58 / 94
Siemens
TX-I/O PROFINET BIM V1.0
CM110564en_02
Building Technologies
Parameters
23.09.2010
Note
Before you activate the synchronization after a reset, set the position in the
positioning model to 0 %.
Recommendation: NONE – no synchronization
Every other configuration can cause unpredictable drive actions (valve, damper
drives).
4.12.7 LimitSynchronization
Parameter for defining the behavior of the synchronization if
[AOValue] reaches a final position (0% or 100%)
and
the positioning model is within ([neutral zone]/2 + hysteresis) – i.e., the
positioning model considers the drive as fully open or fully closed.
The synchronization is interrupted if [AOValue] changes to a value
> 0% + [NeutralZone]/2 + hysteresis
or
< 100% – ([NeutralZone]/2 + hysteresis).
Possible values
Description
NONE No
synchronization
CONTINUOUS
Continuous synchronization (0% and 100%)
SINGLE
Synchronization for 1.5
[rise time] (100%)
or
1.5
[fall time] (0%)
EVERY10MIN
Synchronization for 1.5
[rise time] (100%)
or
1.5
[fall time] (0%) every 10 minutes
EVERY20MIN
Synchronization for 1.5
[rise time] (100%)
or
1.5
[fall time] (0%) every 20 minutes
CONTINOPEN
Continuous synchronization (100%)
SINGLEOPEN
Synchronization für 1.5
[rise time] (100%)
EVERY10MINOPEN Synchronization für 1.5
[rise time] (100%) every 10
minutes
EVERY20MINOPEN Synchronization für 1.5
[rise time] (100%) every 20
minutes
CONTINCLOSE
Continuous synchronization (0%)
SINGLECLOSE
Synchronization für 1.5
[fall time] (100%)
EVERY10MINCLOSE Synchronization für 1.5
[fall time] (100%) every 10 minutes
EVERY20MINCLOSE Synchronization für 1.5
[fall time] (100%) every 20 minutes
Recommendation: SINGLE
Every other configuration can cause unpredictable drive actions (valve, damper
drives).
4.12.8 RiseTime
Parameter for defining the open time of a valve, flap, etc.
Value range
Unit
Recommended range
63...65535
0.1 s
6.5...600 s
The open time (0 % to 100 %) can be defined within the range specified above.
Definition,
addition
Definition,
addition
Содержание TX-I/O
Страница 1: ...s TX I O TX I O PROFINET BIM V1 0 User manual CM110564en_02 23 09 2010 Building Technologies ...
Страница 90: ...90 94 Siemens TX I O PROFINET BIM V1 0 CM110564en_02 Building Technologies Hardware 23 09 2010 ...
Страница 93: ...93 94 Siemens TX I O PROFINET BIM V1 0 CM110564en_02 Building Technologies Index 23 09 2010 ...