4.3 End Closer Instructions (XE100, XE200, XE400)

4.3.1

Remove external housing connectors if present.  Loosen last 

housing screws on top and bottom of duct.  Slip end closer over        
duct, engaging loosened screws.  Tighten screws to retain end 
closer.  

(See Figure 5)

Figure 5

X100, X200

X400

5.0 XJ-L Bus Plug Installation and Removal Instructions

5.1 General Information

5.1.1

XJ-L Bus plugs are available with molded case circuit breakers or Vacu-Break® fusible switches. Bus plugs may be 

operated with a pull-chain or hookstick from the floor. Lightweight and portable, plugs are easily moved from one 
location to another. Captive hardware allows for easy removal and re-installation. 

5.1.2

The bus plug contact fingers are lubricated with an oxide inhibiting grease at the factory. This grease should not be 

removed.

5.1.3 Types of XJ-L Bus Plugs:

XQ Series

XQ-R Series

XEC Series

3 Cir. XPM Series

6 Cir. XPM Series

XLEC Series

XLVB Series

Содержание XJ-L Busway System

Страница 1: ...XJ L Busway Systems Storage Installation and Maintenance Instructions for Piece No 32 J 1010 01 Rev 5 SIEMENS XJ L Busway System ...

Страница 2: ...ect busway components for possible concealed damage from shipping and or handling If damage has occurred file a claim with the carrier If there is no damage restore the packing to its original condition to prepare for job site storage Store busway indoors in a clean and dry area Protect against mechanical damage and exposure to lime dust concrete water corrosive fumes or liquids and salts Failure ...

Страница 3: ...pply pressure to either side of the assembly left hand and then right hand until fully seated 4 0 1 7 Close joint inspection cover and secure it with provided hardware The joint is now complete 4 1 Hanger Instructions XH2 XH3 4 1 1 TO HANG XJ L BUSWAY FROM DROP RODS 4 1 1 1 Position drop rods as required Max 10 Spacing 4 1 1 2 Using a double nut configuration assemble the hanger halves to each dro...

Страница 4: ... 1 1 XJ L Bus plugs are available with molded case circuit breakers or Vacu Break fusible switches Bus plugs may be operated with a pull chain or hookstick from the floor Lightweight and portable plugs are easily moved from one location to another Captive hardware allows for easy removal and re installation 5 1 2 The bus plug contact fingers are lubricated with an oxide inhibiting grease at the fa...

Страница 5: ... busway 5 2 5 Guide the bus plug into the outlet opening ensuring that the bus plug alignment finger and bus plug conductor fingers enter their corresponding openings in the outlet 5 2 6 Push the bus plug firmly into the busway plug in outlet 5 2 7 Make sure the bus plug is fully seated on the busway housing and then tighten all mounting screws 5 2 8 6 and 12 circuit XPMs are provided with drop ro...

Страница 6: ...SE PROCEDURES DO NOT REPRESENT AN EXHAUSTIVE SURVEY OF MAINTENANCE STEPS NECESSARY TO ENSURE SAFE OPERATION OF THE EQUIPMENT PARTICULAR APPLICATIONS MAY REQUIRE ADDITIONAL PROCEDURES SHOULD ADDI TIONAL INFORMATION BE DESIRED OR SHOULD PARTICULAR PROBLEMS ARISE WHICH ARE NOT COVERED SUFFICIENTLY FOR THE PURCHASER S PURPOSES THE MATTER SHOULD BE REFERRED TO THE LOCAL SIEMENS SALES OFFICE OR CALL 1 8...

Отзывы: