Table A: Automatic Star - Delta Starter Type Ref: 3TE7291-0A
Motor
Output
at
415V
(kW/HP)
I(fl)
4 Pole
Squirrel cage
motor
Contactor Line
Contactor Delta
Contactor Star
Recommended
Overload relay at 50ºC
Recommended
Fuse Switch
Recommended Cu
Cable size
(mm
2
)
Line
cur-
rent
(A)
Phase
cur-
rent
(A)
Type Reference
Type - Code
Relay
Range
(A)
Type
Back up
HRC
fuse
rating(A)
Incoming
(from
supply)
Outgoing
(to motor)
7.5/10
16
9.2
3TS32 10-0A*08K 3TS32 01-0A*08K 3TS32 10-0A*08K
3UW51 02-1J
6.3-10
3KL812
20
2.5
1.5
9.3/12.5 19.5 11.2 3TS32 10-0A*08K 3TS32 01-0A*08K 3TS32 10-0A*08K 3UW51 02-1K
8-12.5
3KL812
25
4
2.5
11/15
23
13.2 3TS32 10-0A*08K 3TS32 01-0A*08K 3TS32 10-0A*08K 3UW51 02-2A
10-16
3KL812
25
4
2.5
15/20
32
18.4 3TS33 00-0A*08K 3TS33 00-0A*08K 3TS32 10-0A*08K 3UW52 02-2B 12.5-20 3KL812
50
10
4
18.5/25 38.5 22.2 3TS33 00-0A*08K 3TS33 00-0A*08K 3TS32 10-0A*08K 3UW52 02-2C
16-25
3KL812
50
10
4
* Code for operating coil voltage 50 Hz (Z6 for 200-400V, R0 for 415V)
Other Tables:
Star-Delta Timer:
AC Input Voltage
MLFB
230V-400V
380V-440V
3RP15 76-1NP20 8K
3RP15 76-1NM20 8K
Other Tables:
Motor Output at
415V
Type
4)
kW
HP
(ASD Starter)
7.5
10
3TE72910AW74
9.3
12.5
3TE72910A.75
11
15
3TE72910A.77
15
20
3TE72910A.78
18.5
25
3TE72910A.79
4)
Enter code for operating coil voltage, 50 Hz (B for 200-400V, W for 415V)
Spares:
Sr.
No.
Description
Order No.
1
Contactor 3TS32 10..
Refer Table A
2
Contactor 3TS32 01..
Refer Table A
3
Contactor 3TS33 00..
Refer Table A
4
Relay 3UW51..
Refer Table A
5
Relay 3UW52..
Refer Table A
6
Coil for 200-400V
3TY7 403-0AZ6
7 Coil for 415V
3TY7 403-0AR0
8 1NO Contact Block
3SB5420-0B
9
Aux Block 1NO
3TX4010-2A
10
Aux Block 1NC
3TX4001-2A
10 ‘ON’ & ‘OFF’ Push Button
#
# – contact sales
Replacement of coil
Fig. 7: Contactor – Relay Connection
Hook on relay for
engagement
Contactor
outgoing terminals
Содержание TE7291-0A Series
Страница 5: ...Notes ...