GAMMA
instabus
Technical Specification
March 2010
Colour touch panel UP 588/13
5WG1 588-2AB13
Colour touch panel UP 588/23
5WG1 588-2AB23
Accessories:
Design frame aluminium
5WG1 588-8AB12
Design frame stainless steel design
5WG1 588-8AB13
Design frame glass black
5WG1 588-8AB14
Design frame glass white
5WG1 588-8AB15
flush-type box
5WG1 588-8EB01
Technical Manual
UP 588, 6 pages
Siemens AG
Industry Sector, Building Technologies
Update: http://www.siemens.com/gamma
© Siemens AG 2010
Low Voltage Distribution
Subject to change without further notice
PO Box 10 09 53, D-93009 Regensburg
2.3.1.7/2
•
The depth of the recess must be at least 64 mm.
Figure 1:
Drilling jig for cavity wall box Colour
touchpanel UP 588
V
DANGER
•
The device may only be installed and commissioned by
an authorised electrician.
•
The device may only be used in connection with the
named accessories, in particular the flush-type box.
•
230V devices which are not included with supply may
not be inserted in the flush-type box. It is also not
possible to loop through 230V cables.
•
The prevailing safety and accident regulations should
be observed.
•
The power supply voltage may only be connected to
the supply if the device has been fully installed.
•
Protective isolation should be ensured between the
bus cable and the 230V power supply.
•
For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.
Technical specifications
Power supplies
•
Bus voltage: via the bus line
•
External power supply for:
•
Colour Touch panel UP 588/13
230 V AC ±10%, 50/60 Hz
•
Colour Touch panel UP 588/23
18 – 36 V DC, 400 mA, base isolated comp. 230 V
14 – 28 V AC, 400 mA, base isolated comp. 230 V
Operating elements
•
Programming button to toggle between normal and
addressing modes
•
Reset button to reset the device
•
Resistive analogue touch with contact-sensitive area on
the display
Display elements
•
Red programming LED for displaying normal/addressing
mode
•
Graphics-capable TFT colour display 320 × 240 pixels
(1/4 VGA) with LED background lighting
•
Display fault like ISO 13406-2 fault league 3 by error
type 1 and error type 2
Connections
•
Bus line: KNX bus terminal, screwless
0.6... 0.8 mm
∅
solid, stripped length 5 mm.
•
USB socket mini typ B (use only if needed for image
and symbols load)
•
Power supply
stripped length: 6...7 mm
The following conductor/conductor cross-sections are
permitted:
-
0.5...2.5 mm
2
solid
-
0.5..0.1.5 mm
2
finely-stranded
Mechanical data
•
Housing: Touch panel: plastic
•
Outer dimensions of the display modul (W x H x D):
157 x 131 x 60 mm
•
Outer dimensions of the design frames (W × H × D):
194 × 156 × 5 mm
•
Outer dimensions of the passepartout blind (W × H):
152 × 123 mm
•
Mounting depth in flash-type box: 64 mm
•
Installation: is screwed into the corresponding flush-
type box