10 Electrical
connections
10.1 Connection rules
Synco 200 terminal
connection concept
The following illustration shows the terminal block for the SEZ220 signal converter and
its connection terminals:
M
M
M
M
M
G1
G0
Y2
G0 G0
X1
X2
G1 X3
X4
G1
X5
G1
G0
Y1
G
G
Passiver Fühler/
Passiver Geber
Aktiver Fühler/
Aktiver Geber
Ausgangssignal
DC 0...10 V
Systemspeisung
AC 24 V
Doppelklemme
mit interner
Verbindung
Kleinspannungsseite
Netzspannungsseite
51
46
A
0
7
8
d
e
Terminal
Used for ...
Xx, M
Passive sensors and signal sources.
G1, Xx , M
Active sensors and signal sources.
Yx
Provide measured values to control devices, sequential control of
pumps, valves, fans, etc..
G und G0
AC 24 V power supply.
Terminal assignment
Only one solid or one stranded wire can be connected per terminal.
Note
Connection procedure
with spring cage
terminals
1.
2.
3.
31
40
Z
13
1. Strip wire for 7 to 8 mm.
Steps
2. Locate wire and screwdriver size 0 or 1.
3. Push screwdriver down and, at the same time, insert the wire.
4. Remove
the
screwdriver.
35 / 46
Siemens
SEZ220 signal converter
CE1P5146en
Building Technologies
Electrical connections
02.06.2008