background image

Maintenance

SPDs require minimal maintenance.  Periodic inspection of diagnostic 
LED indicators ensures proper operation.  Clean SPD as appropriate.   

Troubleshooting & Service

Please contact TPS Technical Support at 1.888.333.3545 for service 
related issues. 

Quality  SPDs  are  designed  and  tested  to  withstand  severe  duty.  
However,  there  are  various  electrical  anomalies  against  which 
SPDs  cannot  protect.  These  are  generally  Sustained  Overvoltages 
also  known  as  Temporary  Overvoltages  (TOVs).  In  this  context, 
Sustained Overvoltages may be only a few cycles. Failed SPDs tend 
to be symptoms, not root causes.  There may be larger issues at play.  
Regardless of cause, SPDs attempt to protect their load until failure.

Bonding  or  reference  to  ground  problems  are  the  root  cause  of 
many SPD problems. If the SPD shows problems on startup, there 
is  reasonable  chance  of  bonding/grounding/misapplication  issue.  
Such problems permanently damage the SPD.  If not corrected, SPD 
problems will reoccur.  

Tip: Visually confirm N-G bonding.  Be aware that a voltmeter 
measuring N-G can be misleading.  For example, N-G voltage 
could read 0V because neutral and ground are at the same 
potential  purely  by  happenstance,  not  because  they  are 
bonded.  Visually confirm bonding.

Tip:  Experience  indicates  that  regulation-challenged 
generators  can  cause  Sustained  Overvoltages,  as  well 
as  ungrounded  generators,  and/or  usual  load  transfer 
systems.

Abnormal N-G Voltage Indicators

This SPD include N-G voltage indicators.  If the SPD detects excessive 
N-G voltage, the Red Service LED will blink and the Audible Alarm 
will cycle.  This condition requires immediate attention as the SPD 
will fail.

Incorrectly bonded distribution systems damage SPDs. If the XO or N-G 
bonding jumper is not installed, the electrical system has no reference 
to ground.  It becomes an ungrounded system.  Please see previous 
section regarding SPDs on ungrounded systems.   Such systems are 
known  to  eventually  produce  abnormally  high  L-G  voltages.  SPDs 
will attempt to chase this system-level overvoltage abnormality until 
the SPD fails. This effect is accelerated on Wye systems where SPDs 
are designed for grounded systems.  (SPDs for ungrounded systems 
generally have higher MCOV to allow for L-G voltage fluctuations.)  
Failures of this nature are not defects in the SPDs workmanship or 
material. This is an installation error and is not covered by warranty.

A  differential  voltage  circuit  monitors  neutral  to  ground  voltage.  
When  N-G  voltage  becomes  excessive,  an  amplifier  energizes  a 
resistor.  Eventually, that resistor will overheat and cause thermally 
sensitive shrink wrap to shrink around the resistor. This does not occur 
on transient  or instantaneous N-G overvoltages.  When the SPD is 
deenergized, the shrink wrap  covered resistor can be accessed by 
qualified personnel under the display plate cover. 

Module Replacement & Service

The module is field replaceable. Service should only be performed 
by  qualified  persons.  Deenergize  SPD,  confirm  with  appropriate 
measurement  equipment  and  discharge  internal  capacitance  to 
ground. Mark locations and carefully disconnect diagnostic cables, 
contacts, connecting conductors, etc.  Unbolt module from backplane.  
Reinstall in reverse.

There are no user serviceable parts inside the module. Disassembly 
is not permitted.

Modules  may  be  returned  to  the  factory  for  factory  service, 
qualification and return. Please contact factory at 1.888.333.3545 
for assistance.

CONDUCTING DIELECTRIC AND/OR 

HI-POTENTIAL TESTING WILL CAUSE

INTERNAL DAMAGE TO TPS3 UNIT.

Do not perform dielectric or high potential 

tests with the TPS3 unit installed.

CAUTION

V

Hazardous voltage.

Will cause death or serious injury.

Keep Out.

Qualified personnel only.

Disconnect and lock off all power before 

working on this equipment.

V  

DANGER

11

Содержание TPS3

Страница 1: ...User Manual USA TPS3 Internal Manual Surge Protective Device ...

Страница 2: ...ge rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with...

Страница 3: ...x 7 TPS3 05 and TPS3 06 Module Replacement Instructions 8 TPS3 01 and TPS3 06 Module Installation Instructions MCC 9 Operation 10 TPS3 Control and Diagnostic Display Panel 10 Display Panel with Surge Counter Option 10 Dry Contacts Feature 10 Maintenance 11 Troubleshooting Service 11 Abnormal N G Voltage Indicators 11 Module Replacement Service 11 Technical Support 12 Display Replacement 12 Prevent...

Страница 4: ...ly hazardous situation which if not avoided could result in minor or moderate injury These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the pur...

Страница 5: ...ect plug in type devices surge strips etc Theses devices are intended for installation 10 meters from the panel rationale based on IEEE Cat A location Type4 Surgesuppressioncomponents couldbeabasiccomponent or a complete module Type 4 components can be tested for Type 1 Type 2 or Type 3 applications 2008 NEC Art 285 UL 1449 3 SPD Types Types 1 2 3 4 Based on Location within electrical distribution...

Страница 6: ...rnd Fig 4 K 380Y 220V 3Ø 4W Plus Grnd Fig 2 L 600Y 347V 3Ø 4W Plus Grnd Fig 2 S 400Y 230V 3Ø 4W Plus Grnd Fig 2 AVALABLE SURGE CURRENT RATING Surge Current Rating TPS3 01 TPS3 L1 TPS3 05 TPS3 L5 TPS3 06 TPS3 L6 10 100kA per phase 15 150kA per phase 20 200kA per phase 25 250kA per phase 30 300kA per phase 40 400kA per phase 45 450kA per phase 50 500kA per phase AVAILABLE OPTIONS When Option is Not ...

Страница 7: ...etc NEC and IEEE Std 142 2007 are appropriate standards For sensitive electronics and computer systems ground impedance should be as low as possible When metallic raceway is used as an additional grounding conductor an insulated grounding conductor should be run inside the raceway and sized per the NEC Adequate electrical continuity must be maintained at all raceway connections Do not use isolatin...

Страница 8: ...n it Remove the trim and dead front Remove the two 2 deadfront supports Position the TPS3 unit on the panel base rail so that the TPS3 neutral connector is in front of the panel neutral and the phase tabs are behind the interior bus Slide the unit toward the interior until the four mounting holes line up with the four holes in the base rail Note IfaneutrallugismountedinthepositionwheretheTPS3neutr...

Страница 9: ...A single 14 wire ribbon cable is attached to the display pcb WhentheABCphasesequencechangestoCBA thesingleconnectoris removed from the normal ABC jack and installed in the jack labeled CBA Lock off all power supplying this equipment before working on it Remove the trim and dead front Install the mounting bracket Item 5 to the base rail as shown in Figure 3 using two 2 of the 10 thread forming scre...

Страница 10: ...ified for the purpose and conditions of use Additional instructions for TPS3 01 L1 SPDs including W option Suffix TheWoptionincludesrespositionedphaseconnectiontabsthatallow for wire connections to a circuit breaker within the panelboard This differs from non W models which bolts directly to bus bars The circuit breaker serves as a disconnector device and overcurrent protection to the connecting c...

Страница 11: ...isonnect Lock off all power supplying this equipment before working on it Open unit door and turn the internal disconnect to the off position Remove the neutral lug wire from the disconnect switch Remove the phase wires from the TPS3 06 unit lugs Remove the TPS3 06 unit with the panel and diagnostics display and discard properly Replace units with the new TPS3 06 units Attach the phase lug wires t...

Страница 12: ...on such that the display is visible to user and or protected via an access door A successful installation includes Meets all national and local codes Mount TPS as close as possible to electrical connection Ensure leads are as short and straight as possible Gently twist or tie wrap conductors together wherever possible Ensure that N G bonding hazard warning label is attached to TPS as reminder to i...

Страница 13: ...verysuppression elementinthisSPDismonitored N Gsuppressionelementmonitoring is logic connected to Phase A Service LED red LED illuminates in the event of problems This indicator is logic connected to the Phase LEDs Should a Phase LED go out the Service LED will illuminate and the Audible Alarm will sound Test Tests red Service LED and Audible Alarm and changes state of Dry Contacts Alarm Silence T...

Страница 14: ...round It becomes an ungrounded system Please see previous section regarding SPDs on ungrounded systems Such systems are known to eventually produce abnormally high L G voltages SPDs will attempt to chase this system level overvoltage abnormality until the SPD fails This effect is accelerated on Wye systems where SPDs are designed for grounded systems SPDs for ungrounded systems generally have high...

Страница 15: ...sealing gasket between the display and the enclosure is a key component ensuring weather resistance Replace the gasket whenever the display is removed Preventive Maintenance Inspection and Testing Inspection of the TPS3 SPD unit should be performed periodically to maintain reliable system performance and continued transient voltage surge protection The large variations in operating conditions enco...

Страница 16: ...Siemens Industry Inc Building Technologies Division 5400 Triangle Parkway Norcross GA 30092 888 333 3545 info us siemens com 8 9 10 8171 ...

Отзывы: