Application Manual
Nr. 08
Reception area – room automation
Synco™
& Gamma
44
Device list
Key
Product no. and description
Stock number
1
AQR2576 room sensor, basic module with CO
2
S55720-S203…206
AQR2532 room sensor, temperature
S55720-S136
2
N 141/02 KNX/DALI gateway
5WG1 141-1AB02
3
UP258E21 presence detector with constant light control
5WG1 258-2EB21
4
UP 588 color touch panel
5WG1 588-2AB13
Optional
Key
Product no. and description
Stock number
5
N 125/12 power supply
5WG1 125-1AB12
6
N 151 IP viewer
5WG1 151-1AB01
5a
OZW772.x webserver
OZW772.x
Variants
Key
Product no. and description
Stock number
1a
QMX3.P70 room operator unit, temperature, humidity, CO
2
S55624-H104
1b
QMX3.P30 room operator unit, temperature
S55624-H103
2a
N 141/31 KNX/DALI gateway, twin
5WG1 141-1AB31
Ventilation control
A
ECE01 U2B HQ
Room-supply air temperature cascade control with plate
heat recovery system, recirculated air damper, air
heating coil and air cooling coil
·
7-day time switch with holiday/special day program
·
Recirculated air operation (Precomfort) and outside
air operation (Comfort)
·
Control of supply and extract air fans
·
Room- (extract air)-supply air temperature cascade
control with minimum and maximum limitation of
supply air temperature
·
Control of supply air temperature via the heat recovery
system, the air heating coil valve and the air cooling
coil valve in sequence
·
Frost protection with frost protection sensor on the
air side and controller-internal 2-phase frost protection
function
·
Monitoring of supply and extract air fans with
differential pressure switches
·
Monitoring of supply and extract air filters with
differential pressure switches
·
Sustained mode during nonoccupancy times
·
Night cooling with outside air
·
Summer/winter compensation, preheat function,
activation of air heating coil pump at low outside
temperatures
·
Heat recovery system with Maximum Economy
Changeover (MEU)
·
Control of air heating coil pump, with pump kick
·
Fault relay for all fault status messages
The temperature is acquired in every room and controlled via the supply air. The ventilation controller controls the
supply air temperature and the proportion of fresh air. The heating plant is controlled depending on the heat request
from the ventilation controller plus the outside temperature. The refrigeration plant is controlled depending on the
cooling energy request from the ventilation controller. Nonoccupancy times are reported by the presence detector or
can be set in a time program. During these periods of time, the room temperatures are automatically lowered.