SOFTWARE UPDATES
6-5
SIG-QG-20-02
JANUARY 2021
Version : A.2
The WebUI will ask the user to confirm that there is a serial cable connected between the display and
module to be uploaded. If the cable is connected, press
OK
to continue.
Figure 6-7 WebUI Module Upload
The display module will then transfer the load setup code to the module to be updated and provide a
menu of options.
6.1.3 Reset VLP Module
This menu is used to reset the VLP module. This may be necessary if an attempt has been made to load
a new configuration and the process cancelled before complete. Unlock the screen as described in
section 6.1.5.1, then press the
Reset VLP
button and the WebUI will ask for confirmation first.
Figure 6-8 WebUI Reset VLP
Содержание WEBUI
Страница 16: ...CONNECTING TO THE WEBUI 1 16 SIG QG 20 02 JANUARY 2021 Version A 2 This page intentionally left blank ...
Страница 30: ...SYSTEM VIEW 2 14 SIG QG 20 02 JANUARY 2021 Version A 2 This page intentionally left blank ...
Страница 33: ...CONFIGURATION 3 3 SIG QG 20 02 JANUARY 2021 Version A 2 Figure 3 3 WebUI Site Configuration GCP 5000 ...
Страница 40: ...CONFIGURATION 3 10 SIG QG 20 02 JANUARY 2021 Version A 2 This page intentionally left blank ...
Страница 44: ...CALIBRATION ADJUSTMENT 4 14 SIG QG 20 02 JANUARY 2021 Version A 2 This page intentionally left blank ...
Страница 68: ...SOFTWARE UPDATES 6 12 SIG QG 20 02 JANUARY 2021 Version A 2 This page intentionally left blank ...
Страница 72: ...CPU III WEBUI 8 2 SIG QG 20 02 JANUARY 2021 Version A 2 This page intentionally left blank ...