 500 feet 22 AWG 4 1 000 feet 18 AWG 4 1 500 feet 16 AWG 4 Table 1 Sensor Cable Req...

Страница 6: ...soon as the supply AC is turned ON Be sure that all sensor and relay connections are completed prior to power on When power is connected both channels will go into warm up mode as described in the ga...

Страница 7: ...ing Temperature 320 F to 1130 F 00 C to 450 C Input Power 120 VAC 50 60 Hz 240 VAC available Fuse Ampere Size 8 3 x 8 3 x 4 4 in HWD 20 0 x 20 0 x 10 0 cm Output Voltage 9 13 VDC Adjustable Output Cur...

Страница 8: ...ntification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables ie calibration gases batteries sensors nor to any damage resulti...

Отзывы: