WIRING

Refer to Figure 4

All wiring must comply with national

and local codes.

1. If VSM-1/VLM-1 and/or VFM-1 modules are

present, open the MHD panels so that you are

looking at the back of the VSM-1s, the VLM-

1s, the VFM-1s and the VSB-1s.

2. Start with the first VSA-1 module in the

connection chain. (The first VSA-1 is usually

located in the top left corner of the custom

annunciator backbox.)

3. Connect P1 of the last module to P2 of the

first VSA-1 module, using the 40-inch cable

model MRRC-1, P/N 500-692531, which is

ordered separately.

4. Connect P1 of the first VSA-1 module to P2 of

the next VSA-1 to its right, using the 4-inch

cable, P/N 600-192237, which is supplied.

Continue in the same manner until all of the

VSA-1 modules are connected (Refer to

Figure 4). Use the MRRC-1 to start a new row

of VSA-1 modules, if required.

5.

With an MMB or PSR:

Connect P2 of the first VSA-1 module at the

far left in the top row to P4 of the TBM-2

Termination Block module, using the 3-foot

cable supplied with the TBM-2, P/N 600-

192258.

 

The cables are polarized; do not

force them.

NOTE:

 The TBM-2 module is located in the

enclosure on the right side next to the

MMB-2 or the PSR-1. 

For more

details, refer to the MXLV Manual,

P/N 315-092036.

In a Remote Extender enclosure with a

PS-5N7 used instead of an MMB or PSR:

Connect P2 of the first VSA-1 module at the

far left in the top row to P4 of the TBM-2,

using the 3-foot cable, P/N 600-192258,

which is supplied with the TBM-2.

 

The cables

are polarized; do not force them.

NOTE:

The TBM-2 module is located in the

enclosure on the right side beneath

the PS-5N7. 

For more details, refer

to the PS-5N7 Instructions, P/N

315-092729.

6. Route the cable wires across the hinge to the

back of the enclosure. Do not fasten the cable

with a cable anchor until all wiring is complete.

ELECTRICAL RATINGS

VSA-1: 24 VDC, 160mA
Recommended LEDs:

Bi-color (Green/Red):

DC forward current – 25mA (max)

King Bright L59EGW or equivalent

Yellow :

DC forward current – 40mA (max)

Siemens LY5360HL or equivalent

Figure 3

VSA-1 Pin Assignments

Содержание VSA-1

Страница 1: ...s All Call All Alarm EVAC Warden s Page and Local Speaker The switch use and zone groupings are assigned in CSG M The VSA 1 module may provide LED annuncia tion of system activity when the switch and LED pair are programmed as generic Each VSA 1 module contains 8 sets of 2 LEDs in three different colors to indicate a variety of system information such as zone trouble or alarm In each set the top L...

Страница 2: ... 0 0 X X 0 0 28 0 X X X 0 0 13 0 0 X X 0 X 29 0 X X X 0 X 14 0 0 X X X 0 30 0 X X X X 0 15 0 0 X X X X 31 0 X X X X X NOTE To open a dipswitch press down on the side of the dip switch marked OPEN To close a dipswitch press down on the side of the dipswitch opposite the side marked OPEN To open a slide switch push the slide to the side opposite the side marked ON To close a slide switch push the sl...

Страница 3: ... to P4 of the TBM 2 Termination Block module using the 3 foot cable supplied with the TBM 2 P N 600 192258 The cables are polarized do not force them NOTE The TBM 2 module is located in the enclosure on the right side next to the MMB 2 or the PSR 1 For more details refer to the MXLV Manual P N 315 092036 In a Remote Extender enclosure with a PS 5N7 used instead of an MMB or PSR Connect P2 of the f...

Страница 4: ... supplied with the TBM 2 2 The custom annunciator manufacturer should use 12 position female connectors such as AMP No 1 640440 2 Hood for connector is AMP No 1 640550 2 key for connector is AMP No 641994 1 The hood and key are the same as those used for connection to the MID 16 module Two keys should be inserted at slots 1 and 12 of the female connector leaving 10 slots for connection to the VSA ...

Отзывы: