Installation  Instructions

Model  VSA-1

Visual Switch Annunciator Module

P/N 315-096072-4

INTRODUCTION

The 

SIEMENS

 Model VSA-1 Visual Switch

Annunciator module provides the system

operator with manual control and annunciation

of the MXLV System functions on a custom

graphic annunciator panel. Each VSA-1 has pin

headers for 8 push-button switches with func-

tions assigned to them in the CSG-M; each

push-button switch has pin headers for 2 LEDs

to indicate the function status, for a total of 16

LEDs. (See Figure 1.)
The VSA-1 is used to manually select speaker,

telephone, or strobe zones, as well as a wide

range of general system functions, such as All

Call, All Alarm/EVAC, Warden’s Page, and

Local Speaker. The switch use and zone

groupings are assigned in CSG-M.
The VSA-1 module may provide LED annuncia-

tion of system activity when the switch and LED

pair are programmed as generic. Each VSA-1

module contains 8 sets of 2 LEDs in three

different colors to indicate a variety of system

information, such as zone trouble or alarm. In

each set, the top LED can light red or green;

the bottom LED is yellow.
The VSA-1 provides all the functionality of a

VSM-1 module, and is defined as a VSM-1

module in the CSG-M.

For more information on the Voice System,

refer to the MXLV Manual, P/N 315-092036.

Figure 1

VSA-1 Module Board

Fire Safety

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario L6T 5E4 CN

Содержание VSA-1

Страница 1: ...s All Call All Alarm EVAC Warden s Page and Local Speaker The switch use and zone groupings are assigned in CSG M The VSA 1 module may provide LED annuncia tion of system activity when the switch and LED pair are programmed as generic Each VSA 1 module contains 8 sets of 2 LEDs in three different colors to indicate a variety of system information such as zone trouble or alarm In each set the top L...

Страница 2: ... 0 0 X X 0 0 28 0 X X X 0 0 13 0 0 X X 0 X 29 0 X X X 0 X 14 0 0 X X X 0 30 0 X X X X 0 15 0 0 X X X X 31 0 X X X X X NOTE To open a dipswitch press down on the side of the dip switch marked OPEN To close a dipswitch press down on the side of the dipswitch opposite the side marked OPEN To open a slide switch push the slide to the side opposite the side marked ON To close a slide switch push the sl...

Страница 3: ... to P4 of the TBM 2 Termination Block module using the 3 foot cable supplied with the TBM 2 P N 600 192258 The cables are polarized do not force them NOTE The TBM 2 module is located in the enclosure on the right side next to the MMB 2 or the PSR 1 For more details refer to the MXLV Manual P N 315 092036 In a Remote Extender enclosure with a PS 5N7 used instead of an MMB or PSR Connect P2 of the f...

Страница 4: ... supplied with the TBM 2 2 The custom annunciator manufacturer should use 12 position female connectors such as AMP No 1 640440 2 Hood for connector is AMP No 1 640550 2 key for connector is AMP No 641994 1 The hood and key are the same as those used for connection to the MID 16 module Two keys should be inserted at slots 1 and 12 of the female connector leaving 10 slots for connection to the VSA ...

Отзывы: