background image

• 

Only qualified licensed electricians should install or service SPDs

• 

Hazardous voltages exist within SPDs

• 

SPDs should never be installed or serviced when energized

• 

Use appropriate safety precautions including Personal Protection Equipment

• 

Failure to follow these instructions can result in death, serious injury, and/or equipment damage.

• 

This manual shall be read in entirety prior to installing

Bonding and Grounding Hazard

Verify that the neutral conductor in the service entrance equipment is bonded to ground in accordance with the National 
Electrical Code (NEC®) and all applicable codes.

Verify that the neutral terminal (XO) on the secondary side of distribution transformers are grounded to the system ground 
in accordance with the NEC® and all applicable codes.

During installation into an electrical system the SPD must not be energized until the electrical system is completely installed, 
inspected and tested.  All conductors must be connected and functional including the neutral (if required).  The voltage 
rating of the SPD and system must be verified before energizing the SPD.

Failure to follow these guidelines can lead to abnormally high voltages at the SPD.  This may cause the SPD to fail.  The 
warranty is voided if the SPD is incorrectly installed and/or if the neutral conductor in the service entrance equipment or 
downstream of separately derived systems is not bonded to ground in accordance with the NEC®.

Do Not Hi-Pot Test SPDs

Any  factory  or  on-site  testing  of  power  distribution  equipment  that  exceeds  normal  operating  voltage  such  as  
high-potential insulation testing, or any other tests where the suppression components will be subjected to higher voltage 
than their rated Maximum Continuous Operating Voltage (MCOV) must be conducted with the SPD disconnected from the 
power source.  For 4-wire systems, the neutral connection at the SPD must also be disconnected prior to performing high-
potential testing and then reconnected after test completion.

Failure to disconnect SPD and associated components during elevated voltage testing will damage the SPD and will void 
the warranty.

WARNING -

 

Hazardous Voltage & Shock Hazard

V

Failure to Follow These Instructions Could Result in Death or Serious Injury

2

Содержание TPS3

Страница 1: ...User Manual USA TPS3 Internal Manual Surge Protective Device ...

Страница 2: ...ge rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with...

Страница 3: ...x 7 TPS3 05 and TPS3 06 Module Replacement Instructions 8 TPS3 01 and TPS3 06 Module Installation Instructions MCC 9 Operation 10 TPS3 Control and Diagnostic Display Panel 10 Display Panel with Surge Counter Option 10 Dry Contacts Feature 10 Maintenance 11 Troubleshooting Service 11 Abnormal N G Voltage Indicators 11 Module Replacement Service 11 Technical Support 12 Display Replacement 12 Prevent...

Страница 4: ...ly hazardous situation which if not avoided could result in minor or moderate injury These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the pur...

Страница 5: ...ect plug in type devices surge strips etc Theses devices are intended for installation 10 meters from the panel rationale based on IEEE Cat A location Type4 Surgesuppressioncomponents couldbeabasiccomponent or a complete module Type 4 components can be tested for Type 1 Type 2 or Type 3 applications 2008 NEC Art 285 UL 1449 3 SPD Types Types 1 2 3 4 Based on Location within electrical distribution...

Страница 6: ...rnd Fig 4 K 380Y 220V 3Ø 4W Plus Grnd Fig 2 L 600Y 347V 3Ø 4W Plus Grnd Fig 2 S 400Y 230V 3Ø 4W Plus Grnd Fig 2 AVALABLE SURGE CURRENT RATING Surge Current Rating TPS3 01 TPS3 L1 TPS3 05 TPS3 L5 TPS3 06 TPS3 L6 10 100kA per phase 15 150kA per phase 20 200kA per phase 25 250kA per phase 30 300kA per phase 40 400kA per phase 45 450kA per phase 50 500kA per phase AVAILABLE OPTIONS When Option is Not ...

Страница 7: ...etc NEC and IEEE Std 142 2007 are appropriate standards For sensitive electronics and computer systems ground impedance should be as low as possible When metallic raceway is used as an additional grounding conductor an insulated grounding conductor should be run inside the raceway and sized per the NEC Adequate electrical continuity must be maintained at all raceway connections Do not use isolatin...

Страница 8: ...n it Remove the trim and dead front Remove the two 2 deadfront supports Position the TPS3 unit on the panel base rail so that the TPS3 neutral connector is in front of the panel neutral and the phase tabs are behind the interior bus Slide the unit toward the interior until the four mounting holes line up with the four holes in the base rail Note IfaneutrallugismountedinthepositionwheretheTPS3neutr...

Страница 9: ...A single 14 wire ribbon cable is attached to the display pcb WhentheABCphasesequencechangestoCBA thesingleconnectoris removed from the normal ABC jack and installed in the jack labeled CBA Lock off all power supplying this equipment before working on it Remove the trim and dead front Install the mounting bracket Item 5 to the base rail as shown in Figure 3 using two 2 of the 10 thread forming scre...

Страница 10: ...ified for the purpose and conditions of use Additional instructions for TPS3 01 L1 SPDs including W option Suffix TheWoptionincludesrespositionedphaseconnectiontabsthatallow for wire connections to a circuit breaker within the panelboard This differs from non W models which bolts directly to bus bars The circuit breaker serves as a disconnector device and overcurrent protection to the connecting c...

Страница 11: ...isonnect Lock off all power supplying this equipment before working on it Open unit door and turn the internal disconnect to the off position Remove the neutral lug wire from the disconnect switch Remove the phase wires from the TPS3 06 unit lugs Remove the TPS3 06 unit with the panel and diagnostics display and discard properly Replace units with the new TPS3 06 units Attach the phase lug wires t...

Страница 12: ...on such that the display is visible to user and or protected via an access door A successful installation includes Meets all national and local codes Mount TPS as close as possible to electrical connection Ensure leads are as short and straight as possible Gently twist or tie wrap conductors together wherever possible Ensure that N G bonding hazard warning label is attached to TPS as reminder to i...

Страница 13: ...verysuppression elementinthisSPDismonitored N Gsuppressionelementmonitoring is logic connected to Phase A Service LED red LED illuminates in the event of problems This indicator is logic connected to the Phase LEDs Should a Phase LED go out the Service LED will illuminate and the Audible Alarm will sound Test Tests red Service LED and Audible Alarm and changes state of Dry Contacts Alarm Silence T...

Страница 14: ...round It becomes an ungrounded system Please see previous section regarding SPDs on ungrounded systems Such systems are known to eventually produce abnormally high L G voltages SPDs will attempt to chase this system level overvoltage abnormality until the SPD fails This effect is accelerated on Wye systems where SPDs are designed for grounded systems SPDs for ungrounded systems generally have high...

Страница 15: ...sealing gasket between the display and the enclosure is a key component ensuring weather resistance Replace the gasket whenever the display is removed Preventive Maintenance Inspection and Testing Inspection of the TPS3 SPD unit should be performed periodically to maintain reliable system performance and continued transient voltage surge protection The large variations in operating conditions enco...

Страница 16: ...Siemens Industry Inc Building Technologies Division 5400 Triangle Parkway Norcross GA 30092 888 333 3545 info us siemens com 8 9 10 8171 ...

Отзывы: