ELECTRICAL RATINGS

Input Power

24V Back Plane Current

0mA

24V Screw Terminal Current

180W

90W
45W

9.5A
4.9A
2.7A

6.2V Back Plane Current

0mA

24V Standby Current

300mA

Maximum Output Power

25 VRMS

150W

70 VRMS

180W

100 VRMS

165W

Dry Contact Input

24V/10mA power limited

For CE applications in Cerberus E100 systems refer to

Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German)

Содержание ZAM-180

Страница 1: ...0 amplifiers in a 1 to 1 backup or 1 to many backup The ZAM 180 also contains a local external audio input circuit 0 dB and a dry contact input to switch on the amplifier and activate the zones as configured via the Zeus tool The ZAM 180 is capable of amplifying any one of the 8 audio channels that are transmitted from the DAC NET Digital Audio Card via the internal digital Audio bus ASI Audio Ser...

Страница 2: ...input is isolated on the ZAM 180 to prevent ground loops The local audio input is activated via an external contact The control of this input will be executed by the amplifier directly The ZAM 180 will send a message informing the DAC NET that the ZAM 180 has turned on the local input It is also possible to activate deactivate the local input on the control panel via CAN bus The speaker lines are ...

Страница 3: ... zone trouble open circuit or short circuit Check wires to the speakers EOL resistor s and de coupling capacitors on every speaker ZONE GND FAULT yellow OFF ON unwanted earth ground connection on a speaker line Check wires to the speakers for earth ground connections OVERLOAD Yellow OFF ON Refers to Local Audio input only Press DOWN push button until OVERLOAD LED turns off and NORMAL LED turns on ...

Страница 4: ...tary switches on the front panel refer to Figure 2 Remove screws as shown in Figure 3 on the left and the right side of the ZAM 180 housing and remove the front plate Figure 3 Position Of The Securing Screws For setting the speaker line voltage and the low frequency cutoff see Figure 4 Figure 4 Position of Connectors X4 X36 and X35 and Jumpers X28 and X21 ...

Страница 5: ...n is configured with jumpers on header X28 Speaker Line Voltage 100V Plug in the coded connector on connector terminal X35 and set jumper X28 position 1 2 Figure 5 Jumper Position 100V Speaker Line Voltage 70V Plug in the coded connector on connector terminal X36 and set Jumper X28 position 2 3 Figure 6 Jumper Position 70V Speaker Line Voltage 25V Plug in the coded connector on connector terminal ...

Страница 6: ...uency cut off two jumpers have to be set Never set only one jumper Figure 9 Jumper Position 240 Hz After having done these pre installations install the front plate and secure it again INSTALLATION Remove ELECTRICAL POWER prior to working on equipment The ZAM 180 mounts on the Mounting Plate CAB MP The Mounting Plate may be located either IN or OUT of the enclosure to perform this installation pro...

Страница 7: ...Plate and the mounting screw holes of the PSC 12 will align with the threaded posts Figure 11 Mounting the ZAM 180 On The CAP MP 1 Install four 10 32 M5 screws in the threaded posts at the mounting position Screw each of the 10 32 M5 screws into the threaded posts 5 6 turns 2 Place the ZAM 180 over the four screws on the Mounting Plate and slide it down or towards you to rest on the four screws Re...

Страница 8: ...nal by turning it counterclockwise Insert the wire into the side of the terminal block Tighten the screw of the terminal block by turning it clockwise Power Input 24VDC 9 5A Max Non Power Limited Output 24VDC 12A 24V 24V 0V 0V Loc Audio IN A 1 3 5 7 2 4 6 8 9 11 13 15 10 12 14 16 Back Up Amp B Back Up Amp A Speaker Line 1A Speaker Line 1B Speaker Line 2A Speaker Line 2B Loc Switch A Earth ground E...

Страница 9: ...in 20 feet and in rigid conduit NOTES Speaker Lines and Backup Amplifier 1 Wiring can be Class A or Class B 2 Use twisted pair or shielded twisted pair 3 Terminate shields at one end only 4 Supervised and not power limited NOTES Local Switch 1 24AWG Ø 0 5mm min 12AWG 2 5mm max 2 Use twisted pair or shielded twisted pair 3 Terminate shields at one end only 4 Must be within 20 feet and in rigid cond...

Страница 10: ... B 2 Use twisted pair or shielded twisted pair 3 Terminate shields at one end only 4 Supervised and not power limited NOTES Local Switch 1 24AWG Ø 0 5mm min 12 AWG 2 5mm max 2 Use twisted pair or shielded twisted pair 3 Terminate shields at one end only 4 Must be within 20 feet and in rigid conduit 5 Connect to dry contacts only Loc Audio IN A 1 3 5 7 2 4 6 8 9 11 13 15 10 12 14 16 Back Up Amp B B...

Страница 11: ...24235 A1 K13 DE EOL 68k P N 140 034728 US CA C24235 A1 K13 DE shipped with the ZAM 180 In Canada mount using Model EL 33 NOTES Local Switch 1 24AWG Ø 0 5mm min 12 AWG 2 5mm max 2 Use twisted pair or shielded twisted pair 3 Terminate shields at one end only 4 Must be within 20 feet and in rigid conduit 5 Connect to dry contacts only NOTES Speaker Lines and Backup Amplifier 1 Wiring can be Class A o...

Страница 12: ...4205 A334 B832 Edition 1 P N 315 035600 2 Printed in the Federal Republic of Germany on environmental chlorine free paper ELECTRICAL RATINGS Input Power 24V Back Plane Current 0mA 24V Screw Terminal Current 180W 90W 45W 9 5A 4 9A 2 7A 6 2V Back Plane Current 0mA 24V Standby Current 300mA Maximum Output Power 25 VRMS 150W 70 VRMS 180W 100 VRMS 165W Dry Contact Input 24V 10mA power limited For CE ap...