Siemens VSA-1 Скачать руководство пользователя страница 2

2

X = SWITCH CLOSED OR 

ON

, O = SWITCH OPEN OR 

OFF

INSTALLATION

Remove all system power before

installation, battery first and then AC.

(To power up, connect the AC first

and then the battery.)

1. Remove the card from its protective bag.
2. Refer to the function section of the CSG-M

configuration printout for the address of the

VSM-1 module that is used for the VSA-1.

3. Set the module address for the VSA-1 on

switch S1 using dipswitches SW1-SW6.
a. Refer to Figure 1 for the location of S1 on

the module.

b. Refer to Table 1 for the correct switch

settings.

c. Set the address (See Note below).

Figure 2

Mounting the VSA-1

TABLE 1

ADDRESS 6 5 4 3 2 1 ADDRESS 6 5 4 3 2 1

ILLEGAL

0 0 0 0 0 0

16

0 X 0 0 0 0

1

0 0 0 0 0 X

17

0 X 0 0 0 X

2

0 0 0 0 X 0

18

0 X 0 0 X 0

3

0 0 0 0 X X

19

0 X 0 0 X X

4

0 0 0 X 0 0

20

0 X 0 X 0 0

5

0 0 0 X 0 X

21

0 X 0 X 0 X

6

0 0 0 X X 0

22

0 X 0 X X 0

7

0 0 0 X X X

23

0 X 0 X X X

8

0 0 X 0 0 0

24

0 X X 0 0 0

9

0 0 X 0 0 X

25

0 X X 0 0 X

10

0 0 X 0 X 0

26

0 X X 0 X 0

11

0 0 X 0 X X

27

0 X X 0 X X

12

0 0 X X 0 0

28

0 X X X 0 0

13

0 0 X X 0 X

29

0 X X X 0 X

14

0 0 X X X 0

30

0 X X X X 0

15

0 0 X X X X

31

0 X X X X X

NOTE:

To open a dipswitch, 

press down on the side of the dip-

switch marked OPEN. To close a dipswitch, press down on

the side of the dipswitch opposite the side marked OPEN.

To open a slide switch, 

push the slide to the side opposite the

side marked ON. To close a slide switch, push the slide to the

side marked ON.

MOUNTING

Refer to Figure 2

Before mounting each VSA-1 module, check the

labels and the address setting of S1 on the front

of the module.
1. With the custom annunciator backbox open,

mount the snaptrack to the back of the box

using the double-sided tape. Take care to

mount the snaptrack carefully as it is difficult to

remove the snaptrack once it is in place.

2. Female header connectors should be pre-

wired and assigned to modules by the

custom annunciator manufacturer as shown in

Figure 3.

3. Mount the VSA-1 module on its correspond-ing

snap track by pushing it firmly into place.

Connect the female pin header connector as

assigned by the custom annunciator

manufacturer.

4. VSA-1 modules do not need to be mounted in

numeric order by address. (Refer to the

custom annunciator placement layout.)

Содержание VSA-1

Страница 1: ...s All Call All Alarm EVAC Warden s Page and Local Speaker The switch use and zone groupings are assigned in CSG M The VSA 1 module may provide LED annuncia tion of system activity when the switch and LED pair are programmed as generic Each VSA 1 module contains 8 sets of 2 LEDs in three different colors to indicate a variety of system information such as zone trouble or alarm In each set the top L...

Страница 2: ... 0 0 X X 0 0 28 0 X X X 0 0 13 0 0 X X 0 X 29 0 X X X 0 X 14 0 0 X X X 0 30 0 X X X X 0 15 0 0 X X X X 31 0 X X X X X NOTE To open a dipswitch press down on the side of the dip switch marked OPEN To close a dipswitch press down on the side of the dipswitch opposite the side marked OPEN To open a slide switch push the slide to the side opposite the side marked ON To close a slide switch push the sl...

Страница 3: ... to P4 of the TBM 2 Termination Block module using the 3 foot cable supplied with the TBM 2 P N 600 192258 The cables are polarized do not force them NOTE The TBM 2 module is located in the enclosure on the right side next to the MMB 2 or the PSR 1 For more details refer to the MXLV Manual P N 315 092036 In a Remote Extender enclosure with a PS 5N7 used instead of an MMB or PSR Connect P2 of the f...

Страница 4: ... supplied with the TBM 2 2 The custom annunciator manufacturer should use 12 position female connectors such as AMP No 1 640440 2 Hood for connector is AMP No 1 640550 2 key for connector is AMP No 641994 1 The hood and key are the same as those used for connection to the MID 16 module Two keys should be inserted at slots 1 and 12 of the female connector leaving 10 slots for connection to the VSA ...