UL 1283 required language concerning the installation of EMI Filters

a)  An  insulated  grounding  conductor  that  is  identical  in  size  and 
insulation material and thickness to the grounded and ungrounded 
circuit supply conductors, except that it is green with or without one 
or more yellow stripes, is to be installed as part of the circuit that 
supplies the filter. Reference should be made to Table 250-122 of 
the  National  Electrical  Code  regarding  the  appropriate  size  of  the 
grounding conductor.

b) The grounding conductor mentioned in item a is to be grounded 
to earth at the service equipment or other acceptable building earth 
ground such as the building frame in the case of a high-rise steel-
frame structure.

c) Any attachment-plug receptacles in the vicinity of the filter are 
to be of a grounding type, and the grounding conductors serving 
these receptacles are to be connected to earth ground at the service 
equipment  or  other  acceptable  building  earth  ground  such  as  the 
building frame in the case of a high-rise steel-frame structure.

d) Pressure terminal or pressure splicing connectors and soldering 
lugs used in the installation of the filter shall be identified as being 
suitable for the material of the conductors. Conductors of dissimilar 
metals  shall  not  be  intermixed  in  a  terminal  or  splicing  connector 
where physical contact occurs between dissimilar conductors unless 
the device is identified for the purpose and conditions of use.

Additional instructions for TPS3 01 & L1 SPDs including:
  
W option Suffix:

The W option includes respositioned phase connection tabs that allow 
for wire connections to a circuit breaker within the panelboard. This 
differs from non-W models, which bolts directly to bus bars.

The circuit breaker serves as a disconnector device and overcurrent 
protection to the connecting conductors. The TPS3 SPD includes 
internal overcurrent and overtemperature protective equipment. The 
breaker does not provide  overcurrent protection to the SPD.

Recommended breaker and conductor size is 60A with a 6 AWG 
conductors. Other combinations are possible. Terminal lugs will 
accept 2-14 AWG. Breaker size should be at least 20A. All applicable 
codes must be followed.

Circuit breaker MUST be located immediately adjacent to SPD to 
minimize lead lengths. Move or adjust breaker positions as appropriate. 
Every effort must be taken to reduce lead lengths. Failure to install 
short leads will degrade SPD performance.

Install appropriate circuit breaker in panelboard.

Prior to installing SPD, rotate and tighten lug terminals toward breaker 
location. 

Mount the SPD using supplied hardware.

Connect the neutral connection by wire or bracket as appropriate.

Install conductors, short and straight as possible. Use gentle radius 
on any bends. Do not kink wires. Prevent wires from encroaching 
breaker locations.

Torque all connections to the values specified on the installation and 
maintenance instruction label affixed to the rear of the dead front.

Replace dead front supports and trim.

Energize breaker and confirm proper SPD operation.

7

Содержание TPS3

Страница 1: ...User Manual USA TPS3 Internal Manual Surge Protective Device ...

Страница 2: ...ge rating of the SPD and system must be verified before energizing the SPD Failure to follow these guidelines can lead to abnormally high voltages at the SPD This may cause the SPD to fail The warranty is voided if the SPD is incorrectly installed and or if the neutral conductor in the service entrance equipment or downstream of separately derived systems is not bonded to ground in accordance with...

Страница 3: ...x 7 TPS3 05 and TPS3 06 Module Replacement Instructions 8 TPS3 01 and TPS3 06 Module Installation Instructions MCC 9 Operation 10 TPS3 Control and Diagnostic Display Panel 10 Display Panel with Surge Counter Option 10 Dry Contacts Feature 10 Maintenance 11 Troubleshooting Service 11 Abnormal N G Voltage Indicators 11 Module Replacement Service 11 Technical Support 12 Display Replacement 12 Prevent...

Страница 4: ...ly hazardous situation which if not avoided could result in minor or moderate injury These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the pur...

Страница 5: ...ect plug in type devices surge strips etc Theses devices are intended for installation 10 meters from the panel rationale based on IEEE Cat A location Type4 Surgesuppressioncomponents couldbeabasiccomponent or a complete module Type 4 components can be tested for Type 1 Type 2 or Type 3 applications 2008 NEC Art 285 UL 1449 3 SPD Types Types 1 2 3 4 Based on Location within electrical distribution...

Страница 6: ...rnd Fig 4 K 380Y 220V 3Ø 4W Plus Grnd Fig 2 L 600Y 347V 3Ø 4W Plus Grnd Fig 2 S 400Y 230V 3Ø 4W Plus Grnd Fig 2 AVALABLE SURGE CURRENT RATING Surge Current Rating TPS3 01 TPS3 L1 TPS3 05 TPS3 L5 TPS3 06 TPS3 L6 10 100kA per phase 15 150kA per phase 20 200kA per phase 25 250kA per phase 30 300kA per phase 40 400kA per phase 45 450kA per phase 50 500kA per phase AVAILABLE OPTIONS When Option is Not ...

Страница 7: ...etc NEC and IEEE Std 142 2007 are appropriate standards For sensitive electronics and computer systems ground impedance should be as low as possible When metallic raceway is used as an additional grounding conductor an insulated grounding conductor should be run inside the raceway and sized per the NEC Adequate electrical continuity must be maintained at all raceway connections Do not use isolatin...

Страница 8: ...n it Remove the trim and dead front Remove the two 2 deadfront supports Position the TPS3 unit on the panel base rail so that the TPS3 neutral connector is in front of the panel neutral and the phase tabs are behind the interior bus Slide the unit toward the interior until the four mounting holes line up with the four holes in the base rail Note IfaneutrallugismountedinthepositionwheretheTPS3neutr...

Страница 9: ...A single 14 wire ribbon cable is attached to the display pcb WhentheABCphasesequencechangestoCBA thesingleconnectoris removed from the normal ABC jack and installed in the jack labeled CBA Lock off all power supplying this equipment before working on it Remove the trim and dead front Install the mounting bracket Item 5 to the base rail as shown in Figure 3 using two 2 of the 10 thread forming scre...

Страница 10: ...ified for the purpose and conditions of use Additional instructions for TPS3 01 L1 SPDs including W option Suffix TheWoptionincludesrespositionedphaseconnectiontabsthatallow for wire connections to a circuit breaker within the panelboard This differs from non W models which bolts directly to bus bars The circuit breaker serves as a disconnector device and overcurrent protection to the connecting c...

Страница 11: ...isonnect Lock off all power supplying this equipment before working on it Open unit door and turn the internal disconnect to the off position Remove the neutral lug wire from the disconnect switch Remove the phase wires from the TPS3 06 unit lugs Remove the TPS3 06 unit with the panel and diagnostics display and discard properly Replace units with the new TPS3 06 units Attach the phase lug wires t...

Страница 12: ...on such that the display is visible to user and or protected via an access door A successful installation includes Meets all national and local codes Mount TPS as close as possible to electrical connection Ensure leads are as short and straight as possible Gently twist or tie wrap conductors together wherever possible Ensure that N G bonding hazard warning label is attached to TPS as reminder to i...

Страница 13: ...verysuppression elementinthisSPDismonitored N Gsuppressionelementmonitoring is logic connected to Phase A Service LED red LED illuminates in the event of problems This indicator is logic connected to the Phase LEDs Should a Phase LED go out the Service LED will illuminate and the Audible Alarm will sound Test Tests red Service LED and Audible Alarm and changes state of Dry Contacts Alarm Silence T...

Страница 14: ...round It becomes an ungrounded system Please see previous section regarding SPDs on ungrounded systems Such systems are known to eventually produce abnormally high L G voltages SPDs will attempt to chase this system level overvoltage abnormality until the SPD fails This effect is accelerated on Wye systems where SPDs are designed for grounded systems SPDs for ungrounded systems generally have high...

Страница 15: ...sealing gasket between the display and the enclosure is a key component ensuring weather resistance Replace the gasket whenever the display is removed Preventive Maintenance Inspection and Testing Inspection of the TPS3 SPD unit should be performed periodically to maintain reliable system performance and continued transient voltage surge protection The large variations in operating conditions enco...

Страница 16: ...Siemens Industry Inc Building Technologies Division 5400 Triangle Parkway Norcross GA 30092 888 333 3545 info us siemens com 8 9 10 8171 ...

Отзывы: