background image

   

 

 

 

 

2102 Alarm Panel 

 

 

 

Page 

 

2102 Alarm Panel 

1.2  Configuration 

 

The Model 2102 is available with or 
without a built in audible alarm  at the 
controller: 
Model 2102-00:   Standard Controller. 
Model 2102-01: Controller with audible 
alarm annunciator (common to both gas 
monitors) installed in the enclosure door. 
 
The standard controller is provided with 
the relays configured for separate 
activation by their respective gas 

monitors. (i.e.: Monitor #1 activates 
relay #1 and sensor #2 activates relay 
#2). 
 
On request, the factory installs a jumper 
wire to re-configure the relays to activate 
on an “or” basis so that when either 
sensor alarms both relays energize. This 
jumper is indicates in the locator 
diagram and van be field installed by a 
technician.

 

2.0 Operation 

2.1  Installation 

 

Determine suitable locations for the 
Model 2102 and the fixed gas monitors. 
Mount the panel at eye level using the 
mounting flanges on the top and bottom 
of the enclosure. Install ¾” electrical 
conduit from the right hand tub to the 
monitor locations. For installation 
convenience the wiring for both sensors 
can be run in the same conduit 
necessary. Pull four conductors for each 
monitor. See Table 1 for wire gauge 
requirements. The normal SMC color 
coding is green, red, black, white. 
 

CABLE 

LENGTH 

GAUGE 

CONDUCTORS 

500 feet 

22 AWG 

1,000 feet 

18 AWG 

1,500 feet 

16 AWG 

Table 1 Sensor Cable Requirements 

 

Connect these wires to the terminal strip 
in the gas monitor and to the 
corresponding terminal in the gas 
monitor and to the corresponding 
terminal in the Central Panel. The four 
terminal barrier strips in the Model 2102 
are marked “SENSOR 1” and “SENSOR 
2” to correspond with the lights for 
Channels “1” and “2” on the front panel. 

Model 2102 connections as indicated in 
Table 2. 

 

TERMINAL 

PIN 

COLOR 

FUNCTION 

Green 

Safe Signal 

Red 

+DC Voltage 

Black 

DC Common 

White 

Alarm Signal 

Table 2 Model 2102 Terminations 

 

Connect to the appropriate terminal strip 
pin # (as marked) in the fixed gas 
monitor. 
 
CAUTION: The terminal strip positions 
in the gas monitor are marked with the 
correct numbers as they are not in 
logical sequence, insure that the wires 
are installed in the correspondingly 
numbered positions, not in logical 
sequence. 
 
Connect ¾” conduit to the left hub of the 
enclosure to run 120 VAC power wiring 
to connect externally operated alarms, 
lights or fans to the relay terminal strips 
as required. 
 
The relay terminal strips are identified as 
“J2” corresponding to Cannel 1 and “J3” 
corresponding to Channel 2. The 
connections can be used as follows: 
 

Содержание Gas Alarm Panel 2102

Страница 1: ...Model 2102 Gas Alarm Panel...

Страница 2: ...This manual provides instructions for the following Sierra Monitor products Model Description 2102 00 Alarm Panel 2 Channel 2102 01 Alarm Panel 2 Channel with audible Sierra Monitor Corporation 1991 T...

Страница 3: ...2102 Alarm Panel Table of Contents Table of Contents 1 0 Product Description 1 1 1 Introduction 1 1 2 Configuration 2 2 0 Operation 2 2 1 Installation 2 3 0 Specifications 4 4 0 Warranty 5...

Страница 4: ...such as alarms lights or fans LED indicator on the front of the panel provides visual indication of the SAFE or ALARM status of each monitor Once installed the Model 2102 requires no maintenance The...

Страница 5: ...able 1 for wire gauge requirements The normal SMC color coding is green red black white CABLE LENGTH GAUGE CONDUCTORS 500 feet 22 AWG 4 1 000 feet 18 AWG 4 1 500 feet 16 AWG 4 Table 1 Sensor Cable Req...

Страница 6: ...soon as the supply AC is turned ON Be sure that all sensor and relay connections are completed prior to power on When power is connected both channels will go into warm up mode as described in the ga...

Страница 7: ...ing Temperature 320 F to 1130 F 00 C to 450 C Input Power 120 VAC 50 60 Hz 240 VAC available Fuse Ampere Size 8 3 x 8 3 x 4 4 in HWD 20 0 x 20 0 x 10 0 cm Output Voltage 9 13 VDC Adjustable Output Cur...

Страница 8: ...ntification marks have been removed or altered This Limited Warranty also will not apply to interconnecting cables or wires consumables ie calibration gases batteries sensors nor to any damage resulti...

Отзывы: