3. Installing Unit

3.1. If present, remove existing door by first withdrawing its 

       hinge pins and then closing it halfway before sliding it  

       off its hinges. 

3.2. Remove Intermediate angle by removing the screw

       which fastens it to the Separator Angle and tipping  

       slightly to remove formed tab at top from slot in shelf

       bracket above.

3.3. If necessary, install unit support assembly by inserting  

       shelf brackets at a slight angle into the appropriate

       holes in the vertical bus support angle and snapping 

       into place. Secure support assembly with the two screws

       provided. One screw fastens the right-hand shelf bracket

       to the vertical bus support angle. The second screw  

       fastens the separator angle to the left side of the struc- 

       ture. For additional information on unit support installa- 

       tion, please refer to section 8.2.

3.4. If necessary, remove appropriate unit stab hole covers.

3.5. Install unit door by sliding it onto the hinges while half

       open. Once on the hinges, open the door completely

       and insert hinge pins. 

3.6. Place plug-in unit inside of enclosure (Figure 6a). 

3.6.1. With the handle in the PARK position, slide unit into

          place on support assembly.  

3.6.2. Slightly tilt the front of the unit downwards in order to 

slide the back of the unit over the shelf brackets. 

3.6.3. Once the unit has been pushed in as far as it can go,  

close the racking lever in top barrier plate

(Figure 6b).

3.6.4. Engage locking latch at lower left of the unit to the

separator angle and tighten it using a flat-head 

screwdriver (latch is shown above in Figure 4 on

page 4).

Figure 6a - Placing Unit on Support Assembly

                   and in test position 

Figure 6b - Closing Racking Lever

Содержание tiastar MCC

Страница 1: ...tallation Instructions For Motor Control Center MCC Units E87010 A0401 T002 A5 MCC tiastarTM Motor Control Center Page 1 of 12 Installation Instructions July 2015 Siemens Industry Inc 5300 Triangle Parkway Norcross GA 30092 A5E33045207A ...

Страница 2: ... WARNING For the purpose of this manual and product labels WARNING indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION For the purpose of this manual and product labels CAUTION indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury QUALIFIED PERSON For the purposes of this manual and produ...

Страница 3: ...lot device panel 3 Top barrier plate 4 Pilot device mounting hole used when mounting directly to unit 5 Operating handle 6 Racking lever 7 Swing plate 8 Terminal block Figure 1 Unit Components 8 4 8 3 8 1 8 2 1 Pin type door hinge 2 Shelf bracket 3 Separator angle 4 Intermediate angle Figure 2 Unit Support Components If damage or loss is discovered file a claim with the carrier who delivered the c...

Страница 4: ...g lever in the top barrier plate See Figure 6a 2 6 Disconnect control and load wiring 2 7 Remove unit by slightly tilting the front of the unit downward and sliding it out This is to insure that the unit doesn t get caught on the shelf bracket 2 8 If rearranging units of different sizes perform the following tasks 2 8 1 Remove all unit support assemblies by unfasten ing the screws for each assembl...

Страница 5: ...he second screw fastens the separator angle to the left side of the struc ture For additional information on unit support installa tion please refer to section 8 2 3 4 If necessary remove appropriate unit stab hole covers 3 5 Install unit door by sliding it onto the hinges while half open Once on the hinges open the door completely and insert hinge pins 3 6 Place plug in unit inside of enclosure F...

Страница 6: ...nctions 4 4 Unit must turn ON Unit must turn OFF Unit must indi cate TRIP Unit must RESET 4 5 Operate the handle from the ON position to the OFF position and disconnect will turn OFF 4 6 Return the handle to the ON position and the dis connect will turn ON If it does not rotate the sleeve slightly clockwise and try again Repeat this step until the handle assembly turns the unit ON Then repeat step...

Страница 7: ... current from the motor nameplate data Use screwdriver to set indicator on adjustment screw to the appropriate position 6 7 2 For maximum protection the trip position should be set as low as possible Turn the adjustment screw counterclockwise to successively lower positions until the breaker trips on motor starting After this position is determined turn the adjust ment screw clockwise to the next ...

Страница 8: ...sting hinge if present in the 6 in space See Figure 11 2 Install the unit support bracket per Adding To A Blank Unit Space on page 4 3 Locate and install the new hinge with the two mounting screws 4 Install the door using two new hinge pins supplied with the unit Unit Access For Maintenance 1 Remove the unit from the structure 2 Loosen screw B shown in Figure 12 3 Lift the handle bracket and pull ...

Страница 9: ...9 of 12 Section 7 continued 6 Unit Access for Maintenance 150 250A Circuit Breaker Units Handle Mechanism Screw D Unit Access for Maintenance 1 Remove unit from structure 2 Remove screws D shown in figure 13 qty 4 3 Remove the handle mechanism from the unit 4 When reinserting the handle mechanism the handle must be in the OFF position ...

Страница 10: ...ps 1 4 for each phase Clamp Assembly Notice To be installed on 600A or 800A vertical bus only 1 Connect tie bar riser by sliding bolt H through tie bar and riser Fasten with washer I and torque nut J and bolt H securing to 280 in lbs 2 Loosely assemble the clamp assembly making sure that clamp spring E will compress against bar F when the the bolt is drawn tight 3 Slide carriage bolt B through one...

Страница 11: ...bars as shown in Figure 16 Bundle all cables together above circuit breaker with wire ties Figure 17 Units with smaller circuit breakers 300A positioned anywhere within a section Carefully bend L1 L2 and L3 cables towards the vertical wireway and bundle all three together with a provided wire tie within unit space In 12 increments secure the bundled cables to the MCC back panel with a provided wir...

Страница 12: ...als 11 lb in Apply 2 3 of standard tightening torque 10 3 400A and 600A fixed mounted unit clamp assembly bolts should be tightened to 280 in lbs 10 4 Follow torque requirements of individual components for motor load connections 11 Additional Resources 11 1 MCC Installation Guide E87010 A0156 T003 A5 MCC 11 2 Unit Support Assembly Guides E87010 A0279 T002 A5 MCC E87010 A0280 T002 A5 MCC E87010 A0...

Отзывы: