Application Manual
Nr. 06
Hotel rooms – room automation
Synco™
& Gamma
35
Radiator in the room and the bathroom, sun protection, presence-
dependent switching off of lighting and power supply
Features
·
Individual room temperature control, heating
·
Two control loops for the room and the bathroom
·
Window contact – central detection of open windows
·
Detection of presence via hotel card switch
·
Presence- and time-dependent control of HVAC, lighting, sun protection, and power
supply to the room
·
Central operation and display of HVAC, lighting, and sun protection
·
Pushbuttons for "SOS", "Make up room", and "Do not disturb"
Room setup
1.
UP 227 room operator unit:
The UP 227 acquires the room temperature and sends the temperature
value, the setpoint shift and the operating mode to the AP 562/02 via the KNX bus. The UP 227 can also
be used to control the lighting and the blinds.
2.
AQR2532 room sensor with AQR2570 basic module:
The AQR acquires and controls the room
temperature in the bathroom via the radiator.
3.
AP 562/02 valve actuator:
The AP 562/02 drives the radiator valve. It receives the positioning signal from
the UP 227 or the AQR controller.
4.
AP 118 automation module box:
The AP 118 has a socket for room automation modules type RS or RL.
5.
RS 525/23 universal dimmer:
The RS 525/23 features a relay contact to dim a lighting group up to 250
VA.
6.
RL 521/23 blind actuator:
The RL 521/23 features 2 relay contacts to control blinds.
7.
RS 510/23 binary output, 2-fold:
The RS 510/23 features 2 relay contacts to switch electric circuits.
8.
S 290 door/window contact:
The window contact causes the room operating mode to change to
Protection when the window is open.
9.
DELTA pushbutton:
The pushbutton is connected to the UP 220 and is used to control the lighting.